HomeMy WebLinkAboutSDP201900013 Review Comments Final Site Plan and Comps. 2019-04-23COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, Room 227
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
Project: Wawa Pantops Corner — Final Site Plan
Plan preparer: Ryan Perkins, Kimley-Horn Associates, 1700 Willow Lawn Drive, Suite 200
Richmond,VA 23230 [ryan.perkins(a-)kimley-hom.com ]
Owner or Rep: Pantops Corner LC, 12704 Crimson Court, Suite 101; Henrico,VA 23233-7657
Applicant: Paul Sprouse, The Rebkee Company, 2800 Patterson Ave, Suite 200
Richmond, VA 23221 [psprouse(a)rebkee.com]
Plan received date: 6 Mar 2019
Date of comments: 23 Apr 2019
Reviewer: John Anderson
Project Coordinator: Andy Reitelbach
SDP2019-00013 (Comments below from ISP, SDP2018-00078)
CA-100
1. Provide 1" =2,000 (or less) scale vicinity map. (FSP) Addressed.
2. Include SDP201800078 in revised initial site plan title. (FSP) Addressed. As follow-up: With
assignment of FSP file identifier, please revise next submittal to ref. SDP2019-00013.
3. Engineering recommends include ZMA201300002 proffer on title sheet. (FSP) Addressed.
4. Ref. WP0201800088 (Pantops Corner VSMP Plan) as well as WP0201400028, Mass Grading
and Erosion & Sediment Control Plan for Pantops Corner, approved 6/11/14, with estimated area to
be disturbed =7.01 Ac. (FSP) Addressed.
5. Note: Site under development does not have an existing stormwater management plan. A Mass
Grading and ESC Plan was approved, 6/11/14. No development layout is shown with the Mass
Grading and ESC Plan. Grandfathering (9VAC25-870-48) would not apply in this instance, for this
reason. VARIOE170 (VSMP Program VPDES) permit was issued for mass grading on 9/9/14.
Grading has been performed, and site should be stabilized. If mass grade operations are complete, and
site stabilized, it is time to terminate VAR10E170, and apply for a new VSMP permit for never -
reviewed proposed development on this parcel. Further, VDEQ SWCGP database lists Construction
Activity Operator (VAR10E170) that does not match Initial Site Plan Owner information. Albemarle
does not accept the position that this development is eligible for grandfathering, but views development
subject to stormwater quality and quantity requirements at 9VAC25-870-65 and 9VAC25-870-66.
(FSP) Review error. Comment withdrawn.
CV- 101 (Existing Conditions)
6. Do not show: (FSP) Item 6 Addressed.
a. Proposed development on TMP 78-58G1, which does not exist.
b. Any proposed development features on TMP 78-5A, unless they exist.
C. Show existing features only. If Applicant arranged with Planning Division to represent
proposed features on CV-101 (Existing conditions), provide whatever elements were
requested as an Exhibit or separate ISP sheet with appropriate title.
7. Do show: (FSP) Item 7 Addressed.
a. Full width of U.S. Rt. 250 where it fronts TMP #78-5A. Show existing travel lanes, turn
lanes, traffic signs, median, etc.
Engineering Review Comments
Page 2 of 5
b. Steep slopes (Ref. County GIS Critical Resource layer). Managed steep slopes exist on
this parcel.
C. Proposed RW for private road Pantops Corner Way. (FSP) Addressed. AAPplicant
response: `The proposed public access easement for the Pantops Corner Way is shown on
Sheet CV-102 and CS-101. There is no proposed right-of-way for this road.'
8. Add Note stating that all known existing easements are shown, or that none exist on TMP# 78-5A.
(FSP) Addressed.
9. Provide Ownership information for parcel under development, and adjacent parcels: provide
TMP#, owner name, DB/PG. (FSP) Addressed.
CS- 101 (Site and Utilitv Plan
10. Transfer proposed development features from CV- 101 to CS- 101, including:
a. For FSP approval (submit /respond to comments until approved):
i. Retaining wall design, since proposed retaining walls support necessary
infrastructure (engineered plans, not generic manufacturer's details). Consider
county retaining wall plan review checklist. (FSP) Not addressed. See proposed
plan view information, Final Site Plan checklist (Attached). Engineering restates
requests for design to consider retaining wall plan review checklist. Specifically:
1. Provide complete retaining wall design specific to site design and site
geotechnical parameters sealed by a geotechnical PE, for all walls that
support infrastructure, roads, parking lots, drive aisles, or in close proximity
to a property line. Final Site Plan checklist for reviewers states: `Retaining
Wall Plans checklist. Any walls supporting roads or necessary infrastructure
require engineered plans (not generic manufacturer's details) and computations.
{Design Manual, section 81 This will also be required where walls are close to
property lines and there is the danger of affecting neighboring property, either
during construction, with later failures, or with pedestrian or vehicle safety.
These concerns can be alleviate with layout spacing also. In any case, retaining
walls will require building permits at construction.'
2. Delete reference labels that appear to transfer design responsibility to
Pantops Corner Development. Engineering requires retaining wall design
checklist items for retaining walls integral to Wawa site development.
3. Provide private easements for retaining walls (Access /maintenance).
4. Label all six sets of retaining walls shown on plan sheet CV-102
(including a 2-tier wall, and a 3-tier wall). Label 1 - 6, or A - F.
5. Only the 5' segmental block retaining wall is exempt from requirement
to provide detailed, PE -sealed plan /profile design
ii. Drainage plans. Consider county drainage plan review checklist, including:
1. Drainage structure typ. details. (FSP) Partially addressed. As ollow-
yp: Please include 2016 VDOT R&B Std. details (Site Details); including:
a. Drop inlets, DI-1, DI-3B/C
b. MH Safety steps, SS-1
C. Pipe bedding, PB-1
d. Inlet shaping, IS-1
e. Manhole, MH-1
Please also include commercial entrance detail:
f. CG-11 (2016 R&B Standards)
2. Pipe and inlet type, length, diameter, material, slope, etc. (FSP)
Addressed.
3. Calculations (LD-204, LD-229)
Engineering Review Comments
Page 3 of 5
a. Velocity /Capacity /Inlet spread and depth. (FSP) Partially
Addressed. As follow-up: Provide LD-204 Inlet computations.
4. Profiles, all elements labeled. (FSP) Addressed. Asfollow-up: In
profile (CG-103), label Str. B7 and A13 as BY OTHERS, since not existing.
Also, Engineering recommends increase pipe slope from minimal acceptable
0.5% to 0.55%, for example. Often, designing to a minimum introduces
issues during construction. This is a recommendation, not a requirement.
5. Label inlets, pipes, and structures (FSP) Partially Addressed. As
follow-up: Please revise plan sheet CG-101 to Grading and Drainage Plan.
iii. Water and sewer line profiles. (FSP) Addressed. (Note: Water Line N/A)
iv. WP0201800088, Pantops Corner, must be approved (prior to Wawa at
Richmond Road and Stony Point Road FSP Approval). (FSP) Comment persists as
noted, elsewhere.
V. Include Exhibit for off -site (TMP #78-58G1) SWM facilities required to meet
stormwater quality and quantity requirements. (FSP) Not addressed; nor to be
immediately addressed. Applicant (KHA) should coordinate with Pantops Corner
LLC (hotel) design engineer (Skimp Engineering) to obtain at least conceptual
stormwater management design information to address water quality and quantity
requirements. At present, Wawa and Pantops Corner, LC (hotel) sites are owned by
a single entity. That site plan application processes are pursued by distinct entities
with Wawa site plan that includes direct /indirect reference to work to be performed
by others (Pantops Corner LC), but there is a single owner (Pantops Corner, LC) at
this time. The VSMP plan, WP02018000881 which amends WP0201400028, must
Le approved and bonded, with Wawa site properly registered with DEQ before
SDP201900013 can be approved. Given current single ownership with sale pending
to separate entity, this site plan should include an Exhibit consistent with
WP0201800088 design at point of VSMP approval that ties SWM compliance
requirements and compliance responsibility to the current owner of TMP #78-5A
(Wawa site). Engineering recommends plan sheet images that capture salient specific
SWM facility design information, titled SWM Exhibit for reference only. Subtitled:
Ref. WP0201800088 for approved VSMP plan.
vi. WP0201800088 must be bonded. (FSP) Comment persists.
vii. Pantops Corner Way must be (built or) bonded to limits required by Planning
Division, as defined by ZNIA201300002 proffer. (FSP) Comment persists.
Applicant response: `Comment noted.'
it. Note: Provide Road Plan under separate Application to County at earliest convenience. Ensure
road plan design for Pantops Corner Way considers Road Plan checklist for plan reviewers, and
includes a temporary turnaround meeting VDOT, Fire Rescue, and ACDSM needs, unless fully
constructed between U.S. Rt. 250 and R. 20 with Wawa. Attached. (FSP) Addressed.
SUB201900024 is under review.
12. Light grayscale indicates Pantops Corner Way is existing. Revise to show Pantops Corner Way is
proposed and is to be constructed with Wawa site plan to limits defined by Planning. Provide
turnaround sufficient to meet multiple agencies temporary turnaround requirements. (FSP) Partially
addressed. Applicant response: `The Pantops Corner Way is shown as proposed on Sheet CV- 101 and
shaded as existing on Sheet CS-101 as it will be existing during the construction of the Wawa parcel.'
As follow-up: Label Pantops Corner Way `to be constructed BY OTHERS' on plan sheet CS-101.
13. Loading width is less than 12', if exclude area occupied by bollards. Revise to provide min.
loading space width of 12'. (FSP) Addressed.
14. Delete note stating `Terraced Retaining Wall ...is to be designed and constructed as part of
Pantops Corner Development plans.' The terraced retaining walls are intrinsic to site development.
Include engineered PE -sealed retaining wall design plans with FSP. (FSP) Not addressed. Also, item
CS-502
CG-101
Engineering Review Comments
Page 4of5
10.a.i., above. Comment persists. Applicant response: `Once available the retaining wall plans will be
inserted into this plan set. It should be noted that the wall will be constructed by the current landowner
as part of the Pantops Corner Way plans and not by Wawa. It is a condition in the purchase contract
for this wall to be installed by the seller (current landowner).' Engineering welcomes this explanation.
Please submit detailed PE -sealed design for 5 of 6 retaining wall locations shown on CV-102, if CV-
102 remains part of Wawa FSP. If CV-102 is removed from this FSP (as Engineering recommends),
then provide detailed PE -sealed design for all retaining walls on TMP #78-5A prior to FSP approval.
15. Provide VDOT GR4 2 (guardrail) for parking spaces fronting retaining wall; ensure sufficient
parking space depth, once guardrail is installed. (FSP) Addressed.
16. Proposed SS line appears discontinuous. Revise to show connection with Ex. SS, or extend
proposed SS to a logical endpoint. (FSP) Addressed.
17. If proposed retaining wall fronting Pantops Corner Way coincides with managed steep slopes,
ensure design meets (retaining wall) design standards at 18-30.7.5. (FSP) Comment persists.
Applicant response: `The wall plans will be submitted once available.'
18. Likewise, storm drain pipe from DI at third southernmost parking space facing Pantops Corner
Way is discontinuous. Clarify connection with downgradient elements of storm system. (FSP)
Addressed.
19. xeview proposed bike rack to ensure adequate clearance between typ. bike and proposed sidewalk
(1'-2' clearance, recommended). (FSP) Addressed.
20. Show proposed easements, including:
a. Drainage (FSP) Partially addressed. As follow-up: Show drainage easements on CG-
101, since CG-101 is a Drainage and Grading plan. CS-100, titled boundary plan, shows
drainage easements, and resembles a plat. Easements need to be shown with pipe /inlet
structures (and SWM facility) if they are to be evaluated.
i. Ref. ACDSM, pg. 15
b. Sidewalk (FSP) Withdrawn. Sidewalks appear to be within public access easement.
C. ACSA (FSP) Partially Addressed. CS-100 resembles a plat. Show ACSA easements
on CS-101. Same rationale as above: Engineering cannot evaluate easements against invisible
structures.
d. Sight (FSP) Addressed.
e. RW (FSP) Addressed. Public Access Easement shown on CS-101.
21. Provide entrance sight lines, north -south, for vehicles exiting Wawa. (FSP) Addressed.
22. Label commercial entrance using VDOT nomenclature (CG-9a, etc.). (FSP) Addressed.
23. Label corner clearance distance from site entrance to U.S. Rt. 250. Engineering defers to VDOT.
(FSP) Addressed. Note: Engineering defers to VDOT on corner clearance distance.
24. Label any spilling curb and gutter. (FSP) Addressed.
25. Label entrance curb radius. (FSP) Addressed.
26. Show trench drains. (FSP) Partially addressed. As follow-up: South and East ends of trench are
labeled with elevations, which is helpful. Please provide additional trench, oil -water separator
elevations. Provide profile from the point where the two trenches join and a single pipe departs fuel
canopy, to Str. 7.
27. Provide concrete specification; provide 3000 psi strength at 28 days. (FSP) Addressed.
28. Provide dumpster pad detail. (FSP) Addressed.
29. Provide CG-6 detail. (FSP) Partially addressed. As follow-up: 6" depth of `spilling' gutter must
match VDOT (CG-6) 7" gutter depth. Revise CS-501 Spilling Curb and Gutter detail depth to 7".
30. Recommend spot elevations at entrance. (FSP) Partially addressed. Engineering recommends
spot elevations at entrance EP.
31. Ensure spills from filling UG fuel tanks reach trench drain. Check west -most UG tank, in
particular. (FSP) Withdrawn.
CP-101
Engineering Review Comments
Page 5 of 5
32. Show steep slopes, this sheet. (FSP) Addressed. Shwon on CG-101.
33. Stormwater Management Narrative (Also, items 5, 10.a.iv, above): (FSP) Not addressed.
a.
ti4en4 baPA. will satisfy st .. .,..ate f ma-a,,,.om ent r-e uir-e en4s. Delete specific reference to
2.45 lb. credit from site plan; instead, reference WP0201800088. Transfer specific, detailed
SWM Narrative and design information to WP0201800088.
b. Please note that WP0201800088 references 8.3 lb. purchase. WPQ plan in fefmatior has
not been reviewed i detail; presentation and integration of TMP #78-5A and 78-58G1 SWM
requirements into a single WPO requires care. (FSP) Comment persists. VSMP plan under
review.
34. Provide note for vegetative ground cover hardier than grass for areas between discrete individual
plantings north of retaining wall on north side of site (2:1 slope). Mulch may suffice. (FSP)
Addressed.
35. Remove proposed street trees within drainage easement/s. Recommend show drainage easement/s
on Landscape plan. (FSP) Addressed.
36. Street trees appear to obstruct sight distance. Provide sight lines. Also, item #21 above. (FSP)
Addressed.
New
37. CV-102: It is unorthodox to include site information for separate parcel with separate site plan
application under review with Albemarle County (SDP201800089). This separate site plan may be
referenced, but detailed information shown with separate final site plan should not be included with
SDP201900013 Final Site Plan (Wawa), as Wawa FSP approval would then in effect approve
SDP201800089 site plan elements. Engineering defers to Planning.
38. Note /Reminder: All roadway (Pantops Corner Way /U.S. Rt. 250 /SR 20) elements shown with
FSP201900013 must be consistent with Road Plan design at point Road Plan is approved
(SUB201900024). In other words, Road Plan approval is required prior to FSP approval.
39. CS-101 /Site Legend: There is no concrete sidewalk detail on CS-501. Please provide concrete
sidewalk detail or revise title of Mountable curb/island and stamped concrete detail (CS-502), if this
detail may serve two purposes (stamped /plain).
CS-101
40. Label sidewalk along U.S. Rt. 250 `by others.'
41. Label sidewalk along Pantops Corner Way `by others.'
42. Provide bumper blocks for all 18' L parking spaces adjacent to GR-2.
43. Provide /show detectable surface at ramp on west side of stamped asphalt crosswalk.
Please call if any questions: 434.296-5832 —x3069
Thank you
SDP201900013 Wawa Pantops _FSP 042319