HomeMy WebLinkAboutSDP201800078 Action Letter 2019-01-02 (3)COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
December 20, 2018
Mr. Ryan Perkins, P.E. — Kimley Horn
1700 Willow Lawn Dr., Suite 200
Richmond, VA 23230
(804) 672-4703 / ryan.perkins&kimley-horn.com
RE: SDP2018-00078 Wawa at Pantops — Initial Site Plan - Action Letter
Dear Mr. Perkins:
The Agent for the Board of Supervisors hereby grants conditional administrative approval to the above -referenced site
plan. See below and attached for conditions and process:
SITE PLAN: This approval shall be valid for a period of five (5) years from the date of this letter, provided that the
developer submits a final site plan for all or a portion of the site within one (1) year after the date of this letter as
provided in section 32.4.3.1 of Chapter 18 of the Code of the County of Albemarle, and thereafter diligently pursues
approval of the final site plan.
In accordance with Chapter 18 Section 32.4.2.8 Early or Mass Grading may be permitted after the following approvals
are received:
1. Engineering approval of a VSMP plan meeting the requirements of Chapter 17 of the Code of the County of
Albemarle.
2. Approval of all easements for facilities for stormwater management and drainage control.
3. Submittal of a tree conservation checklist with areas for tree preservation identified.
The final site plan will not be considered to have been officially submitted until the following items are received:
1. A final site plan that satisfies all of the requirements of section 32.6 of Chapter 18 of the Code.
2. Applicable fee outlined in the application.
Please submit 10 copies of the final plans to the Community Development Department. The assigned Lead Reviewer
will then distribute the plans to all reviewing agencies.
The Department of Community Development shall not accept submittal of the final site plan for signature until
tentative approvals for the attached conditions from the following agencies/reviewers have been obtained:
SRC Members:
Albemarle County Planning Services (Planner) — 2 copies (Andy Reitelbach, areitelbach&albemarle.org)
Albemarle County Engineering Services (Engineer) — 1 copy (John Anderson, janderson&albemarle.org)
Albemarle County Information Services (E911) — 1 copy (Andrew Walker, awalker&albemarle.org)
Albemarle County Building Inspections — 1 copy (Michael Dellinger, mdellingergalbemarle.org)
Albemarle County Planning Services (ARB) — 1 copy (Heather McMahon, hmcmahon@albemarle.org)
Albemarle County Fire & Rescue — 1 copy (Shawn Maddox, smaddoxkalbemarle.org)
Albemarle County Service Authority — 1 copy (Richard Nelson, melson(d),serviceauthority.org)
Virginia Department of Transportation — 1 copy (Adam Moore, adam.moore(&vdot.virginia.gov)
If you have any questions about these conditions or the submittal requirements, please contact me at (434) 296-5832
ext. 3261 or at areitelbach(a-)albemarle.org.
Sincerely,
-M. 64vd-&e. /�rv�re�aclti
Andy Reitelbach
Senior Planner
Albemarle County Planning Services (Planner) — Andy Reitelbach, areitelbachgalbemarle.org — Requested
Changes:
1. [General Comment] The final site plan for the Wawa at Pantops project will not be granted approval unless
either one of the two conditions below is met:
a. The final site plan for Pantops Corner (project number SDP2018-00089, prepared by Shimp
Engineering) is granted approval, and the proposed private street, known as Pantops Corner Way (along
with all sidewalks, landscaping, the private access way that stubs out to the east adjacent to the Malloy
Ford property, and all other associated improvements), is either constructed or bonded.
b. The proposed private street, known as Pantops Corner Way (along with all sidewalks, landscaping, the
private access way that stubs out to the east adjacent to the Malloy Ford property, and all other associated
improvements), is shown as an integral part of the proposed plan on the Wawa at Pantops final site plan.
This option will require these improvements to be constructed and installed as part of the development
of the Wawa property.
In addition, the following comments must be addressed before the Planning Division will recommend approval
of the final site plan for the Wawa at Pantops project:
2. [General Comment] Because this project involves improvements that are located on other parcels, these other
parcel numbers and the site information data for these parcels should also be included. (Parcels 78-58G1 and 78-
513)
3. [General Comment] The Existing Conditions sheet should show what the actual conditions are at the site today,
not what is proposed on other site plans, and should include all three parcels involved in the overall development
of this area, as the proposed travelways are partially on those parcels.
What is currently shown on the Existing Conditions sheet should be shown on a separate page indicating that
these improvements are shown on an approved initial site plan, along with that plan's application number,
SDP201800039.
4. [32.5.2(a)] Identify the setback lines on all sheets showing the property, including on the other two parcels for
the Existing Conditions and requested new sheets.
5. [32.5.2(a)] Please provide the tax map and parcel numbers for all three parcels involved in the overall
development of this project, including the two parcels adjacent to Wawa's that include the proposed new roads
and travelways.
Also, include the full 14-digit TMP number for each of these three parcels (e.g., 07800-00-00-005A0).
6. [32.5.2(a)] The Overlay District note on the cover sheet should include "Steep Slopes — Managed," as well as
the overlay districts found on the other two parcels, which include "Steep Slopes — Preserved" and Floodplain
Hazard Overlay District." These various overlay districts should be identified by which parcels they are located
on. These overlay districts should also be shown on each sheet where the property is shown, including the
Existing Conditions, Site and Utility Plan, and Landscape Plan, as well as the requested new sheet from comment
#2.
In addition, all other aspects of the Project Data should include information for all three parcels, as a portion of
this project does extend on the two adjacent parcels as well.
7. [32.5.2(a)] In the project data information on the cover sheet, include that state and federal dam break inundation
zones overlay parcels 78-58G1 and 78-513. Also, on the existing conditions sheet and the requested new sheet,
shown the limits of these two zones.
8. [32.5.2(a)] In the project data information on the cover sheet, identify the building setbacks for front, rear, and
side yards, and label accordingly.
9. [32.5.2(a)] Please include a note describing the zoning map amendment that relates to this property, ZMA2013-
00002, as well as a list of the proffers and conditions included in that ZMA.
10. [32.5.2(a)] In the title, please specify that it is the Rivanna Magisterial District.
11. [32.5.2(a)] Please include a numeric scale, in addition to the graphic that is already included.
12. [32.5.2(a)] On all sheets showing the property, please include the names of the owners, the zoning district, the
tax map and parcel numbers, and the present uses of all abutting parcels.
13. [32.5.2(a)] Provide the dimensions and deed book and page number of the re -located VEPCO easement along
Route 250 that is shown on sheet CS-101.
14. [32.5.2(b)] Provide the proposed height of the canopy structure on the cover sheet, in addition to the height of
the convenience store building that is already provided.
15. [32.5.2(b)] Please revise the parking schedule on the cover sheet. Please see the following comment from the
Zoning Division:
After reviewing your request for a waiver to the maximum allowed parking, Zoning has reconsidered the parking
calculation used for the use proposed with this plan. Instead of the 1 space per 200 sq. ft. of floor area, Zoning
recommends that the site plan use the following calculation. Revise the plan as noted below:
SHEET CA-100
BUILDING
AREA
6049 SF GFA
PARKING
1 SPACE PER 100 SF OF RETAIL SALES AREA FOR THE FIRST 5000 SF
REQUIRED
OF RETAIL SALES AREA. RETAIL SALES AREA = 80% OF THE GROSS
FLOOR AREA (GFA)
6049 * 0.8 = 4839
4839 / 100 = 48
PARKING
48 SPACES
PROVIDED
16. [32.5.2(b)] Please include the maximum amount of impervious area allowed on the site.
17. [32.5.2(b)] Include the maximum amount of paved parking and other vehicular circulation areas. This note
should include those travelways extending onto the adjacent parcels.
18. [32.5.2(b)] Please clarify that the "Maximum amount of paved parking and vehicular circulation" is for the
landscaping purposes.
19. [32.5.2(d)] Identify on the plans on all sheets those areas of the three parcels that are either managed steep slopes
or preserved steep slopes.
20. [32.5.2(h)] Identify the boundaries of the flood hazard overlay district on all sheets showing the property.
21. [32.5.2(i)] Provide the right-of-way width for U.S Route 250 on sheet CS- 101.
22. [32.5.2(i)] As Pantops Corner Way and the access road to the north of the property are required for development
of the Wawa parcel, these proposed streets need to be shown on the proposed site plan. They need to be included
as integral parts of this site plan, not shaded grey with the expectation that they are already in place. There is no
final site plan approved yet for the other two parcels, and the construction of the entire road network in this area,
so the timing of development is not yet known. In addition, the widening of U.S. Route 250 to accommodate a
turn lane must also be included on this plan.
All other required improvements must also be shown, including sidewalks and landscaping along both sides of
the two new streets (Pantops Corner Way and the access street to the north of the Wawa property), and along the
turn lane of Route 250.
These improvements must be shown on this site plan, as this site plan must be able to stand on its own, in case
a final site plan for the adjacent properties does not get approved, or if this project moves toward construction
prior to the project on the adjacent parcels.
23. [32.5.2(i)] Identification of public access easements along the proposed Pantops Corner Way and the street north
of the Wawa parcel must be shown on the site plan.
24. [32.5.2(i)] Provide the right-of-way lines and widths, and the pavement widths, for all of the new streets proposed
for this project, including Pantops Corner Way, the new street to the north of the Wawa property, and the 250
turn lane widening.
25. [32.5.2(m)] The existing ingress/egress to the property should be shown on the existing conditions sheet.
26. [32.5.2(m)] Provide sight lines at intersections, to ensure vegetation and signage does not interrupt the required
sight distances.
27. [32.5.2(n)] Clarify the width of the sidewalk on the south side of the building, as well as identifying the structure
that appears to be in the middle of that sidewalk.
28. [32.5.2(n), 4.171 Please provide a full lighting plan with the final site plan in compliance with Section 4.17
of the Zoning Ordinance.
29. [32.5.2(n)] Please provide the location of all existing and proposed improvements, including the new roads and
sidewalks that extend onto the adjacent properties.
The full set of improvements for the adjacent properties (SDP201800039) should be shown on a new sheet, not
the existing conditions sheet.
30. [32.5.2(n)] Please provide the footprint of the canopy on sheet CS-101.
31. [32.5.2(n)] Reduce the height of the canopy, as requested by the County's Architectural Review Board.
32. [32.5.2(n)] Sidewalks must be provided along both sides of the two new streets, as well as along 250. Please
show them.
33. [32.5.2(n)] In the dumpster enclosure area:
a. What is the proposed material for the enclosure screening?
b. What is the structure in the top left corner of the enclosure?
c. Provide the dimensions of the enclosure and concrete pad in front of it.
34. [32.5.2(n)] What are the dimensions of the loading zone?
35. [32.5.2(n)] Provide bumper blocks in all parking spaces that are adjacent to a sidewalk.
36. [32.5.2(n)] Provide ADA-accessible ramps at all crosswalks, as well as adjacent to the ADA-accessible parking
spaces.
37. [32.5.2(n)] Provide the distance from the gas tanks to the edge of the canopy.
38. [32.5.2(p)] The landscape plan must show all landscaping that is currently shown on the approved initial site
plan, SDP201800039.
39. [32.7.9] On the landscape plan, provide the length of the parcel's frontage along each of the roadways so that
staff may accurately calculate the number of street trees required.
40. [32.7.91 On the landscape plan, provide the number of proposed parking spaces so that staff may accurately
calculate the number of interior trees required.
41. [32.5.2 (e)] Please provide more details about the existing landscape features as described in Section 18-
32.7.9.4(c).
a. The Albemarle County Conservation Plan Checklist and Chapter 3.38 of the Virginia Erosion and
Sediment Control handbook. The Conservation Plan Checklist will need to be signed by the owners and
provided as an exhibit on the final site plan for Block 3A.
42. [32.7.9] On the plant schedule, provide the canopy area for each tree.
43. [32.7.9.91 Please add a note to the Landscape plans stating, "All landscaping shall be installed by the first planting
season following the issuance of the first certificate of occupancy within the development."
44. [32.7.9.91 Please add a note to the Landscape plans stating "All landscaping and screening shall be maintained
in a healthy condition by the current owner or a property owners' association, and replaced when necessary.
Replacement material shall comply with the approved landscape plan."
45. [32.6.2 (h)] Please provide a signature panel with a line for each member of the Site Review Committee.
46. [32.7.9] Please provide individual landscaping schedules for required landscaping in accordance with Sections
32.7.9.5, 32.7.9.6, 32.7.9.7, 32.7.9.8 of the Zoning Ordinance. Each schedule should state the Botanical Name
and Common Name of each species proposed, the proposed caliper and height at time of installation, and the
canopy coverage area per plant species. The canopy area for each species can be found on the Albemarle County
Recommended Plants List and Albemarle County Plants Canopy Calculations tables. PDFs of these documents
can be accessed through the Department of Community Development webpage: LINK. Additional comments
may be provided regarding landscaping once a more complete landscape plan has been submitted.
a. [32.7.9] Indicate what landscaping is being used to fulfill the requirement for the required parking lot
landscaping. Provide calculations showing how the "maximum amount of paved parking and vehicular
circulation" of 5% requirement for landscaping is being met.
b. [32.7.9] Please provide calculations for tree canopy coverage, including if any existing trees are
proposed to count toward this requirement. Also, any plant under five feet in height (32.7.9.8(b)),
including shrubs, does not count toward the required canopy coverage amount. Additional tree canopy
coverage must be provided. Canopy coverage must be 10% of the overall site.
Albemarle County Architectural Review Board (ARB)
Heather McMahon, hmcmahonkalbemarle.org — Requested Changes; ARB conducted 12/3/18; see attached comments.
Albemarle County Engineering Services (Engineer)
John Anderson, janderson@albemarle.org — Requested Changes (12/5/18); see attached comments.
Albemarle County Information Services (E911)
Andrew Walker, awalkerkalbemarle.org—No Objection (10/31/18).
Albemarle County Building Inspections
Michael Dellinger, mdellingerkalbemarle.org — Requested Changes (11/2/18); see attached comments.
Albemarle County Department of Fire -Rescue
Shawn Maddox, smaddox@albemarle.org — Requested Changes (12/5/18); see attached comments.
Albemarle County Service Authority (ACSA)
Richard Nelson, rnelsonnserviceauthority.org — Requested Changes (11/30/18); see attached comments.
Virginia Department of Transportation (VDOT)
Adam Moore, Adam.Moore@vdot.vir ig nia og_v — Requested Changes (11/15/18); see attached comments.
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
December 18, 2018
Ryan Perkins
Kimley-Horn and Associates, Inc.
1700 Willow Lawn Dr., Ste 200
Richmond, VA 23230
RE: ARB-2018-135: Wawa at Pantops Corner, Initial Site Plan
Dear Mr. Perkins,
Staff has received the revised rendering of the fuel -pump canopy, submitted December 18, 2018. After
reviewing the resubmission, staff is satisfied that the revised drawing sufficiently address the following
request made at the December 3, 2018 ARB meeting:
• Regarding requirements to satisfy the design guidelines as per § 18-30.6.4c(2), (3) and (5) and
recommended conditions of initial plan approval:
o Prior to Initial Plan approval the following items shall be resolved to the satisfaction of the
ARB:
Reduce the height dimension of the fuel -pump canopy to comply with the Standards for
Fuel Pump Canopies as outlined in Appendix B of the EC Design Guidelines.
Therefore, staff has approved the Initial Site Plan.
Please note that the ARB made the following recommendations at the December 3, 2018 ARB meeting to
assist with future review:
• Regarding recommendations on the plan as it relates to the guidelines:
1. Consider substituting tree and shrub species native to the Piedmont region for those exotic
species found in the plant schedule.
Regarding the final site plan submittal:
1. Clarify and correct the discrepancy between the stated square footage of the fuel -pump
canopy and the dimensions of the fuel -pump canopy provided on the site plans.
2. Consider continuing windows across the full length of the facade. Relieve blankness on
the east and west elevations by using landscaping.
3. Provide the standard glass note on the elevations: Window glass in the Entrance Corridors
should meet the following criteria: Visible light transmittance (VLT) shall not drop below
4001o. Visible light reflectance (VLR) shall not exceed 3001o.
4. Reduce the height of the fuel -pump canopy to comply with the Standards for Fuel Pump
Canopies as outlined in Appendix B of the EC Design Guidelines.
5. Provide landscape screening for the vent stacks and other similar equipment. Consider
locating the underground tanks to the east side of the site.
6. Show how the visibility of all mechanical equipment will be eliminated from the EC.
7. Provide a roof plan with equipment locations for review if any proposed mechanical
equipment will be roof -mounted. Show equipment locations and heights on the elevation
drawings.
8. Provide a dumpster enclosure detail in the plan. Show how the enclosure is compatible
with the building design.
9. Provide the standard mechanical equipment note on the site plan set and on the
architectural drawings: Visibility of all mechanical equipment from the Entrance Corridor
shall be eliminated.
10. Provide a lighting plan for review.
11. Provide standard lighting note on the lighting plan: Each outdoor luminaire equipped with
a lamp that emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be
arranged or shielded to reflect light away from adjoining residential districts and away
from adjacent roads. The spillover of lighting from luminaires onto public roads and
property in residential or rural areas zoning districts shall not exceed one half footcandle.
12. Provide a glass sample and/or manufacturer's specifications that provide the VLR and
VLT values.
13. Specify the exact species for each tree and shrub proposed in the plant schedule. If
multiple species are proposed, provide distinct symbols for each and call them out on the
landscape plan.
14. Provide a finalized landscape plan at the front of the property which is consistent with
previous reviews and approvals.
15. Clarify the material of the area surrounding the proposed entrance sign.
16. Ensure that all proposed trees are clear of utilities and their easements.
17. Provide plantings in the southwest corner of the site.
18. Consider substituting tree and shrub species native to the Piedmont region for those exotic
species found in the plant schedule.
19. Ensure that the centers of proposed trees are a minimum of 7 feet from the centers of
underground utility lines.
20. Provide landscaping along interior pedestrian ways.
21. Provide three additional interior parking trees.
22. Revise the landscape plan to show the appropriate spacing of proposed shrubs based on
the final species chosen.
23. Ensure that any proposed tree or shrub species does not exceed 25% of the total trees or
shrubs proposed on the site.
24. Provide the standard plant health note on the landscape plan (CP-101): All site plantings
of trees and shrubs shall be allowed to reach, and be maintained at, mature height; the
topping of trees is prohibited. Shrubs and trees shall be pruned minimally and only to
support the overall health of the plant.
25. Clarify the height of the retaining wall on the northwest corner of the site. If the wall is
over 6' tall, it must be terraced and landscaped, and this must be shown on the site plans.
26. Provide top -of -wall and bottom -of -wall elevations for the retaining walls.
27. Show how glare from canopy fixtures will be eliminated.
If you have any questions concerning any of the above, please feel free to contact me.
Sincerely,
Heather McMahon, Senior Planner
hmcmahon&albemalre. org
434-296-5832 ext. 3278
cc: Pantops Corner LC, 12704 Crimson Court, Ste 101, Henrico VA 23233
File ARB-2018-135
LIGHT FD(TURE —i SLOPE PRECAST CAP
T.O. WALL h
Metal
Atas International
Bone White
# 26
Roof 7Tave
—
T.O. CANOPY
03,,Z.
" I I
a K3J
wI
-I- I- I I -17
��'�����
T.O. MASONRY
5
`�
T0. SILL 1
0"
JIM
MANUFACTURED
STONE SILL
BRICKTAVERN
�'
m BOLLARD
,a.
/
E� T.O. FLOOR SLAB
FRONT ELEVATION
RIGHT ELEVATION
GATE,
LEFT ELEVATION
REAR ELEVATION
Metal Door
Trim
Thin Brick
Benjamin Moore
James Hardie
7Tavern Flash Red
White Diamond
Arctic White
Marion Ceramics
BM 2121-60
JH10-20
WAWA CAS CANOPY 5TACKED 9 A
FRAME -
TRA5H
COMPOUND
MA5011-L -
Richmond Rd. & Stoney Point
Rd., Charlottsville,
VA • C&P
Project #2180578 • 10-17-2018
TO. WALL
9' 0°
T.O. MASONRY
8' 8"
`BRICK TAVERN
T0. SILL h
5' - 0"
MANUFACTURED
STONE SILL
I —BRICK TAVERN
STORE #8rorol
Architects Engineers Planners
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, Room 227
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
Project: Wawa Pantops Corner — Initial Site Plan
Plan preparer: Ryan Perkins, Kimley-Horn Associates, 1700 Willow Lawn Drive, Suite 200
Richmond,VA 23230 [ryan.perkins(a-)kimley-hom.com ]
Owner or Rep: Pantops Corner LC, 12704 Crimson Court, Suite 101; Henrico,VA 23233-7657
Applicant: Paul Sprouse, The Rebkee Company, 2800 Patterson Ave, Suite 200
Richmond, VA 23221 [psprouse(a)rebkee.com]
Plan received date: 25 Oct 2018
Date of comments: 5 Dec 2018
Reviewer: John Anderson
Project Coordinator: Andy Reitelbach
SDP2018-00078
CA-100
1. Provide 1" =2,000 (or less) scale vicinity map.
2. Include SDP201800078 in revised initial site plan title.
3. Engineering recommends include ZMA201300002 proffer on title sheet.
4. Ref. WP0201800088 (Pantops Corner VSMP Plan) as well as WP0201400028, Mass Grading
and Erosion & Sediment Control Plan for Pantops Corner, approved 6/11/14, with estimated area to
be disturbed =7.01 Ac.
5. Note: Site under development does not have an existing stormwater management plan. A Mass
Grading and ESC Plan was approved, 6/11/14. No development layout is shown with the Mass
Grading and ESC Plan. Grandfathering (9VAC25-870-48) would not apply in this instance, for this
reason. VAR10E170 (VSMP Program VPDES) permit was issued for mass grading on 9/9/14.
Grading has been performed, and site should be stabilized. If mass grade operations are complete, and
site stabilized, it is time to terminate VAR IOE170, and apply for a new VSMP permit for never -
reviewed proposed development on this parcel. Further, VDEQ SWCGP database lists Construction
Activity Operator (VAR10E170) that does not match Initial Site Plan Owner information. Albemarle
does not accept the position that this development is eligible for grandfathering, but views development
subject to stormwater quality and quantity requirements at 9VAC25-870-65 and 9VAC25-870-66.
CV- 101 (Existing Conditions)
6. Do not show:
a. Proposed development on TMP 78-58G1, which does not exist.
b. Any proposed development features on TMP 78-5A, unless they exist.
C. Show existing features only. If Applicant arranged with Planning Division to represent
proposed features on CV-101 (Existing conditions), provide whatever elements were
requested as an Exhibit or separate ISP sheet with appropriate title.
Do show:
a. Full width of U.S. Rt. 250 where it fronts TMP #78-5A. Show existing travel lanes, turn
lanes, traffic signs, median, etc.
b. Steep slopes (Ref. County GIS Critical Resource layer). Managed steep slopes exist on
this parcel.
Engineering Review Comments
Page 2 of 3
C. Proposed RW for private road Pantops Corner Way.
8. Add Note stating that all known existing easements are shown, or that none exist on TMP# 78-5A.
9. Provide Ownership information for parcel under development, and adjacent parcels: provide
TMP#, owner name, DB/PG.
CS- 101 (Site and Utilitv Plan
10. Transfer proposed development features from CV- 101 to CS- 101, including:
a. For FSP approval (submit /respond to comments until approved):
i. Retaining wall design, since proposed retaining walls support necessary
infrastructure (engineered plans, not generic manufacturer's details). Consider
county retaining wall plan review checklist.
ii. Drainage plans. Consider county drainage plan review checklist, including:
1. Drainage structure typ. details
2. Pipe and inlet type, length, diameter, material, slope, etc.
3. Calculations (LD-204, LD-229)
a. Velocity /Capacity /Inlet spread and depth
4. Profiles, all elements labeled
5. Label inlets, pipes, and structures
iii. Water and sewer line profiles.
iv. WPO201800088, Pantops Corner, must be approved (prior to Wawa at
Richmond Road and Stony Point Road FSP Approval).
V. Include Exhibit for off -site (TMP #78-58G1) SWM facilities required to meet
stormwater quality and quantity requirements.
vi. WPO201800088 must be bonded.
vii. Pantops Corner Way must be (built or) bonded to limits required by Planning
Division, as defined by ZMA201300002 proffer.
11. Note: Provide Road Plan under separate Application to County at earliest convenience. Ensure
road plan design for Pantops Corner Way considers Road Plan checklist for plan reviewers, and
includes a temporary turnaround meeting VDOT, Fire Rescue, and ACDSM needs, unless fully
constructed between U.S. Rt. 250 and R. 20 with Wawa. Attached.
12. Light grayscale indicates Pantops Corner Way is existing. Revise to show Pantops Corner Way is
proposed and is to be constructed with Wawa site plan to limits defined by Planning. Provide
turnaround sufficient to meet multiple agencies temporary turnaround requirements.
13. Loading width is less than 12', if exclude area occupied by bollards. Revise to provide min.
loading space width of 12'.
14. Delete note stating `Terraced Retaining Wall ...is to be designed and constructed as part of
Pantops Corner Development plans.' The terraced retaining walls are intrinsic to site development.
Include engineered PE -sealed retaining wall design plans with FSP.
15. Provide VDOT GR-1 (guardrail) for parking spaces fronting retaining wall; ensure sufficient
parking space depth, once guardrail is installed.
16. Proposed SS line appears discontinuous. Revise to show connection with Ex. SS, or extend
proposed SS to a logical endpoint.
17. If proposed retaining wall fronting Pantops Corner Way coincides with managed steep slopes,
ensure design meets (retaining wall) design standards at 18-30.7.5.
18. Likewise, storm drain pipe from DI at third southernmost parking space facing Pantops Corner
Way is discontinuous. Clarify connection with downgradient elements of storm system.
19. Review proposed bike rack to ensure adequate clearance between typ. bike and proposed sidewalk
(1'-2' clearance, recommended).
20. Show proposed easements, including:
a. Drainage
i. Ref. ACDSM, pg. 15
CS-502
CG-101
CP-101
Engineering Review Comments
Page 3 of 3
b. Sidewalk
C. ACSA
d. Sight
e. RW
21. Provide entrance sight lines, north -south, for vehicles exiting Wawa.
22. Label commercial entrance using VDOT nomenclature (CG-9a, etc.).
23. Label corner clearance distance from site entrance to U.S. Rt. 250. Engineering defers to VDOT.
24. Label any spilling curb and gutter.
25. Label entrance curb radius.
26. Show trench drains.
27. Provide concrete specification; provide 3000 psi strength at 28 days.
28. Provide dumpster pad detail.
29. Provide CG-6 detail.
30. Recommend spot Elevations at entrance.
31. Ensure spills from filling UG fuel tanks reach trench drain. Check west -most UG tank, in
particular.
32. Show steep slopes, this sheet.
33. Stormwater Management Narrative (Also, items 5, 10.a.iv, above):
a. There is no evidence at this point that 2.45 lbs. of phosphorus credits purchased from a
nutrient bank will satisfy stormwater management requirements. Delete specific reference to
2.45 lb. credit from site plan; instead, reference WP0201800088. Transfer specific, detailed
SWM Narrative and design information to WP0201800088.
b. Please note that WP0201800088 references 8.3 lb. purchase. WPO plan information has
not been reviewed in detail; presentation and integration of TMP #78-5A and 78-58G1 SWM
requirements into a single WPO requires care.
34. Provide note for vegetative ground cover hardier than grass for areas between discrete individual
plantings north of retaining wall on north side of site (2:1 slope). Mulch may suffice.
35. Remove proposed street trees within drainage easement/s. Recommend show drainage easement/s
on Landscape plan.
36. Street trees appear to obstruct sight distance. Provide sight lines. Also, item #21 above.
Please call if any questions: 434.296-5832 —0069
Thank you
SDP201800078 Wawa Pantops_ISP_120518.doc
Review Comments for SDP201800078 I Initial Site Plan
Project Name: WAWA @ PANTOPS CORNER - INTIAL
Date Completed: Wednesday, October 31, 2018 DepartmentJDivision/Agency: Review Status:
Reviewer Andrew Walker rnn Fgii No Objection
Review Comments for SDP201800078 I Initial Site Plan
Project Name: WAWA @ PANTOPS CORNER - INTIAL
Date Completed: Friday, November 02, 2018 Department}Division/Agency: Review Status:
Reviewer Michael Dellinger rnn 1nfzn,-rfinnc See Recommendations
Retaining walls greater than 3 feet in height require a separate building permit_ Walls exceeding 4 feet in height require an
stamped engineered design also_
Accessible parking spaces and access isles shall not have a surface slope greater than 1 :48. Access isles shall be at the
same level as the parking space they serve_
Review Comments for SDP201800078 I Initial S ite Plan
Project Name: WAWA @ PANTOPS CORNER - INTIAL
Date Completed: Wednesday, December 05, 2018 Department}Division/Agency= Review Status:
Reviewer. Shawn Maddox Li Firms r-I I 71 Requested Changes
1 _ If the building is going to be sprinklered the FDD must be shown on the site plan and be located within 100' of a
hydrant-
_ The hydrant must be in place prior to construction beginning-
3- A fire flow test will be required prior to final acceptance_
Review Comments for SDP201800078 I Initial S ite Plan
Project Name: WAWA @ PANTOPS CORNER - INTIAL
Date Completed: Friday, November 30, 2018 Department/Division/Agency: Review Status:
Reviewer L Richard Nelson Requested Changes
If a fire hydrant is required on site, submit 3 copies of site plan to ACSAfor review_
Include SDP number for Pantops Corner Hotel, when referencing utilities from that site plan_
If this project is built before the hotel, ADA will require separate water and sewer plans for review and approval_
COMMONWEALTH of VIRGINIA
DEPARTMENT OF TRANSPORTATION
1601 Orange Road
Culpeper Virginia 22701
Stephen C. Brich, P.E.
Commissioner
November 15, 2018
Andy Reitelbach
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902
Re: SDP-2018-00078- WaWa at Pantops Corner — Initial Site Plan
Dear Mr. Reitelbach:
The Department of Transportation, Charlottesville Residency Transportation and Land Use
Section, has reviewed the above referenced plan as submitted by Kimley and Horn, dated
October 19, 2018 and offer the following comments.
Land Use
1. Pantops Corner Way is shown as existing. Currently there are no approved plans for this
street. Will this street be public or private? Comments may change depending on this
determination. This site plan cannot be approved prior to plans for Pantops Corner.
2. Please provide sight distance lines and profile for proposed entrances onto Pantops
Corner Way.
3. Please provide drainage calculations for proposed storm water management structures.
Also please show that the existing drainage structures can adequately handle the
discharge, pre and post construction.
4. Please see appendix F, page F-116, of the Road Design Manual for minimum corner
clearance standards for commercial entrances. Please see figure 4-5 for the appropriate
details. As proposed, the southern entrance doesn't meet the minimum downstream
corner clearance of 225 ft., and an access management exception is required.
5. Please provide Strom Sewer profiles and plot HGL on profiles.
6. Drainage structure on the left side of the southern entrance needs to be tied into the DI.
Please note that the final site plan must show conformance with the VDOT Road Design Manual
Appendices B (1) and F, as well as any other applicable standards, regulations, or other
requirements.
Please provide two copies of the revised plan along with a comment response letter. If further
information is desired, please contact Willis C. Bedsaul at 434-422-9866.
A VDOT Land Use Permit will be required prior to any work within the right of way. The
owner/developer must contact the Charlottesville Residency land Use Section at (434) 422-9399
for information pertaining to this process.
WE KEEP VIRGINIA MOVING
November 15, 2018
Mr. Reitelbach
Page Two
Sincerely,
Adam J. Mo
Area Land Use Engineer
Charlottesville Residency
WE KEEP VIRGINIA MOVING