June 5, 2018 RE: Rivanna Water and Sewer Authority
SDP-2018-00024-Minor
' Crozet WTP Expansion and Rehabilitation
Project
SEH No. RIVAN 144134 14.00
David Benish
Chief of Planning
County of Albemarle Department of Community Development
401 McIntire Road
Charlottesville,VA 22902
Dear David Benish:
This letter is supplemental to the second submission of the Minor Amendment application for Crozet WTP
Expansion and Rehabilitation Project, SDP201800024. Responses to comments on the initial submittal
dated May 25, 2018, are outlined below.
1. [Comment] Page one, cover sheet, correct: 1) spelling in the"...and to approve site plan
ammendment SDP#20600065,"2) information regarding TMP 57-10Am which is printed over other
type making information illegible.
a. Spelling error and overlapping text addressed on cover sheet.
2. [4.10.3; 4.10.3.1.a&b] Provide height of the PAC silo. Height of the structure may be limited by
4.10.3.1(b). The height of the structure is limited to its distance from the property line and the location
shown on the site plan which appears to be approximately 43 from the property line.
a. PAC silo height added to cover sheet Height of the silo is 30-feet, plus an additional a5-feet for
the railing. Total height of the PAC silo is 33.5-feet.
3. [32.7.2.1] Vehicular Access to Site. Each entrance onto any public street shall be designed and
constructed as required by the standards of the Virginia Department of Transporation. VDOT
approval of the entrance to the site shall be required prior to final site plan approval.
a. Acknowledge. All VDOT comments and responses listed below.
4. Recommend that use of Leyland Cypress be reconsidered for screening/buffering along the proposed
ACSA easement adjacent to the Highlands development. While Leyland are a permitted species for
screening,they do not have a long life expectancy.
a. Leyland Cypress trees have been replaced with Eastern Red Cedars. See sheet 12.
Architectural Review Board—Margaret Maliszewski
a. Responses provide in a separate letter to Margaret Maliszewski.
Fire and Rescue—Shawn Maddox
Engineers I Architects I Planners I Scientists
• Short Elliott Hendrickson Inc.,3535 Vadnais Center Drive,St.Paul,MN 5 511 0-51 96
SEH is 100%employee-owned I sehinc.com I 651.490.2000 I 800.325.2055 I 888.908.8166 fax
David Benish
June 5, 2018
Page 2
1. If there are no existing hydrants on the site and water line work is to be performed a hydrant should
be added. A location can be coordinated with Fire Rescue.
a. Existing fire hydrant located at the front of the Water Treatment Filter Building to remian. No work
to existing potable drinking water system is proposed. All new work to involve non-potable plant
process waterlines.
2. It is unclear if any site access work will be done. Fire rescue requires access to within 150' of
structures. Appropriate emergency apparatus turn arounds shall be provided if possible.
a. No improvements am proposed to the driveway entrance at the WTP. Only minor improvements
are proposed at the driveway entrance to the backwash tank and lagoon. Both structures are
within 150'from the roadway. Adding emergency apparatus turn arounds is not feasible at this
location.
Building Inspection—Michael Dellinger
No comments
a. No action required.
Engineering—Mathew Wentland
a. Responses provide in a separate letter to Mathew Wentland.
VDOT—Adam Moore
1. Will the proposed casing pipes crossing Route 240 be bored? Utility crossings are typically required
to be bored.
a. Yes, the proposed casing pipes crossing route 240 will be bored. Can-ier pipes will be installed
inside the bored casing pipes. See sheet 4.
ACSA—Alex Morrison
1. Flow acceptance from RWA will be required.
a. Acknowledged. A representative of RWSA to contact ACSA for further discussion.
2. A flow meter will be required to measure water discharged from treatment facility.
a. As per previous discussions with ACSA engineer Jeremy Lynn, all ACSA potable water used at
the treatment facility will be, or already is, metered. The meters were added as part of the
previous GAC and Finished Water Pump Station(FWPS)projects. A finished water flow meter is
to be installed on the discharge side of the FWPS prior to distribution, as part of the FWPS
project. RWSA believes they have coordinated all ACSA metering needs at this time.
3. All pipe to be installed will be privately owned.
a. Acknowledged.
4. TMP 57-10A is not the ACSA jurisdiction area. [Amendment request now under review-DBB]
a. Acknowledged. A representative of RWSA to contact ACSA for further discussion.
5. TMP 57-29B is called-out as water to existing structures only(limited service). [Amendment request
now under review—DBE].
a. Acknowledged. A representative of RWSA to contact ACSA for further discussion.
Additional changes from submittal 1 included:
Scope of Work:
David Benish
June 5, 2018
Page 3
1. Additional work has been added to the scope of the project. The additional work includes
connecting the sanitary sewer services from the filtration building, and the eastern ACSA
maintenance building to the proposed sanitary sewer forcemain. ACSA is in agreement with this
proposed work The additional work will result in 0.21 acres of additional disturbance. Surface
condition will be restored to pre-construction condition. Thus no changes to the pre and post
impervious coverage: Changes due to the work added are noted below.
Plans:
1. Sheet 1. Cover Sheet, updated with county comments.
2. Sheet 3. Demolition, updated with sanitary sewer services for the Filter Building, and ACSA
maintenance garage.
3. Sheet 4. Proposed Improvements, updated with sanitary sewer services for the Filter Building,
and ACSA maintenance garage.
4. Sheet 5. Grading and Drainage,added watermain connection on the Loading Dock Grading
detail, and aggregate thickness on the Typical Loading Dock Grading Section detail.
5. Sheet 6. Utilities Plan, updated with sanitary sewer services for the Filter Building, and ACSA
maintenance garage.
6. Sheet 7. Utilities Plan 2,added sheet for the sanitary sewer services for the Filter Building, and
ACSA maintenance garage.
7. Sheet 10. Utilities Sanitary Sewer Profile,added sheet for the sanitary sewer services for the
Filter Building, and ACSA maintenance garage.
8. Sheets 11.& 12. Landscaping Plan, (sheets 9 &10 in previous submittal) removed or replace
Leyland cypress with Eastern Red Cedar, spaced out plantings, added Eastern Red Cedar on the
north side of the access drive, per ARB and SDP comments.
9. Sheet 14. Details 2, (sheet 12 in previous submittal)added details.
10. Sheet 15. Details 3, (sheet 13 in previous submittal) added details.
11. Sheet 17. Details 5, added sheet for additional details.
12. Sheet 18. Site Photometrics, (sheet 15 in previous submittal) updated with ARB comments.
13. Sheet 19. Fixture Cut Sheets, (sheet 16 in previous submittal) updated with ARB comments.
If you have any questions or require any additional information, please contact me at 434.409.0464.
Sincerely,
SHORT ELLIOTT HENDRICKSON INC.
/915.-
Douglas March
Sr Professional Engineer II
MNT
Enclosure
Plans (2 full size copies and one 11x17 copies)
\1sp3020-1\projects\pOMvenl144134\3-env-stdy-regs\38-reg\2.sdp\submittaRsubmittal 2W.0 sdp_submittal 1 response letter.docx
I l
�OF
d.
n
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,North Wing
Charlottesville,Virginia 22902-4596
Phone(434) 296-5832 Fax(434) 972-4126
May 25,2018
Douglas March
695 Moore's Creek Ln
Charlottesville VA 22902
RE: SDP201800024—Improvements to Crozet Water Treatment Facility,Minor
Dear Sir:
Your Minor Amendment application has been reviewed.In order for the amended site plan to be
approved the following revisions are required:
1. [Comment] Page one,cover sheet,correct: 1)spelling in the"...and to approved site plan
ammendement SDP#20600065," 2) information regarding TMP 57-10A,which is printed over other type
making information illegible.
2. [4.10.3; 4.10.3.1.a&b] Provide height of the PAC silo. Height of the structure may be limited by
4.10.3.1(b). The height of the structure is limited to its distance from the property line and the location
shown on the site plan which appears to be approximately 43 from the property line.
•
3. 132.7.2.1] Vehicular Access to Site. Each entrance onto any public street shall be designed and
constructed as required by the standards of the Virginia Department of Transportation.VDOT approval of
the entrance to the site shall be required prior to final site plan approval.
4. Recommend that use of Leyland Cypress be reconsidered for screening/buffering along the proposed
ACSA easement adjacent to the Highlands development.While Leyland are a permitted species for
screening,they do not have a long life expectancy.
Architectural Review Board—Margaret Maliszewski
1.Provide specs for the proposed window glass. Ensure that VLT is not below 40%and VLR
does not exceed 30%.Add the standard window glass note to the drawings.
2. Add screening trees or tall screening shrubs to reduce visibility of the equipment on the east
side of the WTP building.
3. Revise the photometric plan to reduce illumination levels to not exceed 20 fc in all areas
outside the WTP sediment basins.
4. Ensure that the photometrics are calculated using an LLF of 1.0 and note the LLF on the
lighting plan.
5.Revise the fixtures to use LED lamps with a consistent warm white color temperature.
6.Provide a luminaire schedule on the plan that identifies fixture height.
7. Label the fixtures on the lighting plan(13 of 31)to coordinate with the cut sheets.
8.Extend the staggered row of evergreen plants down the north/west side of the access road to
provide greater screening.
9.Consider increasing the spacing between plants based on anticipated mature size.
10.Revise the plans to show a tree line to remain in the area where pipes are shown crossing the
road,and revise the landscape plan to show how this area will be replanted to attain an
appearance consistent with the surroundings.
11.Reconsider the Leyland cypress for screening.
12. Consider adding screening at the loading dock.
Fire and Rescue—Shawn Maddox
1.If there are no existing hydrants on the site and water line work is to be performed a hydrant should be
added.A location can be coordinated with Fire Rescue.
2.It is unclear if any site access work will be done. Fire rescue requires access to within 150'of
structures.Appropriate emergency apparatus turn arounds shall be provided if possible.
Building Inspections—Michael Dellinger
No comments
Engineering—Matthew Wentland
A VSMP amendment will need to be approved prior to the Minor Amendment approval.
VDOT—Adam Moore
Comments attached[comments review to wrong application file number but are intended to address this
request-DBB]
ACSA—Alex Morrison
Crozet Sewer Treatment Plant Minor Site Plan Amendment—
• Flow acceptance from RWSA will be required.
• A flow meter will be required to measure water discharged from treatment facility.
• All pipe to be Stalled will be privately owned.
• TMP 57-10A is not in the ACSA jurisdictional area. [Amendment request now under review—
DBB]
• TMP 57-29B is called-out as water to existing structures only(limited service). [Amendment
request now under review-DBB]
•
Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The
Code is kept up to date by the County Attorney's office. The Code may found on the County Attorney's
website which may be found under"Departments and Services"at Albemarle.org.
In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to
submit a revised final site plan to address all of the requirements within six(6)months after the date of
this letter the application shall be deemed to have been voluntarily withdrawn by the developer. If you
have any questions about the comments please feel free to contact me.
Sincerely,
David Benish
Chief of Planning
Planning Division
V
c
at
.sE6 8 SE4,44, RIVANNA WATER AND SEWER AUTHORITY
y 695 Moores Creek Lane•Charlottesville,Virginia 22902-9016
(434)977-2970
f
April 9,2018
Albemarle County Department of Community Development
401 McIntire Road
Charlottesville,VA 22902
Attention: Mr.David Benish
Chief of Planning—Implementation
Subject: Crozet Water Treatment Plant Expansion
County Applications
Dear David,
As we've discussed,RWSA is in the process of designing an expansion to the Crozet Water Treatment Plant. I am
submitting for your review and comment the following:
1. Application for Special Exception
2. Application to Amend the Service Authority Jurisdictional Area for Parcel 057-10A
3. Application to Amend the Service Authority Jurisdictional Area for Parcel 057-29B
Thank you for your assistance and please contact me with questions or comments.
Respectfully submitted,
Thomas E.Freeman,PE
Senior Civil Engineer
SEH
Building a Better World
for All of Us'
April 9, 2018 RE: Rivanna Water& Sewer Authority
Crozet Water Treatment Plant Expansion
and Rehabilitation Project
TMP 57-10A and 57-29B
4685 Three Notch'd Road
Request for Special Exception—
County Code Chapter 18, Section
26.5.c-d
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville,VA 22902
The Rivanna Water and Sewer Authority (RWSA) is proposing water treatment plant upgrade and
rehabilitation improvements to its existing Crozet Water Treatment Plant. The RWSA has contracted with
Short Elliott Hendrickson (SEH) to complete engineering design plans for the project. On November 13,
2017 SEH met with county staff in a Pre-application Meeting to discuss the proposed work in regards to
site planning and county permitting requirements. One topic discussed was the RWSA's desire to improve
the WTP filter backwash storage system as part of the project. This improvement will result in disturbance
within an existing 30' undisturbed buffer which runs along the south property line of TMP 57-29B. The
RWSA parcel is currently zoned light industrial, and the adjacent property to the south is residential. The
proposed disturbance will include installation of a buried 4 inch diameter sanitary sewer pipeline and
proposed tree screening improvements. This letter is a formal request to the County Board of Supervisors
to grant a Special Exception in regards to the county code (Chapter 18, Sections 26.5.c-d).
Project Background:
Due to consistent growth in the Crozet area, the RWSA is experiencing higher potable water demands at
its Crozet WTP facility. In an effort to modernize for better efficiency, and to upgrade the current plant
demand capacity, the RWSA has instituted various improvement projects at the plant site in the past few
years. The latest proposal is the Crozet WTP Expansion and Rehabilitation Project, which will consist of
plant filter and sedimentation basin upgrade/rehabilitation, filter backwash storage and disposal
improvements,chemical feed and storage upgrades, and applicable site utility piping improvements.
The improvements proposed for the filter backwash storage system will provide various benefits to plant
operation and storage lagoon maintenance. The proposed improvements will consist of a covered storage
tank for the backwash water, in place of an open lagoon settling system. The covered storage tank will
allow backwash water to be temporarily stored and then slowly pumped out and discharged into the existing
ACSA sanitary sewer system, which exists in the residential area adjacent to the south property line of the
Crozet WTP. The backwash water will be pumped through a 4 inch diameter buried pipeline. In order to
reach the existing sanitary sewer system, the pipeline will have to cross an existing 30' wide undisturbed
buffer located within the RWSA parcel. The disturbance caused by this crossing is the basis of the request
for Special Exception.The RWSA feels that the proposed backwash water pipeline installation will result in
numerous benefits for operation and maintenance of the Crozet WTP. In addition, the temporary ground
Engineers I Architects I Planners I Scientists
Short Elliott Hendrickson Inc.,3535 Vadnais Center Drive,St.Paul,MN 55110-5196
SEH is 100%employee-owned I sehinc.com I 651.490.2000 I 800.325.2055 I 888.908.8166 fax
County of Albemarle
April 9, 2018
Page 2
disturbance experienced during pipeline construction will cause minimal,temporary,impacts to the adjacent
residential neighborhood. The ground will be restored to its existing grassed condition after the pipeline is
placed into service. In an effort to stay within accordance with existing county code requirements for a
Special Exception request, the RWSA is proposing to increase the landscape screening between the plant
site and adjacent residential home as part of the overall project.
Proposed Screening Improvements:
Currently the only screening within the area of the proposed pipeline disturbance is one evergreen tree
approximately 20 feet in height. The RWSA proposes to maintain and protect the existing tree, and also
add more landscape screening to meet or exceed current county code requirements. This will consist of
planting approximately 8 evergreen trees 15 feet on center in a double staggered row within a 20 foot width.
The RWSA respectively requests that all new tree plantings be kept a minimum of 10 feet away from the
new pipeline and appurtenances.This space will allow for future pipeline access and maintenance. See the
attached Figure 1 showing the proposed project location and pipeline alignment. Figure 2 shows the
proposed new landscape screening in the southwest corner of the RWSA property.
On behalf of the RWSA, SEH respectfully requests that the County of Albemarle Board of Supervisors
review and approve this Request for Special Exception.
Sincerely,
SHORT ELLIOTT HENDRICKSON INC.
Miles B. Jensen, P.E.
Regional Practice Center Leader
Enclosure— Figure 1
Figure 2
s:\pl\rlrivan114413413-env-stdy-regs138-regal.se(special exception)lrequesl for special exception.docx
ExcEpRopoci ow
PLOT1ED• 4-9-2016 12 27 PM -a SPIWWWW\1441345-FINAL-DSCNT1/451-DRAWNGST10-CINLVADWWG\SHEED,WDOAL
BAWD: 4-9-2010 12 27 RA USSR. TROPOR T ROMANIS° PLOT SCN_E
1 •/• ;
T ,„
1Agl‘l i 11T TT\ .. 1 F1 1 i 1 ' -- -, -
, — -
1 "----t 1
•
' J. e
/
; 1,‘ "o; .. .."
, \i, i ,. L. , ,,, . ) ', ,'. ,r ' . ' ‘ ,",',1 , ' I
,i'I,i,, el
' ,
.....,.,
- , 'rice', L,4 r i
, \
k )1“ pH= ,
•) ,( ', i I _
. Sc11, i
I 1 t
“. - ir • ,
-------- ',-. ,_
•- " I1('W• ly ; ,,‘_
._
,-/ I/INV ' ) ''',
• ' ' ' ' '1," //' . ,t'fre '' ':
- 7:"... . 7 - ',:•( ! ' 1
jr•-)‘••-, / , ;•' 's• ‘).. „,‘
) '); ,,-/-:Ce= ,..........-----•-• )
I''• '<< /-„,,'-',,kind•-‘ ,-"-7-‘7
)" , ' y , , ' r f ', •)////1'4 . / ,,
•-) , / ' L'q • 1 ') ' ;•1//),(///yr.)/ , , li) ,,0 ;
,.. _ , -...:. _
`,.. ' 1'1, !ir
= I
'', , il
"\ ;,.i,(lc i:11i 1 c IN
,...._.
' 1.:: .-.::1 .- :CS' .::'''7 / ‘-.::::" f
, •
A\ ‘-'... '1('NO' , *-nennin , t - 1. Cj '..1-''/ \ ''I'. . k'::Ik.'.'11 1 Pa,'
,
/ ,./ ;");;;"i ','',,,. ":.„--_,;-,-e,-' ,,•,„ _, , „,,:c.f.;mi.,,,,,,t '
7
,
\ . „.,--:>-•.,„... - . I ,- -. ? \ -p,--, -- 4,., 2
, , / ,
'1 I ' ' `'-A.-: ' \ . ? (..?
\ , • \ • .., ), ,- . Y- ,,',. , 11 ' -..L'(- ----4-.."'42 4 4.T.')s-kt\\Ir.,,e4— .,,,, 4 ..1 ;f , '' , — , , F„)°,,,?. . ' :, . \ , -'s ,, \-, , ' , ‘ -,i n , , • , Rritilit, ! 1 , ,, , - , ,, , ,, , .,, •-,,, -,
. 1 4
,R8L4„ ; s—c__ ___ ..2--zt2 .;_ --j-,:, ;
' ' 1A • Tnr120' ' ' 1s ss' si ‘' T ' 1 ' ss1. - i''''' 'C-TS*14-.-- 'I j .-'1 I/ ' • 1 1 ' 1 S I "&I , , r 3 ) S 1 ' c \ ' ''111-.-•
T.,... ' ? ,
'' ”"/ --- 1 ,
T T . 441 a"
re)
es
>
R I
t,
m
m
-I
0
.-- „
Sal FILE NO. R1VAN 144134 CROZET WATER TREATMENT PLANT
SHEET IDLE
EXPANSION AND REHABILITATION
_...... 3sTs=yr"
RWSA RFS NO.
SITE AND EXISTING PROJECT STATUS PRELIM
PROJECT 71 CONDITIONS ISSUE DATE 02/22/2018
.....a pEcwe 6E14E32=
'Axes;4m213:,RIVANNA SEWER&WATER AUTHORITY
— w DESIGNED BY 1TR
TOLL wEs mans ass
G) rl
DRAWN BY 1TR
REQUEST FOR SPECIAL EXCEPTION NOT FOR CONSTRUCTION
SEH m
--• Short Soli Hendrickson.hc 0
MAW REVISIONS DATE DOCRIPTION ALBEMARLE COUNTY,VIRGINIA
ISEK)
of AI
14
COUNTY OF ALBEMARLE
Department of Community Development
401 Mclntire Road,North Wing
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
DATE
Contact
Company
Company I/"fflt� 7 r Gam' C)7I 6916
J/1
Address
City State Zip r! !t 1 t l 04
RE:SDP-
Dear Sir or Madam:
Your final plan has been reviewed. In order for the final plan to be approved the following revisions are
required:
1. [Section]
2. [Section]
Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The
Code is kept up to date by the County Attorney's office.The Code may found on the County Attorney's
website which may be found under"Departments and Services"at Albemarle.org.
In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to
submit a revised final site plan to address all of the requirements within six(6)months after the date of
this letter the application shall be deemed to have been voluntarily withdrawn by the developer.
If you have any questions about the comments please feel free to contact me.
Sincerely,
Senior Planner/Planner
Planning Division
2,14 P-e-R5'' -e?)/
�� rggq v
-190 nretP acc419"1r619 ri.71'129 Criattk Slier49 —6114ao
_critical slopes with 4 foot contour elev.
�- �r� \ L` etems on map may not appear in\f/1/ \ l\��
�// `` ✓ 616 /) \ \
----------1-7:-...\\
Elaor
57-9D 636 h _� / m-owl„a~
4696
4708 7:\\\.„,,,\__,57:12
s�\
z..Z.:7;tr 4: 574\
7-11
(-L-'-1-.'<''/'--'/6264�!� ✓�
el -___ );(;-----------()t I
a v 1365 \� ' ({ 62p
164 --t-—_____-.....,
i r/5..------ 1395 .-, '
,s
^/ 57A-2C 38�\ ?' �---�'
�itn� \\ 57A- C 36\
�,. ` 1405 64p 4652 4636
fi 240�- K.--t .:
AMBER'R!DGE RD 7 �` 64
4
4624�
^y ' •
`y�C1400e20 4683 ' `THREE.N
e' \b`! \ O TC H D-
137 Too
� � G� _ RD
v�, 57A=2C=39 `�a � � 1 4' + � � 3---\------_____
v ,1360 w
) , ,
_ N, ai N Qt
Zr-- 4685 t / 4679
n 21 --- - i_/ ' _ -298 _ /
'v, �-c_-_- r� /-(5/7
/yi 'r 57A-2B-20
!. 1305 1307 // /� 658.n: �652 �29E6
o J
z_______,
m 4677
1yi : 57A2B 21 g_c�
A
1~t ' r 4675 4671
` 17 1313 1 ,
57A`26--22
57 112g-.16 b ________ ;
--. __ ,-.'"- 7 -----)
122 ft S7A 26 23 57-29E4 _______.-- 57-29E5 ( r',, ,, Gls-wen
1 V I n^nv�1 r 1321 ' l _ p Geographic Data Services
5•ZIIIII I I 2 j www4)296-5832 albernane rg
yty,+•�`57A-28-24 l j �''�s (a341296-5832
Map is for Display Purposes Only•Aenal Imagery from the Commonwealth of Virginia and Other Sources May 14,2018
�_ ` / Legend
h (Note::ome items on map may not appear in legend)
..... I \ 1
------__________ . \ 2 1 ) ) i
o• Rvn
rs..rn.
��, 57-10P..STATION
i / ii
/\ H' iii / I ▪aa�.a..�
57-9 --"—\\ %, /�
)\ .
./ 616
�
r `
57-11
57:10A
y
'i 624 ft�
636 h�—'l
,,8.ff r640'II-
465 0i-..,k. f41,16
' -10. ,.'',,_-,.i
1
J
644-- r. ►
240. ��= ,„11
1/
THREE NOTc
63 ft ea sit H'o Ro
of 1NR
clsweb
o�`,'� Geographic Data Services
a` � www.albemarle.org
5?-29E 6 ` (434)296-5832
Map is for Display Purposes Only•Aerial Imagery born the Commonwealth of Virginia and Other Sources May 14.2018
\�s� Legend
a,_ r d -,• �� s \ Note Some items on map may not aPPear in legend)
4 -` 60 . i� � \ 1
8 /�� . ,
/6 �
--- ---________:-------________ ------.... "------ ''. / c:t ° 6! a' \ V',Z.7='-'-'''''
1\X
...---"' --___________:j------- \\\
� 57-9D 636'ft �� �' ' a
�4708'' 6�\
/ �j 57-13
- Water Protection
_____,_ , \
Ordinance Buffer 7 1� 57-12
fl,/
624�/•
—1385 4, 632'________.___________It
r i 7 1/57A-2Cr34 s`12? %4104 �Q -\
% -'#
-� 1cn/
, \� 57AC--36\
1 � � -2 690.E 240
�
AMBER'RIDGE RD �644K
y / ( 484
-
ill
�::'I3701 �, \i?C� 24\� '. HREE.IyO.7CH.
0-RD
i-y-`-57A-2C--39 `d, - -- /
U ,r1380 t ;J 111
/ A ) 1111.r.
/r. co ? 4685''; 4679 .
I��-- - - ,i _ s7_z96 1
D.,.----- -""a.. �� ```�` 4673 / /Nf
�yi 'N57A-2B-20 / ' --
.CO r I / r I*,'c -656:n '657--n 57-29E6 ��
co / 46 7 � Illiltfir
�
1306 _ 57A--2 26 1 it i64$
1308 r \\ r �- ..... .,,.„,... /- ..: ,
57A-2B--17 ,'313:;' \ 1 \ 4675 4671/
G.) i ,aye 57A-2B--22 ,... .
\ 7;. / 1 % ' Plat *it
'...> , ..-.. -. o
16 M `
57 e 122 ft 57A-2B-23 57.-29E4
-� C1 1 - / 57-29E5— i GIS.Web
1320 - 2 _' •'j& 4 Geographic Data Services
_f51 p;-2B`15 ' I p, - www albema a org
- iat 57A-2B-24 �t�$1� (434)296-5832
Map is for Display Purposes Only•Aenal Imagery from the Commonwealth of Virginia and Other Sources May 14.2018
-- 1:� \'////'\'/1\\k :
-1\ (Note:Some items on map may not appear in legend(
t„
��40 - �T �6�8 ty _ �� 57-10 �1 f
i / V
57-9D �636 �`� I 1 I-------------"---.....7.,_.____,... s\ ,.,.....
�_ 57-9 '� /�
.;� .,.,
4698 s?\
�4708`
x�.<. �r 57-13
Water Protection /
ro.••finance Buffer 1�7-11 57-12
tr4/ AIIF �'' S7-10 62
N _ _ �� 632K_/
1385 \ \
t i I/57 ..C`-�34 s`�-- f Q
Via/ 57A-2C-*�\ ` .- %0 ��� \
�irn \ , 57A-2C--36\ - \
1 i1 W5 690.E 240 4838
1 \ _r„.� 644 it
AMBER'RIDGE RD / } III `_ 4 4
tr
�y 1400 \
a 0 ' 6?0\ 4683 �rNREE.Nor
CH,
1370 C) "a. �� 6 D.RD
�y /
----lb-57A-2C-39 'fp " ✓ fr \ / r
r,� 4 6i 1390
/r. 8 ��,h.� , 4685. (..." .
91
/ 57-298
/yy m 57A-2B-20 / /
/ 1305 1307 /'la co 656 f 652'� 7 29F r;
46
1306 ç57A=2B 21 l 6A$
— \ /
1308 \ r 4671 /
7 C zk3 �_- '
rig
\ y / 57A,2 i 122
rn
--16 --J��7 ° 57.-29E4 /
122 ft 57A-2B-23 fr i 57-29E5— '._'I.- GIS-Web
•'4``{ Geographic Data Services
132 U 1.5 r wwa albemade org
..5,'�Z � I I I (434)296-5632
c} 57A-2B--24 / 1111/
Map is for Display Purposes Only•Aerial Imagery from the Commonwealth of Virginia and Other Sources May 14.201
S s
SEH
Building a Better World
for All of Us°
April 6, 2018 RE: Rivanna Sewer and Water Authority
CZWTP Expansion and Improvements
SPD201400014
SEH No. RIVAN 144134 14.00
Department of Community Development
County of Albemarle
401 McIntire Road
Charlottesville, VA 22902
Dear
The Rivanna Water and Sewer Authority(RWSA) is proposing to expand and rehab the water treatment
plant located at 4685 Three Notched Road, Crozet, Virginia, and at the lagoons site to the north. For this
project, the RWSA proposes a minor site plan amendment to the site plan SDP#201400014, project title
Crozet WTP Upgrades—Granular Activated Carbon (GAC) Facility, which has had one minor
amendment, SDP#201600065, project title Crozet Water Treatment Plant—Finished Water Pump
Station (FWPS). RWSA also proposes site plan amendment to the site plan SDP#000000298. This
letter provides background to the project and outlines the changes proposed to the site plan SDP
#201400014.
Background
The RWSA owns and operates the Crozet Water Treatment plant, which provides potable drinking water,
at a capacity of 1.0 million gallons per day(MGD),to its customers located in the Crozet service area.
After receiving water from the Beaver Creek raw water pump station, the CZWTP provides treated water
to the distribution system from its nearby Finished Water Pump Station (FWPS) and 0.5 MG ground
storage tanks (GST). Recognizing that water demands in the Crozet service area are continuing to rise,
the RWSA has begun the process for increasing the treatment and pumping capacity of the Crozet water
system by completing design and initiating construction of a new FWPS. Continuing the plan to increase
the treatment and pumping capacity of the Crozet water system,this project will expand and renovate the
Crozet Water Treatment Plant(CZWTP)and the Raw Water Pump Station (RWPS).
Proposed Improvements
GAC Building
As part of expansion of the CZWTP, a building addition to the Granular Activated Carbon (GAC) building
is proposed. This building will house bulk storage tanks for liquid lime and alum, two transfer pumps and
associated piping, electrical, and mechanical equipment. A proposed loading dock will aid in the filling of
the bulk storage tanks. The proposed underground chemical carrier pipe will provided chemical feed to
the Filter Building from the GAC Building.
Engineers I Architects I Planners I Scientists
Short Elliott Hendrickson Inc.,3535 Vadnais Center Drive,St.Paul,MN 55110-5196
SEH is 100%employee-owned I sehinc.com I 651.490.2000 I 800.325.2055 I 888.908.8166 fax
April 6, 2018Errorl Reference source not found.
Page 2
Filter Building
It is proposed to add an above ground propane tank 10 feed east of the filter building. Additional
improvements to the Filter Building include adding a receiving double door for the second floor of the
building, cleaning the outside brick, and minor painting of the window and door trim.
PAC Silo
As part of the project, it is proposed to replace the existing Alum Storage Tank with a 30-foot tall silo to
store Powdered Activated Caron (PAC).
Sanitary Sewer Forcemain
Install two 12 inch casing under the Three Notched Roadway for a sanitary sewer forcemain, electrical,
and potable water. The sewer forcemain is to tie the discharge for the backwash waste to the sanitary
sewer in a property to the south west of the WTP site.
Screening
Screening is to be added within the 30-foot buffer in the southwest corner of the property. This is due to
the sanitary sewer forcemain crossing the 30-foot buffer. Additional screening will also be added along
the north side of the Three Notched Road. This is to screen the new backwash waste tank and the
access bridge to be added to the east lagoon.
Lagoon No.2
Lagoon No. 2 (east lagoon) is to be rehabilitated, and an access bridge added.
Backwash Waste Tank
Lagoon No. 1 is proposed to be removed and an new partially buried concrete backwash waste tank
constructed where Lagoon No. 1 is situated. A new concrete flow diversion structure will split flow
between the backwash Tank and Lagoon No. 2.
Access Driveway
The existing access driveway to the lagoons will have minor gravel improvements. The location of the
access from Three Notched Road will not change. No new access driveways are proposed for Three
Notched Road.
Chain Link Fence
Do to construction the chain-link fence facing Three Notched Road on the lagoon site will be replaced
with poly-coated chain-link fence.
Concluding Remarks
Email correspondences with Christopher Perez of County Planning Department on March 23, 2018 it was
indicated that this project could be brought to the county as a minor site plan amendment to the site plan
SDP#201400014. The email exchange is enclosed with this letter. Included with this letter are the
Application for a Minor Site Plan Amendments, preliminary application meeting notes and the preliminary
plans. Graphical delineation of the proposed changes are shown in the preliminary plan. If you have any
questions or require any additional information, please contact me at 651-490-2020.
April 6, 2018Error! Reference source not found.
Page 3
Sincerely,
SHORT ELLIOTT HENDRICKSON INC.
Miles B. Jensen, P.E.
Regional Practice Center Leader
MNT
Attachment
Minor Site plan Amendment
Meeting Minutes
Email Exchange
Plans
\1sp3020.1\projects\pt\r\rivan\144134\3-env-stdy-regs\3®\2.sdp\submittel\submittal 1\list of proposed changes(letter).docx