HomeMy WebLinkAboutARB201900015 Revised Application Submittal 2019-06-03LITTLE
DIVERSIFIED ARCHITECTURAL CONSULTING
Transmittal
From: Date:05/30/2019
4245 North Fairfax Drive, Suite 650
Arlington, VA 22203
To:
Albemarle County Department of
Community Development
401 McIntire Road
Charlottesville, VA 22902
We are sending you:
❑ Shop Drawings
® Copy of Letter
❑ Attached
® Prints
❑ Change Order
Project No:
223.12094.00
Attention: Heather McMahon,
Senior Planner
RE:
❑ Under Separate Cover
via _ the following items
❑ Samples
❑ Specifications
® Other
Copies
Date
Number
Description
Action
Re 'd
1
05/30/19
Revised Application Submittal
6
05/30/19
Signed/Sealed Drawings sets
1
04/03/19
Letter — Description of landscaping history
1 each
05/30/19
Response Letters to both ARB and LOR comments
1
05/30/19
Revised Letter of Revision (LOR) #3
2
05/30/19
COMcheck
These are transmitted as checked below:
® For Approval ❑ Reviewed ❑ Revise & Resubmit
❑ For Your Use ❑ Rejected ❑ Submit Copies for Distribution
❑ As Requested ❑ Furnished as Corrected and Return Corrected Prints
❑ For Review & Comment ❑ Not Marked ❑ Prints Returned after Loan to Us
❑ For Bids Due
Copy to: RECEIVED
Signed:
JUN 0 3 2019 Printed Name: Ryan McGrath
Email: rmcgrath@littleonline.com
If enclosures are not as UEe ' aWkT
Little Diversified Architectural Consulting 4245 North Fairfax Drive, Suite 650, Arlington, VA 22203 703.908.4501
LETTER OF TRANSMITTAL 1
COUNTY OF ALBEMARLE
Department of Community Development
REVISED APPLICATION SUBMITTAL
This form must be returned with your revisions to ensure proper tracking and distribution. County staff
has indicated below what they think will be required as a resubmission of revisions. If you need to submit
additional information please explain on this form for the benefit of the intake staff. All plans must be
collated and folded to fit into legal size files, in order to be accepted for submittal.
TO: Heather McMahon DATE:
PROJECT NAME: _ARB-2019-15: Bank of America, Rio Road E, Minor Amendment/SDP-1996-35
Bank of America, Letter of Revision #3
Submittal Type Requiring Revisions () indicates submittal Code
County Project Number
# Copies
Erosion & Sediment Control Plan E&S
Mitigation Plan MP
Waiver Request WR
Stormwater Management Plan SWMP
Road Plan RP
Private Road Request, with private/public comparison PRR
Private Road Request — Development Area PRR-DA
Preliminary Site Plan PSP
Final Site Plan or amendment FSP
Final Plat FP
Preliminary Plat PP
Easement Plat EP
Boundary Adjustment Plat BAP
Rezoning Plan REZ
Special Use Permit Concept Plan SP-CP
Reduced Concept Plan R-CP
Proffers P
Bond Estimate Request BER
Draft Groundwater Management Plan D-GWMP
Final Groundwater Management Plan F-GWMP
Aquifer Testing Work Plan ATWP
Groundwater Assessment Report GWAR
Architectural Review Board ARB
ARB-2019-15
2
Other: Please explain
SDP-1996-35 LOR#3
4
(For staff use only)
Submittal Code
# Copies
Distribute To:
Submittal Code
# Copies
Distribute To:
ARB
6
Heather McMahon
4/3/2019
Jeremy Ellis
BrightView Enterprise Solutions
Bank of America 1523 East Rio Rd
To whom it may Concern:
This letter is in reference to the county's requirement of Bank of America at 1523 East Rio rd in
Charlottesville, VA to have a hedge along Rio rd. The Oak trees along Rio Rd have grown quite
large since the original hedge of Dwarf Bufordii Holly were installed which have shaded out the
plants, along with the oak trees aggressive root system robbing nutrients and water from the
hollies. This has led to the original plantings to all die as well as the replacement plants that
were installed back in the 2015/2016 time range. At this point from a professional view we feel
like there will be no plant material that would be able to survive and thrive up against the
current condition of the area. Getting new plant material to establish with the dense shade, the
root system of the oaks, and the slope of the ground causing majority of water to run off would
be near if not completely impossible. Please feel free to contact me with any questions or
concerns.
Sincerely
Jeremy Ellis
Market Account Manager
BrightView Enterprise Solutions
(804)304-7266
LITTLE''
DIVERSIFIED ARCHITECTURAL CONSULTING
May 30, 2019
Heather McMahon
Senior Planner
County of Albemarle
401 McIntire Road, North Wing
Charlottesville, VA 22902-4596
Re: RE: SDP1996-35 Bank of America on Rio Road E. — Letter of Revision #3
Thank you for reviewing the attached plans. Below are our responses to the comments dated
February 22, 2019.
Comment 1. Submit site and architectural drawings with your LOR application. Everything that
has been submitted for the ARB application must be duplicated and submitted for the LOR
application.
Response: Noted. Plans package now contains Architectural, Civil and Electrical plans,
all represented on the Architectural cover sheet. LOR and ARB plans are the same and
have incorporated all comments.
Comment 2. Observe traditional conventions and revise the site plan drawings to orient the
North arrow at the top of the page.
Response: True North is represented on all Civil Plan sheets in a slightly west of north
orientation.
Comment 3. Revise the site plan drawings to include public roads Rio Road East and Putt Putt
Place.
Response: All Civil Sheets C1.00. C1.10 and C1.20 show Rio Road East and Putt Putt
Place.
Comment 4. Revise the site plan A03.01 which shows existing conditions to reflect the
landscaping and site features that currently exist on the ground. This will require a site visit or
survey.
Response: New sheet C1.10 shows the Original 1996 Site Plan with current missing trees
marked out. New Sheet C1.20 show what is to be replaced to bring the site into
compliance with the approved 1996 Site Plan.
Comment 5. Note that not all of the landscaping which was approved with the site plan in 1996
exists on the site today, which means the site plan is not in compliance (for instance, shrubbery
on the eastern property line, near the southeastern corner of the site, is not visible in current -
day (last capture July 2018) Google Street Views). This landscaping must be provided.
Response: All landscaping and shrubbery has been documented across the Civil Plans.
Trees and shrubs no longer present on site have been called out on Sheet C1.10 and
proposed trees and ground cover are shown on Sheet C1.20.
Comment 6. Note that there is no documentation of a previous Letter of Revision that approved
the current location of the dumpster. The dumpster is not in compliance with the approved final
site plan of 1996. Therefore, the dumpster location must be addressed in this Letter of Revision
4245 N. Fairfax Drive, Suite 650, Arlington, VA 22203 t 703.908.4501 703.908.4502 w littleonline.com
LITTLE'
DIVERSIFIED ARCHITECTURAL CONSULTING
application unless documentation can be provided showing staff that the dumpster location has
been previously reviewed and approved.
Response: The County does have proof of the dumpster location (which was approved
via an ARB submission ARB-2013-5. As stated in an email dated February 26, 2019, this
ARB approval was supposed to be coordinated and approved with a new LOR, which
was never submitted (or approved). This revised LOR Submission includes the
dumpster and its appropriate location onsite — including details/ sections and a
photograph of the dumpster with respect to the passing view approaching the site along
the Entrance Corridor. Our LOR letter now includes the dumpster as well.
Comment 7. Revise the architectural drawings on sheet A09.11 to include all light fixtures visible
from the Entrance Corridor (Rio Road East).
Response: All requested information is included in this submission. This lighting
information can be found in Plan view on Sheets A03.01 and Sheet C1.20.
Comment 8. Respond to and address ARB comments that are provided in the attached letter.
Response: All ARB comments are addressed and a Comment Response Letter for the
ARB is submitted along with this Letter.
Included in this submission package are the following items:
• Comment Response Letters
• Six (6) total copies of the electrical plans
• Two (2) signed and sealed COMcheck calculations.
If you have any questions or concerns, please do not hesitate to contact me at (571) 257-2865.
Sincerely,
Kevin Thorstad
Little Diversified Architectural Consulting
4245 N. Fairfax Drive, Suite 650, Arlington, VA 22203 t 703.908.4501 f 703.908.4502 w littleonline.com
LITTLE
DIVERSIFIED ARCHITECTURAL CONSULTING
May 30, 2019
Heather McMahon
Senior Planner
County of Albemarle
401 McIntire Road, North Wing
Charlottesville, VA 22902-4596
Re: Plan Number: ARB-20179-15: Bank of America, Rio Road E., lighting and landscaping
renovations.
Thank you for reviewing the attached plans. Below are our responses to the comments dated
February 26, 2019.
Comment 1. Ensure that the property lines drawn on the site plans are correct and that the site
plans reflect all of the site conditions currently existing on the parcel.
Response: Per comments for the LOR and Comment 1, all property lines and other site
features have been represented to the best of our abilities as they currently exist on the
parcel.
Comment 2. Merge "site" and landscape plans on A03.01. Eliminate sheet E1.01. Ideally, your
application package should consist of three site plan drawings (in addition to the building
elevations you provided): Response: Site and landscape plan have been merged onto one
plan on sheet A03.01. Sheet E1.01 has been removed from the project set of drawings.
a. A Current Conditions and Demolition Plan that shows all current site features and all
lighting and landscaping to be removed. This should include a schedule that explains
exactly what fixtures will be removed and not replaced and what fixtures will be replaced.
b. A Landscape Plan that shows proposed landscaping as well as current landscaping.
This plan should also include all of the existing and proposed freestanding light poles on
the site.
c. A Lighting Plan that shows existing and proposed light fixtures, if the plan becomes
too complicated to read, you may omit those light fixtures that are either outside of the
scope of work and/or that will be removed and not replaced (those should be shown on
the Current Conditions and Demolition Plan).
Responses to a., b., and c.: Sheets C1.00, C1.10 and C1.20 represent the Original Site
Plan (1996), the Existing Conditions Plan, and the Proposed Landscaping and Lighting
Plans, respectively. Architectural Sheet A03.10 shows the sight lighting with respect to
existing tree and shrub trimming. Additionally, the Electrical Plans provide a detailed
photometric plan with all electrical notes and details outlining new site lighting and
power.
Comment 3. Ensure that all of the current and proposed wall -mounted lights are drawn on the
elevations visible from the Entrance Corridor street (i.e., the south, west, and east elevations.
The north elevation is not visible from Rio Road and therefore does not require ARB review).
Response: A North, West, and East elevation has been provided on sheet A9.11 showing
all existing light fixtures as well as all new light fixtures.
4245 N. Fairfax Drive, Suite 650, Arlington, VA 22203 t 703.908.4501 f 703.908.4502 w littleonline.com
L ITT LEI
DIVERSIFIED ARCHITECTURAL CONSULTING
Comment 4. Note that the color of the poles of the two proposed new freestanding lights has not
been stated in the luminaire schedule or in manufacturer's specifications and that the new poles
must match the color of the existing light poles on the site. This will be made a condition of the
Certificate of Appropriateness. If bronze is the color of the existing freestanding light poles, then
the color bronze must be selected for the two new proposed poles in order to maintain
Consistency.
Response: See fixture clarification note on sheet E0.01. (D.Edelman 5/30/2019)
Comment 5. Remove light models R1, R2, and R3 from the luminaire schedule if they are to be
removed and not replaced. Remove light model Y1 from the luminaire schedule if it is outside
the scope of work.
Response: Light fixtures R1, R2, R3, and Y1 have been removed from the luminaire
schedule. (D.Edelman 5/30/2019)
Comment 6. Provide a landscape schedule on a revised landscape plan that details the plant
symbol used; quantity, species; common name; caliper/size at planting; and canopy of any
proposed (new) landscaping. Note that all proposed species should be selected from the
Albemarle County Recommended Plants List; canopy calculations can be attained using this
Plant Canopy Calculations reference sheet.
Response: See Sheet C1.20 for this proposed landscape information.
Comment 7. Provide the standard plant health note on the landscape plan: All site plantings of
trees and shrubs shall be allowed to reach, and be maintained at, mature height; the topping of
trees is prohibited. Shrubs and trees shall be pruned minimally and only to support the overall
health of the plant.
Response: See note #17 on Sheet C1.20.
Comment 8. There is spillover along the Rio Road frontage in excess of halt (0.5) footcandle
(fc). As per the Zoning Ordinance Chapter 18, Section 4.17.4.b.1, spillover at the property line
cannot exceed .5 fc into the public right-of-way. Please revise the proposal and plan ccordingly.
Response: Fixtures have been revised to accommodate Zoning Ordinance and will not
exceed .5 fc into the public right-of-way. (D.Edelman 5/30/2019)
Comment 9. Provide a luminaire schedule on a revised lighting plan (i.e., ensure that the
schedule is on the same page as the photometric plan).
Response: Luminaire schedule has been added to photometric plan. (D.Edelman
5/30/2019)
Comment 10. Provide the Maintenance Factor (LLF) as a category to the luminaire schedule.
Note that the LLF must equal 1.0 and that the photometric calculations must reflect an LLF
equal to 10,
Response: LFF has been set to 1.0 for lighting calculations. (D.Edelman 5/30/2019)
4245 N. Fairfax Drive, Suite 650, Arlington, VA 22203 t 703.908.4501 f 703.908.4502 w littleonline.com
LITTLE
DIVERSIFIED ARCHITECTURAL CONSULTING
Comment 11. Note that light levels in excess of 20 footcandles is generally not accepted in the
Entrance Corridor. Reduce the footcandle values in excess of 20 fc.
Response: Foot-candles do not exceed 20fc around Entrance Corridors. (D.Edelman
5/30/2019)
Comment 12. Note that the height and scale of freestanding pole -mounted light fixtures in the
Entrance Corridor should not exceed 20 feet including the base. The two new proposed poles
are listed as 25 feet AFG. Reduce this to 20 feet inclusive of the base.
Response: Pole fixtures have been reduced to 20 feet AFG. (D.Edelman 5/30/2019)
Comment 13. Add the standard lighting note to the plan: Each outdoor luminaire equipped with
a lamp that emits 3, 000 or more
initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light
away from adjoining residential districts and away from adjacent roads. The spillover of lighting
from luminaires onto public roads and property in residential or rural areas zoning districts shall
not exceed one-half footcandle.
Response: Standard lighting not added to plan and fixture schedule. (D.Edelman
5/30/2019)
Included in this submission package are the following items:
• Comment Response Letter
• Six (6) total copies of the electrical plans
• Two (2) signed and sealed COMcheck calculations.
If you have any questions or concerns, please do not hesitate to contact me at (703) 908-4535.
Sincerely,
Ryan McGrath
Little Diversified Architectural Consulting
4245 N. Fairfax Drive, Suite 650, Arlington, VA 22203 703.908.4501 f 703.908.4502 w littleonline.com
1K
May 30, 2019
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902-4596
RE: Letter of Revision Application #3 (Second Submission)
Site Plan: Nationsbank at Rio Road SDP-1996-35
Tax Map/Parcel Number: 06100-00-00-124E2
LITTLE'
DIVERSIFIED ARCHITECTURAL CONSULTING
This letter is to approve as a Letter of Revision the improvements of site lighting and the replacement of
trees and shrubs to the above referenced site plan (a more detailed narrative of site changes is outlined
below). As noted above, this is the Third and Final Letter of Revision for this site. As per the
requirements of Albemarle County, a total of three (3) Letters of revision are allowed before all changes
to the plan are required to be submitted in the form of a site plan amendment.
As part of a voluntary program, our client, Bank of America, has performed an assessment of the site in
question and determined some improvement work is necessary to bring the site lighting up to current
bank standards. Incidental to this effort, some changes to the existing Site Plan for Nationsbank at Rio
Road (1505 Putt Putt Place, Charlottesville, VA SDP-1996-35) are necessary.
The proposed changes to Site Plan SDP-1996-35 entail the addition of two (2) new light poles as denoted
by Keynote #1 on the revised site plans. With the proposed work, it was recommended to us to bring
the current Site up to the standards of the original Approved 1996 Site Plan. All of our proposed work is
shown on the LOR and ARB Plans and the requested changes after first submittal are outlined in the
Comment Response Letters; this includes new site lighting and the replanting of trees and shrubs which
have since been removed from the site on unspecified dates. Additionally, we have provided the
relevant requested information to the LOR of the Existing Dumpster Enclosure. The Architectural and
Lighting/Photometric plans which accompany this LOR and Site Plans are included in this merged
LOR/ARB submission.
We hereby request your approval of the above -mentioned improvements, and the change to the
approved Site Plan SDP-1996-35. Should you have any comments or concerns, please do not hesitate to
contact me.
Sincerely,
Kevin Thorstad, P.E
LITTLE
Civil Engineer, Land Development Services
42245 North Fairfax Dr. Suite 650 1 Arlington, VA 22203 1 p: 571.257.2865 f: 703.908.4502 1 www.littleonline.com
COMcheck Software Version 4.0.8.2
Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Rio Road ELP Renovation
Project Type: Alteration
Exterior Lighting Zone 1 (Developed rural area)
Construction Site: Owner/Agent:
Designer/Contractor:
1505 Putt Putt Place
Daniel Edelman
Charlottesville, VA 22901
Little
4245 N Fairfax Dr
Suite 650
Arlington, VA 22203
571.257.4063
daniel.edelman@littleonline.com
Allowed Exterior Lighting Power
A B
C D
E
Area/Surface Category Quantity
Allowed Tradable
Allowed Watts
Watts / Unit Wattage
(B X C)
Parking area 47755 ft2
0.04 Yes
1910
Total Tradable Watts (a) =
1910
Total Allowed Watts =
1910
Total Allowed Supplemental Watts (b) =
500
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 500 watts may be applied toward compliance of both non -tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A
B C
D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
Lamps/ # of
Fixture (C X D)
Fixture Fixtures
Watt.
Parking area (47755 ft2)Tradable Wattage
LED 1: B01: CANOPY FIXTURE: Other:
1 5
20 100
LED 2: B01: CANOPY FIXTURE: Other:
1 2
20 40
LED 3: DW1: CANOPY FIXTURE: Other:
1 3
22 66
LED 4: GW1: POLE MOUNT: Other:
1 4
86 344
LED 5: HE1: POLE MOUNT: Other:
1 5
101 505
LED 6: HE2: POLE MOUNT: Other:
1 1
101 101
LED 7: HK1: POLE MOUNT: Other:
1 2
130 260
LED 8: HLi: POLE MOUNT: Other:
1 1
166 166
LED 9: SE1: WALL MOUNT: Other:
1 5
25 125
LED 10: SH1: WALL MOUNT: Other:
1 1
25 25
Total Tradable Proposed Watts = 1732
Project Title: Rio Road ELP Renovation
Report
date: 05/30/19
Data filename: WARetail\Service Retail\ BAC\—ELP\2231209400 Rio Road ELP\2 Design\9 Engineering\Electrice
Page 1 of 6
Design\COMcheck_Rio Road_2019.5.30.cck
❑r Lirthfinn P4
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting alteration project represented in t is document is consistent with the
building plans, specifications, and other calculations submitted with this permit a oposed exterior lighting
systems have been designed to meet the 2015 IECC requirements in COMch Ti to comply with any
applicable mandatory requirements listed in the Inspection Checklist. tj t
STEPHEN ROBEY, P.E.
Name - Title
Signature
'MEIN EDWARD ROBEY
Lic. No. 049826
Project Title: Rio Road ELP Renovation Report date: 05/30/19
Data filename: W:\Retail\Service Retail\ BAC\—ELP\2231209400 Rio Road ELP\2 Design\9 Engineering\Electricz Page 2 of 6
Design\COMcheck_Rio Road_2019.5.30.cck
COMcheck Software Version 4.0.8.2
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans, specifications, and/or ❑Complies Requirement will be met.
[PR8]1 calculations provide all information ❑Does Not
with which compliance can be ❑Not Observable Location on plans/spec: E0.01
determined for the exterior lighting
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Additional Comments/Assumptions:
F1 j High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Rio Road ELP Renovation Report date: 05/30/19
Data filename: W:\Retail\Service Retail\ BAC\--ELP\2231209400 Rio Road ELP\2 Design\9 Engineering\Electric Page 3 of 6
Design\COMcheck_Rio Road_2019.5.30.cck
on
# I Rough -In Electrical Inspection I Complies?
& Rea.ID
Comments/Assumptions
C405.2.5 Automatic lighting controls for exterior ❑Complies Requirement will be met.
[EL25]ni° lighting installed. Controls will be ❑Does Not
daylight controlled, set based on Location on plans/spec: E0.01
business operation time -of -day, or ❑Not Observable
reduce connected lighting > 30% ❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Rio Road ELP Renovation Report date: 05/30/19
Data filename: W:\Retail\Service Retail\ BAC\—ELP\2231209400 Rio Road ELP\2 Design\9 Engineering\ElectricE Page 4 of 6
Design\COMcheck_Rio Road_2019.5.30.cck
* I Final Inspection I Complies? I Comments/Assumptions
& Rea ID
C405.5.1 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[F119]1 with what is shown on the approved ❑Does Not
lighting plans, demonstrating
proposed watts are less than or equal ❑Not Observable
to allowed watts. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 M e lium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Rio Road ELP Renovation Report date: 05/30/19
Data filename: W:\Retail\Service Retail\ BAC\-ELP\2231209400 Rio Road ELP\2 Design\9 Engineering\Electric Page 5 of 6
Design\COMcheck_Rio Road_2019.5.30.cck
Project Title: Rio Road ELP Renovation Report date: 05/30/19
Data filename: W:\Retail\Service Retail\ BAC\--ELP\2231209400 Rio Road ELP\2 Design\9 Engineering\Electrice Page 6 of 6
Design\COMcheck_Rio Road_2019.5.30.cck