The Planner for the Planning Division of the Albemarle County Department of Community
Development will recommend approval of the plan referred to above when the following items
have been satisfactorily addressed. (The following comments are those that have been identified
at this time. Additional comments or conditions may be added or eliminated based on further
review.) [Each comment is preceded by the applicable reference to the Albemarle County Code.]
First Review Comments:
[General Comment] Revise the title of this plan to indicate that it is a Minor Amendment, and
include the former site plan application numbers, SDP199300001 and SDP201500013, that
are being amended.
2. [General Comment] As this is a minor amendment, provide a list of all proposed changes on
the cover sheet.
[General Comment] On page C0.3, there is a note regarding the proposed stairway to look at
separate plans. There are no other plans within this application that pertain to the stairway.
It appears that this stairway may have been approved as a Letter of Revision (LOR) in May
2018. If this is the case, please indicate the application number and approval date for this LOR
in the note on the stairway.
4. [32.5.2 (a)] In the zoning note, include that this property is located within the Entrance
Corridor and Steep Slopes — Managed overlay districts.
5. [32.5.2 (b)] Include on the cover sheet the acreage of the subject parcel.
6. [32.5.2(a) and 4.20 (a)] Please include the setbacks in the data table on the cover sheet. In
the HC Zoning District, the minimum front setback is 10' from the right-of-way. The minimum
side and rear setbacks should state, "Primary structures shall be constructed and separated
in accordance with the current edition of the Building Code."
7. [32.7.3 and 4.121 On Sheet C0.3, please also include in the parking summary the number of
spaces that is required for this use.
8. [32.5.2(i)] Label the access road to this site, indicate if it is public or private, and provide its
right-of-way and pavement widths.
9. [32.7.9] The plant schedule on sheet L1.1 states that there are three (3) QP, Quercus phellos,
trees proposed for the landscaping. However, on the plan on sheet L1.0, only two (2) QP trees
are shown. Please add an additional QP to the plan to match what is shown in the Plant
Schedule.
10. [4.17] In the Electrical Plan on E1.0, there appears to be a tree in the proposed drive aisle of
the new parking area. Please remove this tree.
11. [4.17] On sheet C3.0, the light poles proposed to be removed in the demolition plan on C2.0
are still shown in their current locations. Please remove these existing poles from the layout
plan on sheet 3.0 since they are proposed to be relocated.
12. [4.17] Please clarify the light fixture type proposed for this project, as shown on sheet E1.1.
The graphic describes the light fixture type as C1 and C3. However, the Lighting Fixture
schedule only has information on "Type A." It also does not appear to indicate whether this
proposed lighting is a full cut-off fixture or not, as is required.
Please contact Andy Reitelbach at the Department of Community Development at
areitelbach@albemarle.ore or 434-296-5832 ext. 3261 for further information.
Comments from other Reviewing Departments and Agencies
Albemarle County Engineering Services — John Anderson, janderson2@albemarle.org —
Requested Changes; please see the attached memo, with comments.
Albemarle County Architectural Review Board — Margaret Maliszewski,
mmaliszewski@albemarle.org — No Objection
A
VIRGlN1P
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, Room 227
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
Site Plan Review
Project title:
ACSA Admin & Ops Center —Minor Amendment
Project file number:
SDP201800061
Plan preparer:
Dewberry Engineers / 4805 Lake Brook Drive, Suite 200
Glen Allen, VA 23060
Owner or rep.:
Alexander J. Morrison, PE /ACSA[aorrisongserviceauthority.org]
Plan received date:
7 Aug 2018
Date of comments:
10 Sep 2018; rev. 13 Sep 2018
Plan Coordinator:
Andy Reitelbach
Reviewers:
John Anderson
SDP201800061
1. A separate standalone VSMP permit is required. Please remove the following from the Minor Site
Plan Amendment: C0.2; portion of C2.0 related to ESC; C5.0, C5.1, C6.2, C6.3.
2. Recommend revise title of Minor Site Plan Amendment to include `SDP201800061, Minor Site
Plan Amendment' and to delete `100% submission.' (Engineering recommendation only).
3. Title VSMP Plan: `Albemarle County Service Authority Operation Center Expansion Parking Lot
Expansion, VSMP /WP02018-XXXXX.' Note: once WPO# assigned, will provide # for final
VSMP Plan title sheet revision.
4. Ref. Albemarle County Code, Chapter 17, Sec. 17-401 thru 17-405 for VSMP Application form
and content requirements (incl. SWPPP, PPP, ESC /SWM plans + Application /fee requirements).
Link:
http://www.albemarle.or¢Luuload/images/Forms_Center/Departments/County Attorney/Forms/AlbemarleC
ounty Code Ch17 Water_Protection.pdf
5. C3.1 —Label ditch and ditchline slope on upslope side of retaining wall.
6. C3.1 — Recommend revise description of Str. 20 (in data arranged as table) to include 48" diameter.
7 C3-2 Proposed retaining wail .design profle atio: (Rev. 13-Sep) After further consideration of
18-30.7.5 design standards, plan review, and discussion, a combination of grade at base of wall not
to exceed 2:1 and wall height not to exceed 6' is permissible; however, revised design must
eliminate angle at top of 2:1 fill slope. Option recommendation: provide min. 1' wide bench, 1-2%
slope away from base of wall. ACSA to coordinate slope -grade design revision with Dewberry.
Further, Dewberry is encouraged to consider stabilization matting for existing drainage way at base
of wall /base of 2:1 slope that will likely be in proposed fill section, and susceptible to erosion.
a. Proposed design must meet each applicable standard listed at 18-30.7.5.a.1-3, b.l-4;
please call if any questions.
b. Eliminate proposed 2:1 slope at base of wall, an impen:nissible appFeach to liffliting
height 61. (Rev. 13-Sep) Comment withdrawn.
e. Provide stepped walls, max. ht. 6', with 3' sepaFation between walls-.
d. Consider constructability /possible need for off -site temporary construction easement.
e. Proposed design (w/ 2:1 slope at toe, to be eliminated) requires 6' horizontal space; 4.5'
is available between face of wall and property line.
f. Show property line (accurate scale) in profile view.
Engineering Review Comments
Page 2 of 2
listed at 19 3 0.7.5 A"ile still pr-eviding 18 paf4iag spaces. Reviewer- is unawafe of any
o
C4.0
8. Revise STM 24 MH-1 label (typo) -diameter should read 60".
9. Provide Note that steps are required for MH depth > 4.0'.
10. Compare inside crown of pipe elevation, 375.75 (INV IN, STM 20), with 10-31 event elevation,
376.52. Detention pipe must be sized to contain a 10-yr event without exceeding interior elevation
(of top of pipe, at lowest point). Avoid pressurized system. Recommend examine next larger pipe
diameter.
11. STM20 - Provide ref. to weir plate detail, sheet C5.3.
12. C4.1 - Conduit flex table slope and length values for Node # 25, 30 do not match profile labels,
C4.0, C4.1. Review /revise for consistency.
13. 5_2 - Recommend detail for handrail post, since detail provided assumes handrail set in retaining
wall. Proposed handrail is not on wall, but behind wall, in fill section. Also note: handrail design
must prevent easy access to top of wall. If rail slopes down with grade behind wall, ensure design
provides suitable deterrent to trespass /prevents access to top of wall.
14. C5.3 - Show MH steps schematically in top view of weir plate MH detail, to limit conflict and
guide installation during construction.
15. C5.3 - Provide VDOT ST-1 (MH step) detail.
16. C5.3 - Provide trash rack, 4" orifice.
VSMP (preview comments): additional comments likely, once VSMP Application submitted:
17. C0.2, ESC Maintenance /Note. 2: Revise to specify paved construction entrance. Provide paved
CE detail. Ref. ACDSM /p. 8 -link:
http://www.albemarle.org/ul)load/images/forms center/departments/community development/forms/design s
tandards manual/Albemarle County Design Standards Manual 2015-04-25 draft.pdf
18. C0.2, ESC Sequence item 4 must come prior to item 3; install silt fence prior to clearing /grubbing.
19. C2.0 -Revise CE label to read PCE (Incl. PCE in ESC legend).
20. Provide schematic depicting Phase 2, once retaining wall constructed and STM25 installed. See
ESC Sequence note 6 (storm structure #25). Provide phased ESC schematic.
21. In Phase 2 ESC schematic, specify VESCH blanket stabilization for ditch behind (upslope side of)
retaining wall to limit proximate effect on adjacent property, should erosion develop in this area.
22. C5.0 - Provide paved construction entrance detail -ref. p. 8, ACDSM; also, comment 17, above.
23. C6.2 - Coordinate nutrient credit purchase with Ana Kilmer, Management Analyst, CDD, prior to
purchase. Legal must review documents prior to sale. Ms. Kilmer: 434.296-5832 -x3246
/akilmer(j- albemarle.M. (Rev. 13-Sep) ACSA has purchased credits; will work with Albemarle to
address any outstanding nutrient credit purchase document (VSMP) needs or requirements.
24. C6.2 -Provide stormwater quality /quantity narrative to outline and demonstrate compliance.
25. C6.3 -Energy balance is incomplete, and confusing. Provide RV(1_yr, pre -/Post -development)•
26. C6.3 -Provide routing for 1-year event, pre -development; provide model input /hyrdrograph.
27. Use county SWPPP template.
Link:
http://www.albemarle.org/upload/images/forms center/departments/Community_ Development/forms/Engine
eringtand _WPO_Forms/Stormwater_Pollution _ Prevention_Plan _S WPPP_template.pdf
Thank you.
J. Anderson 434.296-5832 -0069
SDP201800061 ACSA Admin Parking 091318comment-rev.docx