HomeMy WebLinkAboutSUB201400101 Soil Report 2018-06-19underhilI ENGINEERING geotechnical I geothermal I geoconstruction Letter of Transmittal June 19, 2018 Mr. John Anderson, PE, Civil Engineer II Community Development Dept. County of Albemarle, Virginia 401 McIntire Road Charlottesville, VA 22902-2702 Subject: Documentation Regarding Earthwork and Pavement Subgrade Testing Services, Hollymead Towncenter Block C4, Albemarle County, Virginia (Underhill Engineering Project No. 16009.02) (Albemarle County RE: SUB2014-00101) Dear Mr. Anderson: Underhill Engineering, LLC (Underhill) is pleased to present this transmittal consisting of documentation regarding Earthwork and Pavement Subgrade Testing services. This transmittal includes daily field records, soil laboratory Proctor data, Underhill's California Bearing Ratio (CBR) Testing report dated March 15, 2017, and Underhill's letter dated March 7, 2018, summarizing the services provided. This information is provided as requested by our client, Mr. Katurah Roell, copied here. Note that Underhill's March 15, 2017 report includes a figure indicating the approximate test locations where we excavated through the existing base course to obtain the soil samples for the CBR tests. Base course thickness observed at the test locations met the required aggregate base course thickness as indicated in the Dominion Engineering project documents last revised December 17, 2013. T: 434.531.2565 327 W. Main Street, Suite 2, Charlottesville, VA 22903 underhillengineering.com Underhill has endeavored to complete the services identified herein in a manner consistent with that level of care and skill ordinarily exercised by members of the profession currently practicing in the same locality and under similar conditions as this project. No other representation, express or implied, is included or intended, and no warranty or guarantee is included or intended in this report. Sincerely, UNDERHILL ENGINEERING, LLC r O. Christopher Webster, PE z e ors 2018.06.19 20:25:32 -04:00 O. Christopher Webster, PE Principal Exhibits: 1. Moisture Density Relationship, Sample 1, 21A Dense -Graded Aggregate Base Course 2. Compaction Test Report, 4-11-16 through 4-15-16 3. Compaction Test Report, 5-27-16 4. Summary of Laboratory Testing, Samples S-1, S-2, and S-3 S. California Bearing Ratio (CBR) Testing Report dated 3-15-2017 (9 pages) 6. Letter Regarding Services Provided and Suitability of Pavement Section dated 3-7-18 cc: Mr. Katurah Roell- Town Properties, LLC Project 16009.02 / June 19, 2018 2 Underhill Engineering, LLC 134.0 133.0 132.0 131.0 130.0 WON U Q >-128.0 U5 z w }127.0 ry 1 126.0 125.0 124.0 123.0 122.0 121.0 3 \ \ \ \ \ \ \ \ \ \ \ 5 7 9 11 13 WATER CONTENT, % Sample Description: DENSE GRADED AGGREGATE, contains Assumed Specific Gravity: crushed stone, gray Uncorrected Max. Dry Density (pcf) Uncorrected Opt. Moisture (%): 15 2.76 130.4 8.8 Sample Source: Sample 1 Test Methods: ASTM D698 Method C Corrected Max. Dry Density (pcf): 133.6 Oversize Fraction Sieve Size: 3/4 in. Corrected Opt. Moisture (%): 8.1 Percent Oversized Retained: 10% Liquid Limit (LL): NP Comments: Plasticity Index (PI): NP Borrow Source: Rockydale Quarry, Albemarle % Retained #4 Sieve: County, VA % Passing # 200 Sieve: Date: 4-20-16 Reviewed By: DS MOISTURE DENSITY RELATIONSHIP Schnabel Project: Underhill Engineering 16009.02 E N G I N E E R I N G Charlottesville, VA Contract: 15643010 Testing Lab: CVILL Project Name: Project Number: Rep: Gauge ID Number: Dates: Hollymead Town Center - Block 4 15643010 J. Bossinger, B. Cathey I, Q April 11 - 15, 2016 Field Density Test Summary Test Date: Density Standard: Moisture Standard: Lab Reference: Optimum Moisture (%): Maximum Dry Density: 95% of Maximum Dry Density 04/11/16 04/15/16 2009 1915 679 617 1 2 8.1 16.4 133.E 109.6 126.9 104.1 Test Number Date Tested Elevation (ft) Probe Depth (inches) Lab Ref. Wet Density (PCF) Moisture Content (%) Dry Density (PCF) Maximum Dry Density (PCF) Percent Compaction (%) Remarks / Location 1 04/11/16 583 12 2 - 15.5 - - - Over Sanitary Sewer in Laurel Pk Ln, STA 0+20 as shown in profile on Drawing SP7. Density not recorded due to crushed stone and construction debris mixed with soil. 2 04/11/16 583 12 2 1. _ 3 04/11/16 585 12 2 15.6 4 04/11/16 586 12 2 17.0 - 5 04/11/16 587 12 2 17.0 - 6 04/15/16 598 12 1 139.2 4.5 133.2 133.6 99.7% Over 8" W in Laurel Pk Ln, North of MH5 7 04/15/16 594 12 1 134.4 3.6 129.7 133.6 97.0% Over 8" W in Laurel Pk Ln, North of MH4 Lab Reference Key: Dense -graded aggregate, gray, imported from Rockydale Quarry (Standard Proctor) On -site soils visually classifying as Sandy Silt (ML) contains mica and gravel, brown (One -Point Proctor) Page 1 of 1 Project Name: Project Number: Rep: Gauge ID Number: Dates: Hollymead Town Center - Block 4 15643010 N. Silman X 05/27/16 Field Density Test Summary Test Date: Density Standard: Moisture Standard: Lab Reference: Optimum Moisture (%): Maximum Dry Density: 95% of Maximum Dry Density Test Number Date Tested Elevation Elevation (ft) Probe Depth (inches) Lab Ref. Wet Density (PCF) Moisture Content (%) Dry Density (PCF) Maximum Dry Density (PCF) Percent Compaction (%) Remarks / Location 8 05/27/16 583 10 1 137.4 6.6 128.8 133.6 96.4 Over 24" HDPE STA -0+15 between EX ST-61 and EX ST-62 on Laurel Park Lane at Timberwood Blvd. 9 1 05/27/16 584 12 1 1 137.9 6.5 129.5 133.6 96.9 10 05/27/16 585 10 1 137.2 6.3 129.6 133.6 97.0 Lab Reference Key: Dense -graded aggregate, gray, imported from Rockydale Quarry (Standard Proctor) Page 1 of 1 appendix Summary Of Laboratory Tests Sheet 1 of 1 Project Number: Sample y � -_ Depth c w >, a d Boring ft Sample Description of Soil R 0 d o N \ 3 \ Ui o N No. Type Specimen H e H rn a E" c w Elevation H o H o r E w E o o a > ft y aw av 0 x c - c c V co _ H e z° a z° e z �o 0U UU Ua U 0.0- 0.0 SILTY SAND (SM), fine to coarse grained S-1 Bulk sand, contains rock fragments and mica, RICH 43.1 65.8 6.9 107.5 17.3 17.2 107.0 0.3 12.9 red -brown (Visual) 0.0 SILTY SAND (SM), fine to coarse grained S-2 Bulk sand, contains rock fragments and mica, RICH 36.8 59.4 8.5 112.9 15.3 15.3 111.7 0.0 18.5 red -brown (Visual) 0.0 SILTY SAND (SM), fine to coarse grained S-3 Bulk sand, contains rock fragments and mica, RICH 43.0 61.9 10.5 108.0 16.8 15.4 111.6 0.0 18.5 red -brown (Visual) Notes: 1. Soil tests in general accordance with ASTM standards. 2. Soil classifications are in general accordance with ASTM D2487(as applicable), based on testing indicated and visual Sch n a b e! classification. 12 3. Key to abbreviations: NP=Non-Plastic; -- indicates no test performed E N G I N E E R I N G Project: Hollymead Town Center 16009.02 Albermarle County, VA underhilI ENGINEERING geotechnical I geothermal I geoconstruction March 15, 2017 Mr. Katurah Roell Town Properties, LLC 325 Barracks Hill Charlottesville, VA 22901 Subject: California Bearing Ratio (CBR) Testing, Hollymead Towncenter Block C4, Albemarle County, Virginia (Underhill Engineering Project No. 16009.02) Dear Mr. Roell: Underhill Engineering, LLC (Underhill) is pleased to present this report, summarizing the results of California Bearing Ratio (CBR) testing for this project. These services are provided in accordance with Underhill's Services Agreement with you dated March 1, 2016, and your authorization of January 21, 2017. Laboratory Test Results Three bulk samples were retrieved by Underhill from on site for soil laboratory testing. The approximate sample locations are shown in Figure 1. Soil laboratory testing assigned by Underhill consisted of the following: ■ Three gradation tests (ASTM D422). ■ Three Standard Proctor tests (ASTM D698). ■ Three California Bearing Ratio tests (VTM-8). A summary of the soil laboratory test results, gradation curves, and moisture -density relationships follows the text of this report. CBR tests results varied from 12.9 to 18.5 with zero to 0.3 percent swell. We understand a design CBR value of 10 was considered for the design pavement section. The as -tested CBR values exceed this design value. Underhill has endeavored to complete the services identified herein in a manner consistent with that level of care and skill ordinarily exercised by members of the profession currently practicing in the same locality and under similar conditions as this project. No other representation, express or implied, is included or intended, and no warranty or guarantee is included or intended in this report. T: 434.531.2565 108 South First Street, Charlottesville, VA 22902 underhillengineering.com Thank you for the opportunity to provide our services. If you have any questions or require additional information, please do not hesitate to contact me. Sincerely, UNDERHILL ENGINEERING, LLC O. Christopher Webster, PE Principal Exhibit A: Soil Laboratory Test Results Project 16009.02 / March 15, 2017 2 Underhill Engineering, LLC Soil Laboratory Test Results Figure 1: Location Plan Summary of Soil Laboratory Tests Gradation Curves (1 sheet) Moisture -Density Relationships (3 sheets) Project 16009.02 / March 15, 2017 Underhill Engineering, LLC U) C) D r m Z D O C/) 0 C) o D 'A r aPf { n s awl, C* Ln f — CD Q ,� J - �- L` eaf T i WALL rip era I CD yI �f 3CD cc xSto sf I 1 ��fqJ O CD Q O co .. O CD ,�k�► s y N r CD 0 ti C 77 v ti m Z CD $ to �m l< �z < m z �_ o M m v" 2Z 3 L7 Summary of Soil Laboratory Tests Sample No. S-1 S-2 S-3 Sample Type BULK BULK BULK Description, SILTY SAND (SM) SILTY SAND (SM) SILTY SAND (SM) Symbol USCS (visual) (visual) (visual) % Passing No. 200 Sieve 43.1 36.8 43.0 % Passing No. 40 Sieve 65.8 59.4 61.9 % Passing No. 4 Sieve 6.9 8.5 10.5 Max. Dry Density (pcf) 107.5 112.9 108.0 Optimum Moisture 17.3 15.3 16.8 Content (%) CBR Value 12.9 18.5 18.5 (soaked) Swell (%) il 0.3 Zero Zero Testing provided by Underhill's subconsultant laboratory, Schnabel Engineering Project 16009.02 / March 15, 2017 Underhill Engineering, LLC U.S. SIEVE OPENING IN INCHES U.S. SIEVE NUMBERS I HYDROMETER n 1 1/9 4 R in in in ZZn inn 9nn 100 95 90 85 80 75 70 65 x 60 (D w 55 m 50 ry w 45 z LL 1.- 40 z w U 35 Of w 0 30 25 20 15 10 5 0 100 10 1 0.1 GRAIN SIZE IN MILLIMETERS 0.01 0.001 COBBLES GRAVEL SAND SILT OR CLAY coarse fine coarse medium fine Specimen Sample Description LL PL PI Cc Cu N SILTY SAND (SM), fine to coarse grained sand, contains rock o0 S-1 0.0 ft fragments and mica, red -brown (Visual) 0 N m S-2 0.0 ft SILTY SAND (SM), fine to coarse grained sand, contains rock fragments and mica, red -brown (Visual) -- -' a a SILTY SAND (SM), fine to coarse grained sand, contains rock WE ♦ S-3 0.0 ft fragments and mica, red -brown (Visual) Specimen Test Method Testing Lab D100 D60 D30 D10 %Gravel %Sand %Silt %Clay • S-1 0.0 ft ASTM D422 RICH 38.1 0.25 -- -- 6.9 50.0 43.1 a o m S-2 0.0 ft ASTM D422 RICH 64 0.45 -- -- 8.5 54.7 36.8 Q ♦ S-3 0.0 ft ASTM D422 RICH 38.1 0.35 -- -- 10.5 46.5 43.0 GRADATION CURVES Project: Hollymead Town Center 16009.02 Contract: 110.0 109.0 108.0 107.0 106.0 -105.0 a z104.0 w 0 ry '103.0 102.0 101.0 100.0 99.0 98.0 11 13 15 17 19 21 WATER CONTENT, % Sample Description: SILTY SAND (sM), fine to coarse grained Assumed Specific Gravity: sand, contains rock fragments and mica, Max. Dry Density (pcf): red -brown (Visual) Opt. Moisture (%): Sample Source: S-1, 0.0 ft Test Methods: ASTM D698 Method B Liquid Limit (LL): -- Plasticity Index (PI): -- % Retained #4 Sieve: 6.9 % Passing # 200 Sieve: 43.1 Comments: 23 2.60 107.5 17.3 Date: 2-03-17 Reviewed By: DS MOISTURE DENSITY RELATIONSHIP Project: Hollymead Town Center 16009.02 Contract: Testing Lab: RICH 116.0 115.0 114.0 113.0 112.0 108.0 107.0 106.0 105.0 104.0 9 \ \ \ \ \ 11 13 15 17 19 WATER CONTENT, % Sample Description: SILTY SAND (sM), fine to coarse grained Assumed Specific Gravity: sand, contains rock fragments and mica, Max. Dry Density (pcf): red -brown (Visual) Opt. Moisture (%): Sample Source: S-2, 0.0 ft Test Methods: ASTM D698 Method C Liquid Limit (LL): -- Plasticity Index (PI): -- % Retained #4 Sieve: 8.5 % Passing # 200 Sieve: 36.8 Comments: 21 2.63 112.9 15.3 Date: 2-03-17 Reviewed By: DS MOISTURE DENSITY RELATIONSHIP Project: Hollymead Town Center 16009.02 Contract: Testing Lab: RICH 112.0 111.0 110.0 109.0 108.0 -107.0 a z106.0 w 0 ry '105.0 104.0 103.0 102.0 101.0 100.0 11 13 15 17 19 21 WATER CONTENT, % Sample Description: SILTY SAND (sM), fine to coarse grained Assumed Specific Gravity: sand, contains rock fragments and mica, Max. Dry Density (pcf): red -brown (Visual) Opt. Moisture (%): Sample Source: S-3, 0.0 ft Test Methods: ASTM D698 Method C Liquid Limit (LL): -- Plasticity Index (PI): -- % Retained #4 Sieve: 10.5 % Passing # 200 Sieve: 43.0 Comments: 23 2.61 108.0 16.8 Date: 2-03-17 Reviewed By: DS MOISTURE DENSITY RELATIONSHIP Project: Hollymead Town Center 16009.02 Contract: Testing Lab: RICH underhilI ENGINEERING geotechnical I geothermal I geoconstruction March 7, 2018 Mr. Katurah Roell Town Properties, LLC 325 Barracks Hill Charlottesville, VA 22901 Subject: Construction Engineering and Testing Services in Pavement Areas, Hollymead Towncenter Block C4, Albemarle County, Virginia (Underhill Engineering Project No. 16009.02) Dear Mr. Roell: Underhill Engineering, LLC (Underhill) is pleased to present this letter, summarizing Underhill's services for the above -referenced project. These services are provided in accordance with Underhill's Services Agreement with you dated March 1, 2016. Underhill's services for the project included construction observation and testing in the new pavement areas. These services included observation and testing of utility backfill including fill placed in areas of pavements, observations of subgrades, observations of aggregate, and California Bearing Ratio (CBR) testing. We provided our services from April 11, 2016, through March 15, 2017. Soil laboratory test results consisting of soil classification, Standard Proctor tests, and CBR test results were provided to you in our report dated March 15, 2017. Note that the majority of the site pavement subgrades are in areas of cut consisting of generally firm SILTY SAND (SM) residuum containing rock fragments. The earthwork observation and testing of compacted structural fill placed in the pavement areas as provided by Underhill indicated that the compacted structural fill observed and tested to be compacted to at least 95 percent of the maximum dry density in accordance with ASTM D698, Standard Proctor, and in general accordance with the project documents prepared by Dominion Engineering last revised December 17, 2013. Also, CBR testing indicated the three samples of on -site soils to exhibit laboratory CBR values of 12.9, 18.5, and 18.5; each exceeding the design CBR value of 10. Based on our observations and testing, including the high CBR test results obtained, we consider the project's constructed pavement section to be suitable for the design traffic. T: 434.531.2565 327 W. Main Street, Suite 2, Charlottesville, VA 22903 underhillengineering.com Underhill has endeavored to complete the services identified herein in a manner consistent with that level of care and skill ordinarily exercised by members of the profession currently practicing in the same locality and under similar conditions as this project. No other representation, express or implied, is included or intended, and no warranty or guarantee is included or intended in this report. Thank you for the opportunity to provide our services. If you have any questions or require additional information, please do not hesitate to contact me. Sincerely, UNDERHILL ENGINEERING, LLC /'�-* ,�— O. Christopher Webster, PE Principal l40#N 4V' LTH Ow � L� 0 0. CIT ISTOPIOR U W f?85'lFdt Lic. No. 019910 .a� 0 �srONALG �'rM�as►N�� Project 16009.02 / March 7, 2018 2 Underhill Engineering, LLC