HomeMy WebLinkAboutSUB201800171 Review Comments Appeal to BOS 2018-11-16November 16, 2018
Timmons Group
Attn: Mr. Craig Kotarski, P.E.
608 Preston Ave. Suite 200
Charlottesville, VA 22903
Re: Lewis and Clark Drive Road Extension
Dear Clint:
We have reviewed the plans entitled "Lewis and Clark Drive Road
Extension," dated September 24, 2018. The following comments need to be
addressed.
C;PnPral
1. A fire hydrant is required every 1000 feet, proposed locations shown on
sheets C4.0-C4.3.
2. An in -line valve is required every 1000 feet, proposed locations shown on
sheets C4.0-C4.3.
3. Submit an updated master plan if available.
4. This area will be switching pressure bands in the area in the future. Model
the water main extension using the Piney Mountain Pressure Band and
the elevation of the new tank will be 770.5, to ensure adequate fire flow for
future development.
.qhPPt ra n
1. Remove tree from proposed ACSA water easement, as shown on plans.
.qhPPt ra
1. ACSA GIS indicates the existing stub -out is 14-inch DIP.
Sheet C4.7-C4.9
1. Have water crossings on top of storm.
2. Insulation of water main will be required at open ended storm crossings.
If you have any questions concerning this review feel free to call at
(434) 977-4511 Ext. 113.
Sincerely,
Richard Nelson
Civil Engineer