Loading...
HomeMy WebLinkAboutSDP201800046 Review Comments Minor Amendment 2018-11-30 of A lor, .eg--P1‘ COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road,North Wing Charlottesville,Virginia 22902-4596 (434)296-5832 11-30-18 Clark Gathright 100 10th Street Suite 200 Charlottesville VA 22902 RE: SDP2018-46 Mint Spring Park-Minor Amendment Dear Sir: Your Minor Amendment application has been reviewed.In order for the amended site plan to be approved the following revisions are required: 1. 132.6.2(k)&4.11 Lighting. Provide a cut sheet with luminaire schedule for each proposed light fixture. Also. provide the locat on bf the outdoor lighting fixtures.Rev. Comment addressed. 2. [Comment] The Health Department approval is required prior to minor sit an approval.The applicant states that they submitted soil work directly to VDH per contact w/Josh Kirtl .VDH review comments pending,to be forwarded upon receipt.Rev. VDH approval is still pending. -.1 3-/9 3. 132.7.9.7(0]Sir ern kg.This use shall be screened from the adjacent rural areas zoning district.At a minimum provide a 6'tall oo en fence along the northern portion of the facility;additionally provide a 6' tall wooden fence along porti ns b f the east and west of the facility(see diagram below).Ensure the proposed fence is on the county prope v. l.f the applicant would like to provide a double staggered row of evergreen trees in place of the fencing ensue the trees are a minimum of 4'tall at the time of:planting and depict their location and planting information on the plan. Rev. Comment addressed. 4. 1Comment'On the site plan depict and label the stormwater management easements associated with the use. Rev. Continent addressed 5. [Comment' Priott to minor site plan amendment the VSMP plan shall be approved.Rev.Comment addressed 6. 14.12.1.50)]Su,face itfaterial: The Agent in consultation with the County Engineer has signed off on the use of gravel for this lots' As such,provide a note on the plans stating: "Gravel parking and d access aisles have been permitted:for the.site pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking Which is designed and constructed as provided in section 4.12. "Rev Cotnment addressed 7. 14.12.16(E)1 BumperBlocks. The Agent in consultation with the County Engineer has waived the requirement for bumper blocks. As such provide the following note on the site plan "The site will not require bumper blocks for parking spaces pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed nd constructed as provided in section 4:12'°Rev. Comment addresser' Engineering—John Anderson No objections. Fire and Rescue-Shawn Maddox ustardarmigiwial Review comments pending,to be forwarded once received. Virginia Department of Health—Josh Kirtley The applicant needs to record a letter at the Clerk's office before the permit is released. To the best of my knowledge,they were going to be working on that today. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may found on the County Attorney's website which may be found under"Departments and Services"at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six(6)months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer.If you have any questions about the comments please feel free to contact me. Sincerely, Christopher P.Perez Senior Planner Planning Division COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902-4596 (434) 296-5832 11-30-18 Clark Gathright 100 10' Street Suite 200 Charlottesville VA 22902 RE: SDP2018-46 Mint Spring Park - Minor Amendment Dear Sir: Your Minor Amendment application has been reviewed. In order for the amended site plan to be approved the following revisions are required: 1. 132.6.2(k) & 4.171 Lighting. Provide a cut sheet with luminaire schedule for each proposed light fixture. Also, provide the location of the outdoor lighting fixtures. Rev. Comment addressed. 2. [Comment] The Health Department approval is required prior to minor site plan approval. The applicant states that they submitted soil work directly to VDH per contact w/ Josh Kirtley. VDH review comments pending, to be forwarded upon receipt. Rev. VDH approval is still pending. 3. [32.7.9.7(a)] Screening. This use shall be screened from the adjacent rural areas zoning district. At a minimum provide a 6' tall wooden fence along the northern portion of the facility, additionally provide a 6' tall wooden fence along portions of the east and west of the facility (see diagram below). Ensure the proposed fence is on the county property. If the applicant would like to provide a double staggered row of evergreen trees in place of the fencing, ensure the trees are a minimum of 4' tall at the time ofplanting and depict their location and planting information on the plan. Rev. Comment addressed. 4. [Comment] On the site plan depict and label the stormwater management easements associated with the use. Rev. Comment addressed. 5. [Comment] Prior to minor site plan amendment the VSMP plan shall be approved. Rev. Comment addressed. 6. [4.12.15(a)] Surface Material. The Agent in consultation with the County Engineer has signed off on the use of gravel for this lot. As such, provide a note on the plans stating: "Gravel parking and access aisles have been permitted for the site pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed and constructed as provided in section 4.12. " Rev. Comment addressed. 7. [4.12.16(E)] Bumper Blocks. The Agent in consultation with the County Engineer has waived the requirement for bumper blocks. As such provide the following note on the site plan: "The site will not require bumper blocks for parking spaces pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed and constructed as provided in section 4.12 " Rev. Comment addressed. Engineering — John Anderson No objections. Fire and Rescue - Shawn Maddox Review comments pending, to be forwarded once received. Virginia Department of Health — Josh Kirtley The applicant needs to record a letter at the Clerk's office before the permit is released. To the best of my knowledge, they were going to be working on that today. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may found on the County Attorney's website which may be found under "Departments and Services" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six (6) months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. If you have any questions about the comments please feel free to contact me. Sincerely, A��— Christopher P. Perez Senior Planner Planning Division Review Cammer., i for SDP201800046 .. [Minor Amendment 7.1 Project Name: Mint Springs Park- Minor Amendment Date Completed: Friday. November 30. 2018 DepartmentDivision?.Agency: Review Status: Reviewer: John Anderson Li CDD Engineering - j No Objection No objection_ Review Commer for SDP201800046 - rviinorAmendment Project tJame:IMint Springs Park - Minor Amendment Date Completed.[Tuesday. December 04. 2018 Review Status: Department;Di�:ision/:Agenc; Reviewer: Shawn Maddox Fire Rescue No Objection 1. Fire Rescue_hasobjections to the site plan as provided based on VA Statewide Fire Prevention Code section 503.1.1 exception 2 The proposed pull offs will allow two way vehicular traffic if needed 2 Aforestry grant application must be completed prior to the completion of construction { a Nose Now November 27, 2018 Christopher Perez Senior Planner Community Development County of Albemarle 401 McIntire Rd. Charlottesville, VA 22902 RE: SDP2018-46 Mint Springs Park - Minor Amendment Chris: The following is a response to your review comments dated November 20, 2018: 1. Provide a cut sheet with luminaire schedule for each proposed light fixture. Also,provide the location of the outdoor lighting fixtures. (The Title Sheet notes there is no outdoor lighting.) V Ok. 2. The Health Department approval is required prior to minor site plan approval. - applicant states that they submitted soil work directly to VDH per contact w/Josh Kirtley. VD eview comments pending, to be forwarded upon receipt. (The Health Department approved the septic permit.) 14 5�► i 3. This use shall be screened from the adjacent rural areas zoning district. At a minimum provide a 6' tall wooden fence along the northern portion of the facility, additionally provide a 6' tall wooden fence along portions of the east and west of the facility(see diagram below). Ensure the proposed fence is on the county property. (A 6'wood fence is now shown on the plan.) V o C t.74<)n the site plan depict and label the stormwater management eas ents associated with the use. r n (Stormwater Management Easement is now shown on the plan.) 5. rior to minor site plan amendment the VSMP plan shall be approved. (The VSMP plan is approved.) Sart torril 6. The Agent in consultation with the County Engineer has signed off on the use of gravel for `/ this lot. As such,provide a note on the plans stating: "Gravel parking and access aisles have been permitted for the site pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed and constructed as provided in section 4.12." (The note is added to the plan.) tne Q S /7. The Agent in consultation with the County Engineer has waived the requirement for bumper ✓ blocks. As such provide the following note on the site plan: "The site will not require bumper blocks for parking spaces pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed and constructed as provided in section 4.12" (The note is added to the plan.) Z ye> Should you have any questions, don't hesitate to call me. Best regards, / %/ ,/) Clark Gathright, P.E. IP . ;,1�A 1J,. �gfawl�`y,,,� ..... COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road,North Wing Charlottesville,Virginia 22902-4596 (434) 296-5832 11-20-18 Clark Gathright 100 10`h Street Suite 200 Charlottesville VA 22902 RE: SDP2018-46 Mint Spring Park-Minor Amendment Dear Sir: Your Minor Amendment application has been reviewed.In order for the amended site plan to be approved the following revisions are required: 1. [32.6.2(k)&4.17]Lighting. Provide a cut sheet with luminaire schedule for each proposed light fixture. Also, provide the location of the outdoor lighting fixtures. 2. [Comment] The Health Department approval is required prior to minor site plan approval.The applicant states that they submitted soil work directly to VDH per contact w/Josh Kirtley.VDH review comments pending,to be forwarded upon receipt. 3. [32.7.9.7(a)]Screening. This use shall be screened from the adjacent rural areas zoning district.At a minimum provide a 6'tall wooden fence along the northern portion of the facility,additionally provide a 6'tall wooden fence along portions of the east and west of the facility(see diagram below).Ensure the proposed fence is on the county property.If the applicant would like to provide a double staggered row of evergreen trees in place of the fencing, ensure the trees are a minimum of 4'tall at the time of planting and depict their location and planting information on the plan. i I - — — ----x ---�,a -- �-i'' T r" _ ....... ...\ -- - r \ „. R50" . 'le t034.7 n I \ DUR t PARKING SPACES eo9 I, e5;i 23. 7./ \ —1 i I: , 3034 103t.7 t OF PIPE 8031.4120. 'vv /�'\ �• ri 4. Comment]On the site plan depict and label the stormwater management easements associated with the use. 5. [Comment] Prior to minor Ilan amendment the VSMP plan shall be appy . 6. [4.12.15(a)]Surface Material. The Agent in consultation with the County Engineer has signed off on the use of gravel for this lot.As such,provide a note on the plans stating: "Gravel parking and access aisles have been permitted for the site pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed and constructed as provided in section 4.12." 7. [4.12.16(E)]Bumper Blocks. The Agent in consultation with the County Engineer has waived the requirement for bumper blocks.As such provide the following note on the site plan: "The site will not require bumper blocks for parking spaces pursuant to section 32.3.5 Variations and Exceptions, which allow modification of 32.7.3 Parking, which is designed and constructed as provided in section 4.12" Engineering—John Anderson Review com -. -_ . _, o .e orwar.e. one r ived. Fire and Rescue-Shawn Maddox Review comments pending,to be forwarded once received. Virginia Department of Health—Josh Kirtley Review co_ arded once r d. 4.440-.01 Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office.The Code may found on the County Attorney's website which may be found under"Departments and Services"at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six(6)months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. If you have any questions about the comments please feel free to contact me. Sincerely, Christopher P.Perez Senior Planner Planning Division Review Comments for SDP201800046 (vlinorAmendment ProjectName:trvlint Springs Park - Minor Amendment Date Completed:'Monday November 26 2018 Department'DilisioniAgency: Review Status: Reviewer: John.AndersonCDD Engineering Objection g .I No Ob ection Minor Site Plan Engineering Review comments 1. ACF&R must review proposed access .loop design around proposed new Maintenance Facility to ensure adequate fire-rescue access (Rev. 1)Addressed Ref email Clark Gathright 11/912018 9.27 AM. 2 Well and septic field require VDH /DEQ approval- well testing is required (Rev. 1)Applicant pursuing 3 Code 18-4 1 b 2. for septic field (VDH) review./approval requirements, Ch. 5,Article 5 Private Ground Water Well Testing (Rev 1)A building permit requirement 4 Engineering will consult with planning concerning groundwater study requirements (17-1000). (Rev. 1)Addressed Tier Ill Groundwater Assessment approval email sent. '22912018 1:50 PM 5. VSMP/WPO Plan is in process (Rev 1)Addressed WPO201800060 is approved pending recordation of 3 75 Ac SWM Forest /Open Space Easement 6 VSMP.JWPO Plan approval is required prior to Minor Site Plan approval (Rev 1)Addressed Also see item 5 above 7. Remove sheets 5 and 6. now included with the VSMP 'WPO Plan (Rev 1)Addressed 8. Remove T-1 0 Minimum Standards and General Erosion and Sediment Control Notes now included 'r,lith the VSMP /WPO Plan (Rev 1)Addressed. 9. Sheet 3 (C-1.1): Revise and relocate text to avoid labels occupying same space (near septic field; (Rev 1; Addressed Sheet 4. 10 Revise sheet title to Site Plan (Rev 1)Addressed 11. Remove all reference to ESC elements- include note reading '.'VP0# 'to be assigned (If WPO# is known reference WPO# on sheet 4 (Rev 1)Addressed 12 Label building dimensions (Rev 1)Addressed 13 Provide stone yard typical section_ (Rev_ 1) Comment withdrawn 14 Dimension parking spaces (Rev 1)Addressed 15 Provide bumper blocks (Rev 1) Comment withdrawn 16 Recommend sidewalk front building to preserve interior finishes especially flooring (Rev. 1)NA, design declines to incorporate recommendation_ 17 Eliminate ESC Linetype & Symbols in legend (Rev 1j Addressed 18 Show roof leader lines (Rev 1)Addressed Splash blocks shown Page: 1 County of Albemarle Printed On: 11'3012018 itrand *tie i y�"111 �•P J .101ht r Oa,t'A' COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road,North Wing Charlottesville,Virginia 22902-4596 (434)296-5832 08-30-18 Clark Gathright 100 10th Street Suite 200 Charlottesville VA 22902 RE: SDP2018-46 Mint Spring Park-Minor Amendment Dear Sir: Your Minor Amendment application has been reviewed. In order for the amended site plan to be approved the following revisions are required: 1 .7(C),32.7.91 Buffer zone adjacent to the rural area district. No construction activity including grading or v. el clearing of vegetation shall occur closer than twenty(20)feet to any residential or rural areas district.On the plans relocate the entire proposal 20 feet from the adjacent property line,to provide the 20'buffer zone. This 20'buffer shall also be applied to the entrance road connection to the existing drive. Also,provide a double staggered row of 6'tall evergreen plantings within the 20'buffer zone for the duration of the land disturbance/travelway. ,_, .4.-. [32.5.2(11)]Proposed Improvements. On the plans label the proposed paving material used for the travelway and parking spaces. 3 [4.12.16(e),32.5.2(n)] Proposed Improvements. Provide bumper blocks for all parking spaces. Each bumper block shall be a minimum length of six(6)feet,a maximum height of five(5)inches,and shall be securely anchored into the pavement in at least two(2)places. Rev1: The County Engineer has waived the bumper block requirement upon the request of the applicant. V1. [32.5.2(n)]Proposed Improvements. Dimension parking spaces and the building. [32.5.2(n)]Proposed Improvements. On the plans depict the general physical location of all existing improvements on the property and the location of the proposed improvements.This can consist of a breakout of SDP000-234. t76:- [32.5.2(n)] General Information. On sheet 3,provide TMPs of adjacent owners and parcel boundaries. tel. [32.5.2(n)]Proposed Improvements. Provide the square footage of the new paved area. t.8( [32.5.2(n)] General Information. On sheet 1 under zoning,provide the maximum building height of 35'. [32.6.2(k)&4.17]Lighting. Provide a cut sheet with luminaire schedule for each proposed light fixture.Also, ��provide the location of the outdoor lighting fixtures. 10{[Comment] Revise the title of the plan: "SDP2018-46 Mint Spring Park—Minor Amendment". i it Comment] The Health Department approval is required prior to minor site planapproval.Comments pending to be forwarded upon receipt.Rev 1: Comments have been provided to the applicant.VDH is unable to review the proposal at this time,as they do not have soil work for the prop$al. r • 12. [Comment] A Tier 3 groundwater study is required to be approved prior to minor site plan approval. Engineering staff has received the study and is reviewing it. Comments or approval on this item is forthcoming. Rev 1:Approved. Engineering—John Anderson Minor Site Plan Engineering Review comments: 1.ACF&R must review proposed access/loop design around proposed new Maintenance Facility to ensure adequate fire-rescue access. 2.Well and septic field require VDH/DEQ approval;well testing is required. 3.Code 18-4.1.b.2.for septic field(VDH)review/approval requirements;Ch. 5,Article 5,Private Ground Water Well Testing. 4.Engineering will consult with planning concerning groundwater study requirements(17-1000). 5.VSMP/WPO Plan is in process.(.PDF previewed;plan revised in response to comments;WPO#to be assigned.) 6.VSMP/WPO Plan approval is required prior to Minor Site Plan approval. 7. Remove sheets 5 and 6,now included with the VSMP/WPO Plan. 8.Remove T-1.0 Minimum Standards and General Erosion and Sediment Control Notes,now included with the VSMP/WPO Plan. 9. Sheet 3 (C-1.1):Revise and relocate text to avoid labels occupying same space(near septic field). Sheet 4: 10.Revise sheet title to Site Plan. 11.Remove all reference to ESC elements;include note reading: 'WPO# 'to be assigned.' (If WPO#is known,reference WPO#on sheet 4.) 12.Label building dimensions. 13.Provide stone yard typical section. 14.Dimension parking spaces. 15.Provide bumper blocks. 16.Recommend sidewalk front building to preserve interior finishes,especially flooring. 17.Eliminate ESC Linetype&Symbols in legend. 18. Show roof leader lines. Fire and Rescue-Shawn Maddox 1.A knox box will be required on any gate. This knox box may include building keys as well. 2.The 10'existing gravel driveway does not meet required emergency apparatus access.A minimum of 20'clear width of an approved surface must be provided. 3.Please show turning radii around the building.An approved turnaround is not provided however if apparatus can drive around the building to exit a turnaround may not be necessary. Please contact our office with any questions,434-296-5833. SNM Virginia Department of Health—Josh Kirtley 1. VDH is unable to review the proposal at this time,as they do not have soil work for the proposal. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office.The Code may found on the County Attorney's website which may be found under"Departments and Services"at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six(6)months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. If you have any questions about the comments please feel free to contact me. Sincerely, i Christopher P.Perez Senior Planner Planning Division COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902-4596 (434) 296-5832 08-30-18 Clark Gathright 100 10' Street Suite 200 Charlottesville VA 22902 RE: SDP2018-46 Mint Spring Park - Minor Amendment Dear Sir: Your Minor Amendment application has been reviewed. In order for the amended site plan to be approved the following revisions are required: L 121.7(C), 32.7.91 Buffer zone adjacent to the rural area district. No construction activity including grading or clearing of vegetation shall occur closer than twenty (20) feet to any residential or rural areas district. On the plans relocate the entire proposal 20 feet from the adjacent property line, to provide the 20' buffer zone. This 20' buffer shall also be applied to the entrance road connection to the existing drive. Also, provide a double staggered row of 6' tall evergreen plantings within the 20' buffer zone for the duration of the land disturbance/travelway. Revl: Comment was generated by Zoning, per conversations with the Chief of Planning the comment has been redacted. 2. [32.5.2(n)] Proposed Improvements. On the plans label the proposed paving material used for the travelway and parking spaces. 3. [4.12.16(e), 32.5.2(n)] Proposed Improvements. Provide bumper blocks for all parking spaces. Each bumper block shall be a minimum length of six (6) feet, a maximum height of five (5) inches, and shall be securely anchored into the pavement in at least two (2) places. Revl: The County Engineer has waived the bumper block requirement upon the request of the applicant. 4. [32.5.2(n)] Proposed Improvements. Dimension parking spaces and the building. 5. [32.5.2(n)] Proposed Improvements. On the plans depict the general physical location of all existing improvements on the property and the location of the proposed improvements. This can consist of a breakout of SDP000-234. 6. [32.5.2(n)] General Information. On sheet 3, provide TMPs of adjacent owners and parcel boundaries. 7. [32.5.2(n)] Proposed Improvements. Provide the square footage of the new paved area. 8. [32.5.2(n)] General Information. On sheet 1 under zoning, provide the maximum building height of 35'. 9. [32.6.2(k) & 4.171 Lighting. Provide a cut sheet with luminaire schedule for each proposed light fixture. Also, provide the location of the outdoor lighting fixtures. 10. [Comment] Revise the title of the plan: "SDP2018-46 Mint Spring Park — Minor Amendment ". 11. [Comment] The Health Department approval is required prior to minor site plan approval. Comments pending to be forwarded upon receipt. Rev 1: Comments have been provided to the applicant. VDH is unable to review the proposal at this time, as they do not have soil work for the proposal. 12. [Comment] A Tier 3 groundwater study is required to be approved prior to minor site plan approval. Engineering staff has received the study and is reviewing it. Comments or approval on this item is forthcoming. Rev 1: Approved. Engineering — John Anderson Minor Site Plan Engineering Review comments: 1. ACF&R must review proposed access /loop design around proposed new Maintenance Facility to ensure adequate fire -rescue access. 2. Well and septic field require VDH /DEQ approval; well testing is required. 3. Code 18-4.1.b.2. for septic field (VDH) review /approval requirements; Ch. 5, Article 5, Private Ground Water Well Testing. 4. Engineering will consult with planning concerning groundwater study requirements (17-1000). 5. VSMP /WPO Plan is in process. (.PDF previewed; plan revised in response to comments; WPO# to be assigned.) 6. VSMP /WPO Plan approval is required prior to Minor Site Plan approval. 7. Remove sheets 5 and 6, now included with the VSMP /WPO Plan. 8. Remove T-1.0 Minimum Standards and General Erosion and Sediment Control Notes, now included with the VSMP /WPO Plan. 9. Sheet 3 (C-1.1): Revise and relocate text to avoid labels occupying same space (near septic field). Sheet 4: 10. Revise sheet title to Site Plan. 11. Remove all reference to ESC elements; include note reading: `WPO# `to be assigned.' (If WPO# is known, reference WPO# on sheet 4.) 12. Label building dimensions. 13. Provide stone yard typical section. 14. Dimension parking spaces. 15. Provide bumper blocks. 16. Recommend sidewalk front building to preserve interior finishes, especially flooring. 17. Eliminate ESC Linetype & Symbols in legend. 18. Show roof leader lines. Fire and Rescue - Shawn Maddox 1. A knox box will be required on any gate. This knox box may include building keys as well. 2. The 10' existing gravel driveway does not meet required emergency apparatus access. A minimum of 20' clear width of an approved surface must be provided. 3. Please show turning radii around the building. An approved turnaround is not provided however if apparatus can drive around the building to exit a turnaround may not be necessary. Please contact our office with any questions, 434-296-5833. SNM Virginia Department of Health — Josh Kirtley 1. VDH is unable to review the proposal at this time, as they do not have soil work for the proposal. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may found on the County Attorney's website which may be found under "Departments and Services" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six (6) months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. If you have any questions about the comments please feel free to contact me. Sincerely, Christopher P. Perez Senior Planner Planning Division Review Gommentc for SDP201800046 Minor Amendment Project Name: Mint Springs Park- MinorAmendment Date Completed: Monday, August 27. 2018 Department'Di.ision,Agenc Review Status: Reviewer: John Anderson • CDD Engineering Approved Tier Ill Groundwater Assessment email Attachment from C Gathright. 8/112018 10.34 AM (in RMS docs) Mint Springs Park Maintenance Building Tier 3 Groundwater Assessment /Groundwater Management Plan (report) is approved pending receipt of CPG signature (Nick H. Evans PhD CPG). PE-seal (Clark Gathright. PE) copy of report Please delete reference to draft report (title pg.). and email .PDF scan of signed /PE-sealed report to Albemarle County/engineering janderson2@albemarle org Please send he /original report follow-up for our files. Thank you update Final Report received /approved: see RMS Doc. -Approval email sent: 8/ it. 018 1:50 PM / janderson2 829/2018 1.51 PM J rbeo Page: 1 County of.Albemarle Printed On: 1'1'311.'2018 /1111#0 eprail �F ALg�,tr t7�;3�P COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road,North Wing Charlottesville,Virginia 22902-4596 (434) 296-5832 August 23,2018 Clark Gathright 100 10th Street Suite 200 Charlottesville VA 22902 RE: SDP2018-46 Mint Spring Park-Minor Amendment Dear Sir: Your Minor Amendment application has been reviewed. In order for the amended site plan to be approved the following revisions are required: 1. [21.7(C),32.7.9]Buffer zone adjacent to the rural area district. No construction activity including grading or clearing of vegetation shall occur closer than twenty(20)feet to any residential or rural areas district. On the plans relocate the entire proposal 20 feet from the adjacent property line,to provide the 20'buffer zone.This 20'buffer shall also be applied to the entrance road connection to the existing drive. Also,provide a double staggered row of 6' tall evergreen plantings within the 20'buffer zone for the duration of the land disturbance/travelway. 2. [32.5.2(n)]Proposed Improvements. On the plans label the proposed paving material used for the travelway and parking spaces. 3. [4.12.16(e),32.5.2(n)]Proposed Improvements. Provide bumper blocks for all parking spaces. Each bumper block shall be a minimum length of six(6)feet,a maximum height of five(5)inches,and shall be securely anchored into the pavement in at least two(2)places. 4. [32.5.2(n)]Proposed Improvements. Dimension parking spaces and the building. 5. [32.5.2(n)] Proposed Improvements. On the plans depict the general physical location of all existing improvements on the property and the location of the proposed improvements.This can consist of a breakout of SDP000-234. 6. [32.5.2(n)] General Information. On sheet 3,provide TMPs of adjacent owners and parcel boundaries. 7. [32.5.2(n)]Proposed Improvements. Provide the square footage of the new paved area. 8. [32.5.2(n)] General Information. On sheet 1 under zoning,provide the maximum building height of 35'. 9. [32.6.2(k)&4.17]Lighting. Provide a cut sheet with luminaire schedule for each proposed light fixture.Also, provide the location of the outdoor lighting fixtures. 10. [Comment] Revise the title of the plan: "SDP2018-46 Mint Spring Park—Minor Amendment". 11. [Comment] The Health Department approval is required prior to minor site plan approval. Comments pending to be forwarded upon receipt. 111 .41 12. [Comment] A Tier 3 groundwater study is required to be approved prior tonor site plan approval. Engineering staff has received the study and is reviewing it. Comments or approval on this item is forthcoming. Engineering—John Anderson Minor Site Plan Engineering Review comments: 1.ACF&R must review proposed access/loop design around proposed new Maintenance Facility to ensure adequate fire-rescue access. 2. Well and septic field require VDH/DEQ approval;well testing is required. 3.Code 18-4.1.b.2. for septic field(VDH)review/approval requirements; Ch. 5,Article 5,Private Ground Water Well Testing. 4. Engineering will consult with planning concerning groundwater study requirements(17-1000). 5.VSMP/WPO Plan is in process. (.PDF previewed;plan revised in response to comments;WPO#to be assigned.) 6.VSMP/WPO Plan approval is required prior to Minor Site Plan approval. 7. Remove sheets 5 and 6,now included with the VSMP/WPO Plan. 8. Remove T-1.0 Minimum Standards and General Erosion and Sediment Control Notes,now included with the VSMP/WPO Plan. 9. Sheet 3 (C-1.1): Revise and relocate text to avoid labels occupying same space(near septic field). Sheet 4: 10. Revise sheet title to Site Plan. 11. Remove all reference to ESC elements;include note reading: 'WPO# 'to be assigned.' (If WPO#is known,reference WPO#on sheet 4.) 12.Label building dimensions. 13.Provide stone yard typical section. 14. Dimension parking spaces. 15.Provide bumper blocks. 16. Recommend sidewalk front building to preserve interior finishes,especially flooring. 17. Eliminate ESC Linetype&Symbols in legend. 18. Show roof leader lines. Fire and Rescue-Shawn Maddox 1. A knox box will be required on any gate. This knox box may include building keys as well. 2.The 10'existing gravel driveway does not meet required emergency apparatus access.A minimum of 20'clear width of an approved surface must be provided. 3. Please show turning radii around the building. An approved turnaround is not provided however if apparatus can drive around the building to exit a turnaround may not be necessary. Please contact our office with any questions,434-296-5833. SNM Virginia Department of Health—Josh Kirtley Comments pending,to be forwarded once received. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office.The Code may found on the County Attorney's website which may be found under"Departments and Services"at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six(6)months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. If you have any questions about the comments please feel free to contact me. Sincerely, j •/ - / _ e Christopher P. Perez Senior Planner Planning Division