HomeMy WebLinkAboutARB201900085 Plan - Submittal (First) 2019-07-09 (2)CONSTRUCTION NOTES: 1. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO COVER A COMPLETE PROJECT, READY TO USE, AND ALL ITEMS NECESSARY FOR A COMPLETE AND WORKABLE JOB SHALL BE FURNISHED AND INSTALLED. ANY DISCREPANCY SHALL BE IMMEDIATELY REPORTED TO THE OWNER OR HIS REPRESENTATIVE. 2. NOTIFY THE INSPECTOR OF THE LOCAL GOVERNING AUTHORITY 24 HOURS BEFORE EVERY PHASE OF CONSTRUCTION. 3. ALL WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL CODES. ALL NECESSARY LICENSES AND PERMITS SHALL BE OBTAINED BY THE CONTRACTOR, AT HIS EXPENSE, UNLESS ALREADY OBTAINED BY THE OWNER. 4. THE CONTRACTOR SHALL COORDINATE LOCATION AND INSTALLATION OF ALL UNDERGROUND UTILITIES AND APPURTENANCES TO MINIMIZE DISTURBING CURBING, PAVING, AND ALL OTHER UTILITIES. 5. THE EXISTING UTILITIES SHOWN ARE FOR THE CONTRACTOR'S CONVENIENCE ONLY. THERE MAY BE OTHER UTILITIES NOT SHOWN ON THESE DRAWINGS. THE UTILITIES SHOWN ARE THOSE LOCATED BY THE SURVEYOR OF RECORD. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE LOCATION OF THE UTILITIES SHOWN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE LOCATIONS OF ALL UTILITIES WITHIN THE LIMITS OF WORK. ALL DAMAGE MADE TO EXISTING UTILITIES BY THE CONTRACTOR SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 6. DEVIATIONS FROM THESE PLANS AND SPECIFICATIONS WITHOUT PRIOR CONSENT OF THE ENGINEER AND THE MUNICIPALITY MAY CAUSE FOR THE WORK TO BE UNACCEPTABLE. 7. ALL MATERIALS SHALL BE NEW UNLESS USED OR SALVAGED MATERIALS ARE AUTHORIZED BY THE OWNER. 8. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ALL NECESSARY BARRICADES AROUND THE WORK AND SHALL PROVIDE PROTECTION AGAINST WATER DAMAGE AND SOIL EROSION. 9. ALL WORK SHALL BE PERFORMED IN A FINISHED AND WORKMANLIKE MANNER TO THE ENTIRE SATISFACTION OF THE OWNER, AND IN ACCORDANCE WITH THE BEST RECOGNIZED TRADE PRACTICES. 10. THE CONTRACTOR SHALL PROVIDE SHEETING AND SHORING FOR ALL TRENCH CONSTRUCTION IN ACCORDANCE WITH OSHA GUIDELINES. 11, ALL PIPE LENGTHS SHOWN ARE TO THE CENTERLINE OF THE STRUCTURES UNLESS SPECIFICALLY NOTED. 12. PIPES (STORM AND SANITARY SEWER) SHALL BE LAID ON SMOOTH, CONTINUOUS GRADES WITH NO VISIBLE BENDS AT THE JOINTS. 13. BEDDING REQUIREMENTS SPECIFIED HEREIN ARE TO BE CONSIDERED AS MINIMUM REQUIRED FOR RELATIVELY DRY STABLE EARTH CONDITIONS. ADDITIONAL BEDDING SHALL BE REQUIRED FOR ROCK TRENCHES TO PROVIDE SUCH ADDITIONAL BEDDING AS REQUIRED TO PROPERLY CONSTRUCT WORK. 14. ALL STORM DRAINAGE INLET STRUCTURES SHALL HAVE METAL RING AND COVER FOR ACCESS. 15. ALL ANGLES SHOWN ARE 90 DEGREES UNLESS SHOWN OTHERWISE. 16. ALL GRADES SHOWN ARE FINISHED GRADES. CONTRACTOR SHALL VERIFY DIMENSIONS, GRADES, AND EXISTING ELEVATIONS PRIOR TO CONSTRUCTION. 17. CONCRETE CURBS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE DETAILS SHOWN ON PLANS. MATERIALS, EQUIPMENT, METHODS OF CONSTRUCTION AND WORKMANSHIP SHALL CONFORM TO STATE D.O.T. STANDARD SPECIFICATIONS. 18. ALL CONCRETE SHALL HAVE 3000 PSI COMPRESSIVE STRENGTH AFTER 28 DAYS, WITH A MAXIMUM SLUMP OF FOUR (4) INCHES, UNLESS SPECIFIED OTHERWISE. 19. ALL EXPOSED CONCRETE SHALL HAVE A FINE HAIR BROOMED FINISH. 20. PARKING AND DRIVEWAY BASE COURSE AND ASPHALTIC CONCRETE SURFACE AND PRIME MATERIALS, EQUIPMENT, METHODS FOR CONSTRUCTION AND WORKMANSHIP SHALL CONFORM TO STATE D.O.T. STANDARD SPECIFICATIONS. 21. CONTRACTOR TO FIELD VERIFY ALL STORM, SANITARY, WATER AND OTHER UTILITIES LOCATIONS AND INVERTS PRIOR TO INSTALLATION OF ANY UTILITIES. NOTIFY ENGINEER PRIOR TO PROCEEDING WITH ANY WORK IF DISCREPANCIES FOUND. 22, THE USE OF CONCRETE THRUST BLOCKS FOR THE INSTALLATION OF WATER MAINS IS STRICTLY PROHIBITED. PRESSURE PIPE FITTINGS AND OTHER ITEMS REQUIRING RESTRAINT SHALL BE RESTRAINED USING METHODS SPECIFIED IN SECTION 3.8 OF THE CITY'S TECHNICAL STANDARD SPECIFICATIONS. THE PREFERRED METHOD OF RESTRAINT IS THROUGH THE USE OF "MEGA -LUGS" OR "MJR" DEVICES. 23. ALL DIMENSIONS ARE MEASURED TO THE BACK OF CURB UNLESS OTHERWISE NOTED. EARTHWORK SPECIFICATIONS: CLEARING AND GRUBBING • CLEARING AND GRUBBING SHALL CONSIST OF CLEARING THE SURFACE OF THE GROUND OF THE DESIGNATED AREAS OF ALL TREES, LOGS, SNAGS, BRUSH, UNDERGROWTH, HEAVY GROWTH OF GRASS, WEEDS, FENCE STRUCTURES, DEBRIS AND RUBBISH OF ANY NATURE, NATURAL OBSTRUCTIONS SUCH AS OBJECTIONABLE SOIL MATERIAL UNSATISFACTORY FOR FOUNDATIONS. IT SHALL ALSO CONSIST OF GRUBBING OF STUMPS, ROOTS FOUNDATIONS AND DISPOSAL OF ALL SUCH MATERIAL. ALL HOLES REMAINING AFTER THE GRUBBING OPERATION IN EMBANKMENT AREAS AND IN EXCAVATION AREAS LESS THAN TWO (2) FEET IN DEPTH, SHALL HAVE SIDES BROKEN DOWN AND LEVELED IF NECESSARY TO FLATTEN OUT SLOPES, REFILLED WITH ACCEPTABLE MATERIAL THAT IS PROPERLY COMPACTED IN LAYERS BY TAMPERS, ROLLERS OR CONSTRUCTION EQUIPMENT. • BURNING ON SITE IS NOT PERMITTED WITHOUT WRITTEN APPROVAL OF THE LOCAL GOVERNING AUTHORITIES HAVING JURISDICTION. EXISTING TREES OUTSIDE OF GRADING LIMITS LINE: • TREES AND VEGETATION TO BE SAVED SHALL BE PROTECTED FROM DAMAGE BY A FENCE BARRICADE PRIOR TO, OR DURING, CLEARING OPERATIONS. TREES TO BE REMOVED FROM THE AREA OUTSIDE THE LIMITS OF GRADING OR FROM SPECIFICALLY DESIGNATED AREAS WITHIN THE CONSTRUCTION AREAS. IF, IN THE OPINION OF THE ENGINEER, A CONTRACTOR DAMAGES A TREE NOT TO BE REMOVED, THE CONTRACTOR WILL BE FINED A PREDETERMINED AMOUNT FOR EACH DAMAGED TREE. THE CONTRACT SHALL ALSO BE RESPONSIBLE FOR ALL COSTS ASSOCIATED IN REMOVING THE DAMAGED TREE FROM THE SITE. FILL: • ALL VEGETATION SUCH AS ROOTS, BRUSH, HEAVY GROWTH OF GRASS, TOPSOIL, ALL DECAYED VEGETABLE MATTER, RUBBISH, AND OTHER UNSUITABLE MATERIAL WITHIN THE AREA UPON WHICH FILL IS TO BE PLACED SHALL BE STRIPPED OR BE OTHERWISE REMOVED BEFORE THE FILL OPERATION IS STARTED. IN NO CASE SHALL UNSUITABLE MATERIAL REMAIN IN OR UNDER THE FILL AREA. SLOPED GROUND SURFACE STEEPER THAN ON VERTICAL TO FOUR HORIZONTAL, ON WHICH FILL IS TO BE PLACED, SHALL BE PLACED, STEPPED OR BENCHED IN SUCH A MANNER THAT THE FILL TO BE PLACED SHALL BE 97 PERCENT OF THE MAXIMUM LABORATORY DRY DENSITY ACCORDING TO STANDARD PROCTOR (AASHTO T99, ASTM D-698). MOISTURE CONTENT SHALL BE WITHIN 3 PERCENT OF THE OPTIMUM MOISTURE CONTENT. PROOF ROLL THE AREAS TO BE FILLED OR ON WHICH STRUCTURES ARE TO BE PLACED. A LOADED DUMP TRUCK OR OTHER RUBBER TIRED EQUIPMENT SHALL BE USED FOR PROOF ROLLING. OVERLAPPING PASSES OF A VEHICLES SHOULD BE MADE ACROSS THE SITE IN ONE DIRECTION AND THEN PERPENDICULAR TO THE ORIGINAL DIRECTION OF ROLLING. • ANY YIELDING, PUMPING OR SOFT AREAS SHOULD BE CUT OUT AND REPLACED WITH FILL COMPACTED AS DESCRIBED HEREIN. • THE PROPOSED FILL SHOULD BE LIMITED TO SOILS CLASSIFIED IN ACCORDANCE WITH ASTM D-2487 AS GM, GC, SW, SM, SC, ML AND CL. SOIL CLASSIFIED AS PT, OH, OL, CH AND MH ARE NOT SATISFACTORY AS COMPACTED FILL. • FILLS AND EMBANKMENTS SHALL BE CONSTRUCTED AT THE LACTATIONS AND TO THE LINES AND GRADES INDICATED ON CONSTRUCTION PLANS. THE SLOPE SHALL NOT EXCEED 2 FOOT HORIZONTAL TO 1 FOOT VERTICAL (3 FOOT HORIZONTAL TO 1 FOOT VERTICAL IN THE PUBLIC RIGHT OF WAY). THE COMPLETED FILL SHALL CORRESPOND TO THE SHAPE OF THE TYPICAL SECTIONS INDICATED ON THE CONSTRUCTION PLANS. MATERIAL REMOVED FROM THE EXCAVATION SHALL BE USED IN FORMING THE FILL. FILL MATERIAL SHALL BE REASONABLY FREE FROM ROOTS, OTHER ORGANIC MATERIAL, TRASH AND STONES HAVING MAXIMUM DIMENSIONS GREATER THAN 6 INCHES (4 INCHES IN TRENCHES FOR UTILITIES). NO FROZEN MATERIAL WILL BE PERMITTED IN THE FILL. STONES HAVING A MAXIMUM DIMENSION OF 4 INCHES WILL NOT BE PERMITTED IN THE UPPER SIX INCHES OF FILL OR EMBANKMENT OR UTILITY TRENCH. THE MATERIAL SHALL BE PLACED IN SUCCESSIVE HORIZONTAL LAYERS NOT MORE THAN 8 INCHES THICK, UNLESS OTHERWISE NOTED, IN LOOSE DEPTH FOR THE WIDTH OF THE CROSS-SECTION AND SHALL BE COMPACTED TO AT LEAST 97 PERCENT OF THE MAXIMUM LABORATORY DRY DENSITY ACCORDING TO STANDARD PROCTOR (ASTM D-698, AASHTO T-99). MOISTURE SHALL BE WITHIN 3 PERCENT OF THE OPTIMUM MOISTURE CONTENT. THE TOP 12 INCHES OF THE PAVING, PARKING AND/OR ROADWAY SUB -GRADE SHALL BE COMPACTED TO 97 PERCENT OF THE MAXIMUM DRY DENSITY (STANDARD PROCTOR). EACH LIFT SHALL BE ROLLED WITH A VIBRATORY ROLLER, A SHEEPSFOOT ROLLER, OR A LOADED RUBBER TIRED DUMP TRUCK, SCRAPER OR LOADER. IF THE SOIL IS TOO DRY, A WATER TRUCK WITH SPREADER BAR OR SPRAY HOSE SHALL BE USED TO BRING THE SOIL TO THE PROPER MOISTURE RANGE. THE WATER SHALL BE THOROUGHLY AND PROPERLY MIXED WITH THE SOIL PRIOR TO COMPACTION. • STORM DRAIN PIPES SHALL BE PLACED ON FIRM BOTTOM AND HAND TAMPED TO SAFE UP THE PIPE. A CUSHION OF SOIL SHALL BE TAMPED ABOVE THE CROWN OF THE PIPE IN ACCORDANCE WITH THE PIPE MANUFACTURER'S RECOMMENDATIONS SO THAT THE HEAVIER COMPACTION EQUIPMENT CAN THEN BE USED TO BRING THE SOIL TO A DENSITY AS DESCRIBED ABOVE FOR FILL AREAS. • IF SOILS INVESTIGATION REPORT IS PROVIDED, THEN FOLLOW THE RECOMMENDATIONS OF THE REPORT IF THEY EXCEED THE RECOMMENDATIONS OF THESE SPECIFICATIONS. TOPSOIL: • UNLESS OTHERWISE SPECIFIED, AREAS DESIGNATED FOR GRADING OPERATIONS THAT CONTAIN A BLANKET OF TOPSOIL SHALL BE STRIPPED AND PLACED IN CONVENIENT STOCKPILES FOR LATER USE AS A TOPSOIL BLANKET ON THE NEW GRADED AREAS SPECIFIED HEREIN, OR AS DESIGNATED. TOPSOIL SHALL BE STRIPPED FROM ALL AREAS DESIGNATED TO RECEIVE FILL. THE STRIPPING OF MATERIAL FOR TOPSOIL SHALL BE CAREFULLY DETERMINED AND ONLY THE QUANTITY REQUIRED SHALL BE STOCKPILED. MATERIAL STOCKPILED SHALL BE STORED IN A SATISFACTORY MANNER TO AFFORD PROPER DRAINAGE. WHEN GRADING OPERATIONS PERMIT, INSTEAD OF STOCKPILING, THE TOPSOIL SHALL BE HAULED AND SPREAD DIRECTLY ON THE AREAS DESIGNATED TO RECEIVE TOPSOIL. ROCK EXCAVATION: • IF ROCK IS ENCOUNTERED, CLEAR AWAY EARTH TO EXPOSE MATERIAL. NOTIFY OWNER AND RECEIVE WRITTEN INSTRUCTIONS PRIOR TO EXCAVATION. REMOVE ROCK TO A DEPTH OF 6 INCHES BELOW AND 8 INCHES ON EACH SIDE OF PIPES IN TRENCHES. A MEASUREMENT OF EXTENT OF ROCK TO BE REMOVED SHALL BE MADE. ROCK EXCAVATION SHALL BE PAID FOR IN ACCORDANCE WITH AGREEMENT WITH THE OWNER. SITE DEVELOPMENT PLANS FOR )N4 DEVELOP CAR WASH CLIENT W4 DEVELOPMENT PROJECT LOCATION MENT 2100 RIO HILL CENTER CHAR LOTTESVI LLE, ALBEMARLE COUNTY VI RG I N IA 22901 TAX PARCEL ID # 045 00-00-00-09 3 CO J U LY 05, 2019 45Vn. 'u-85 45 84A+ "4 - ZO PO=R7 D 6 9 a�A aP Cry' O .O *a a5 ac1 49Bt 041�Caf rrshc°°k=D. /C 45-78 7i a5,a 1 GhC.�`.' 45-112 - / 4591-01-01-00 ro 45-88B i5-86 k5 t12G a^,r CP /41 ,f 4 h Gj 45-i12C 45-38 45-90 45 1a4 1 y VC a 1`4 45-29A6 m �,,` aJ ems'/ 45-509E 2r% 45B1-05-CA 44 E yg1�_S.Prin&: n q otlA q / 2a4581-41-mA- A JO or Hlist ag^� 45-93A ° y '•7ry htl.P ,j � I��r b. 0.5C. 45 as +tr.xtlq o °q u"ns erg-{ia'r �,-. llCas�oi 4rn io /'d5-27A 45 h, Y f6 yi45C 010M`--§`-`' }-._y , 5 a 7DA ly v d5C 41 M8 ��6 .0 rya as -Da ;e.a c1-�oq1� 4'W$bdhraak 4s�luM; +ts a5-27 1ss-rdtl ° '. j ,#" 111n __c� s "' °Ldl,p as: 8° 1i / °14y- ��3 ��ti� ° ss y 45-t 77 O a r� '�--1 �''u °o �h \ay F @ 45-44B E 6 as 0v e 1F xs45Su`' at°jr , 11y - eay �Ir O h/5� 45-145 fl, 1 f\ l6a 6iG kh/"l-'C.'L �� OYf? - -45 104B5 5 d Jnfi @ a -102A 45-10 Y°i q y b2 ryoer\,th/`d 0.5C 02-� � il 5i 125' 124 ✓ fiC-421E a rydti S c a St-t 12A' 61 -524E5 .-,2 1' m , "-12 w LOCATION MAP SCALE: N.T.S. PROJECT NOTES: DEVELOPER: W4 Development 2500 Daniell's Bridge Road Building 200, Suite 3A Athens, Georgia 30606 Contact: Greg DeBacker Tel. (706) 548-1151 ENGINEER: Carter Engineering Consultants, Inc. 3651 Mars Hill Road - Suite 2000 Watkinsville, GA 30677 Contact: Jeff Carter, P.E. jeff@carterengineering.net Tel. 770-725-1200 SHEET INDEX SHEET NO. DESCRIPTION 1 COVER SHEET 2 EXISTING CONDITIONS & DEMO PLAN 3 SITE PLAN 4 UTILITY PLAN 5 GRADING PLAN 6 PI-+ASE 1EROSION-CON-T-ROLPL-AN EROSIO-N CO-NTRO-L DETAILS 8 PTO-i3 M-A N-D--S-EWER P-RO-FI-LE -TA-N DA-R-D DETAILS 10 ADAACCESS-FL-AN 11 ADA DETAILS 12 LANDSCAPE PLAN A. LAAN-DSOAP-E-D-ET41-L� 14 OUTD-0O-R LaGHT-1 N ESP-L�4N REVISION BLOCK REV. NO. DATE DESCRIPTION 1 07/05/19 ARCHITECTURAL REVIEW BOARD SUBMITTAL Carter Engineering Consultants, Inc. 3651 Mars Hill Road Suite 2000 Watkinsville, GA 30677 P: 770-725-1200 F: 770-725-1204 www.carteren ineerin .net g g ���pLTH 0,�tr o JAMES J, CARTERD No. 41920 `AID IAI E� 24-HOUR CONTACT: Greg De6acker (706) 548-1151 Project Tract = 1.05 acres Disturbed area = 0.86 acres Total Impervious Area = 0.57 acres Project Site Location: Lat 38.087836' Long-78.471183' DEMOLITION NOTES: 1. THE LOCATIONS OF ALL EXISTING FACILITIES SHOWN ON THIS PLAN HAVE BEEN DETERMINED FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THEIR ACCURACY. PRIOR TO THE START OF ANY DEMOLITION ACTIVITY, THE CONTRACTOR SHALL NOTIFY THE UTILITY COMPANIES FOR ON SITE LOCATIONS OF EXISTING UTILITIES. 2. THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR, SUPERVISION AND EQUIPMENT REQUIRED FOR THE ORDERLY DEMOLITION AND REMOVAL OF EXISTING CURB AND SIGNS AS SHOWN ON THE DRAWINGS AND DESCRIBED HEREIN. A. DEMOLITION AND REMOVAL OF EXISTING ON SITE ASPHALT, CONCRETE PAVING, AND CURBING TO DEMOLITION LINE SHOWN. 3. ALL EXISTING CURB AND SIGNS INDICATED ON THE DRAWINGS TO BE REMOVED SHALL BE DEMOLISHED AND REMOVED BY THE CONTRACTOR. REMOVE NO STRUCTURE SUBSTANTIALLY AS A WHOLE. DEMOLISH COMPLETELY ON THE PREMISES. 4. ALL EXISTING SEWERS PIPING UTILITIES SHOWN ARE NOT TO BE INTERPRETED AS THE EXACT LOCATION, OR AS THE ONLY OBSTACLES THAT MAY OCCUR ON THE SITE. VERIFY EXISTING CONDITIONS AND PROCEED WITH CAUTION AROUND ANY ANTICIPATED FEATURES. GIVE NOTICE TO ALL UTILITY COMPANIES REGARDING DESTRUCTION AND REMOVAL OF ALL SERVICE LINES AND CAP ALL LINES BEFORE PROCEEDING WITH THE WORK. 5. PROVIDE ADEQUATE PROTECTION FOR PERSONS AND PROPERTY AT ALL TIMES. EXECUTE THE WORK IN A MANNER TO AVOID HAZARDS TO PERSONS AND PROPERTY AND PREVENT INTERFERENCE WITH THE USE OF AND ACCESS TO ADJACENT BUILDINGS. STREETS AND SIDEWALKS SHALL NOT BE BLOCKED BY DEBRIS AND EQUIPMENT. 6. CONTRACTOR MUST STOP OPERATION AND NOTIFY THE OWNER FOR PROPER DIRECTION IF ANY ENVIRONMENTAL OR HEALTH RELATED CONTAMINATE IS ENCOUNTERED DURING THE DEMOLITION/EXCAVATION PROCESS. 7. DISPOSAL A. REMOVE AND LEGALLY DISPOSE OF ALL OTHER RUBBISH, RUBBLE, AND DEBRIS. COMPLY WITH ALL APPLICABLE LAWS AND REGULATIONS GOVERNING DISPOSAL OF WASTE AND DEBRIS. 8. PAVEMENT REMOVAL A. WHERE EXISTING PAVEMENT IS TO BE REMOVED, SAW -CUT THE SURFACING LEAVING A UNIFORM AND STRAIGHT EDGE WITH A MINIMUM OF DISTURBANCE TO THE REMAINING ADJACENT SURFACING. IF CONSTRUCTION RESULTS IN RAVELING OF THE SAW -CUT SURFACE, RECUT BACK FROM THE RAVELED EDGE PRIOR TO RESTORATION. B. WHERE EXISTING PAVEMENT, CURB, CURB AND GUTTER, SIDEWALK, DRIVEWAY OR VALLEY GUTTER IS REMOVED FOR THE PURPOSE OF CONSTRUCTING OR REMOVING BOX CULVERTS, PIPE, INLETS, MANHOLES, APPURTENANCES, FACILITIES OR STRUCTURES, SAID PAVEMENT, ETC., SHALL BE REPLACED AND RESTORED IN EQUAL OR BETTER CONDITION THAN THE ORIGINAL, CONTRACTOR SHALL PROVIDE ALL NECESSARY LABOR, MATERIALS, EQUIPMENT, TOOLS, SUPPLIES, AND OTHER EQUIPMENT AS REQUIRED. 9. CONTINUOUS ACCESS SHALL BE MAINTAINED FOR THE SURROUNDING PROPERTIES AT ALL TIMES DURING DEMOLITION OF THE EXISTING FACILITIES. 10.PERMITTING: IT IS THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN ANY REQUIRED PERMITTING FOR DEMOLITION FROM RESPONSIBLE REGULATIONS AND FULLY ACKNOWLEDGE AND COMPLY WITH ALL REQUIREMENTS PRIOR TO COMMENCING DEMOLITION WORK. 11.IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED IN ORDER TO PERFORM THE CONTRACT WORK FOR THIS PROJECT. THE CONTRACTOR SHALL CONDUCT SITE VISITS AND SHALL EXAMINE ALL OF THE INFORMATION WITHIN THESE DOCUMENTS: ALL DISCREPANCIES AND/OR OMISSIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO BID SUBMITTAL. 12.CONTRACTOR SHALL LIMIT ALL DEMOLITION ACTIVITY TO THAT AREA DELINEATED IN THE DRAWING, ALL OTHER EXIST. UTILITIES INCLUDING: STORM DRAINAGE, GAS, ELECTRIC, TELEPHONE, AND WATER & SEWER SHALL BE PRESERVED & PROTECTED. I REMOVE LINES AS NECESSARY (TYPICAL) 7 r Ex •' EX INV. OUT WITH FLARED - 14 END SECTION =470.4' 30 1► 1 1 A STORMWATER EASEMEDI -Z Ld EXISTIN ZEL 1 / Q DRAINAGE I -n- Gs� \ / 1 --_ - -SG- - -n- - -5S= -- - • ��EASEMENT s_ D OH 1.0 ZLµf\ A OHP OH OHP- F / t OHP OHP OHP OHP OH TOP 486.1' OH T cA IS•,� �,\; . �� /�T -����" w uG T � \ / % � RC -_-_----- --- INV. IN=475.3' - ---- --�IAL�Ot}T_11r�485 ---� - - - ---- _ --- -- -_---_ -_-- - - _----------= �- ------� -- - ---� } EX MANHOLE NOT _------ --- ---S2 19' 26"W------\� /��---____ `__---- -2-1.9 FOUND_ r/ , --_--- - -UGT_UG1-- --�_�UGT--- --------------- \ _ _t - - _ 1`�--------.- BUG UGT--UCT - -uGT- -UGT- �� _------_- -- T� D° p V p D uk D EX DROP INLET EXISTING LANDSCAPE TO BE REMOVED (TYPICAL) EX GRATED DROP INLET--JTOP =487.1' I TOP=484.3' INV. OUT (15" RCP) =481.4' INV. IN=475.8' I INV. OUT=475.7' U. S. ROU TE 29 (SBL) I SEMINOLE TRAIL (VARIABLE WID TH) y IS � � I i 1 SCT RIO HILL, LLC, / I C/O ROSENTHAL PROPERTIES I TM# 04500-00-00-094AO I I I I I DB 4134, PG 199 I I � ' _--498- _----- I W / / - I n//�----495-----------------------� WV 3 a \ Q / / \ ' / w / /hI 4/CAP/Y--CENTER--)- - - - TOP /=it/71--'------- --RIO-+ L-L /!1 /----------wv. - - - I �\� I \ i x ' z E�ISTING \ \/ / SIGN EASEME I�I \ \� X / /ZAP/ / ' / N24 18' 10"E / 191.25 , L 3 // 1711 lI I IE� BRICIKSIGN�= 8' /' I I I LL�� E(X,14 I AKS• �� /7/ �� n � I i Q �' � EXISTING ASPH A LT PARKING LOB AND CURB / 1 I / AND GUTTER 0 BE DEMOLISHED AND /I REMOVED. I ��2 4' 0 EXISTING TREE TO BE REMOVED (TYPICAL) /t� `� 1 1 I I I I I I I i I 1 ' 11 I I I II (DI 1, I/ 1' I I I \ /1 \ /OD p I I OD CoI AJ I I I \� / 1 �� Q II II �' II I II i6 11 PI 19, 1 / �\\ /I \ 1 / II I SCT RIO HILL, LLC, 11 1 1 1 1 1 1 1 1 1 1 1 �I 1 J �!\ �R Z2� 18" AKS I J J X IJ`�v1PST RI A / \ \ C/O ROSENTHAL PROPERTIESAIQ \1 TM# 04500-00-00-094A0 I I I I I I I I 1 N h; /;_ ,- / \ \ \ q/ 1 1 I I I I � I � �/� � I v I I � �g _ I � 1 / DB 4134, PG 199 I I I I I 2 \ \\\ \� 1 / / II i I II II II II II II II�� 1'- I ��, % /rt I I � �\ �' //\ If A = 8'06' 15" L= 140.14' C. = 140 02' I/ I C.B. = S59'24'42" E EX EXISTING EXISTING STRUCTURE TO BE DEMOLISHED AND REMOVED. DISPOSE OF IN APPROVED LANDFILL. - I VXI�TIINq A�IT R1' I I I I� I I / �� �� EXISTING UTILITY EASEMENT �- I I I I I I I III I� I II� EX CO EXISTING LIGHT POLE TO BE REMOVED. PIIJE I v� rA Eh 14" WWOOD ----- _--------- ____ EX 15" RCP LET INV. IN =482.3' INV. OUT=481.3' OHP UGE---UGE EX JBOX p T- T- D EXISTING SIGN AND LANDSCAPE. DEMOLISH AND REMOVE (DISPOSE OF IN AN APPROVED LANDFILL) '/ �`✓ d3-1 ❑/ -..1 pdpW OB�p 45 81 WSJ. SS SB ��Q ,\ a. 0 9r I � y M1� 45-6aC a OF F3 /sj r�C UJ O \ ,� �50.xr r7`ti ,'L�`�/ ^.'.'•:ry F�'& 458104 t.vC/a r•Fsbrol kOi SQ 45-79�+�,\2i a 8sa1 `d 4s -tit 5 / J y _87 45-W - 2 45-68A ` ^ :4 4581-qt-0B-1 ,ro. 45.-88B 45-86 �45 112G 45-90Aa ��C, "� 45-112U �� y 45-88 t ' eye h 4 JR 45-90 d �09C3.: O I�;� W 4 0 45-29AG 45 91 m? B7F�� G5-409E. 45 iq9 u7^�7 45 B7-01-9A-4 a 4set-gr-aA.- c v a Agnar-Hu t o-yg� 45-93A il'ti c 2..o a BT �'aA.s 45-95 I L 45 2FA. 4 5 /�ROVl�5l5 ef=E. -rS45C vqt O��M=9"-`�� +CS - 45-94A. try aT °9-L3 C�01 qp pM-0 ale 1Z 45-94 /L•°Care%4�: ° 45GV'e'30fibr00�t 4SC p 0 ., iFC 451 T E$ W \ JA& . 1y y3atl ArPq'St Y 43rq s\ 7cj ti°91IZI %g M1^eJ�y�rtt 'ir °'s. t eA f1 6 nary / /pOpp, Z, �a 0 t/�140p s✓u1� �t.�� '" '/,� 4f_�0"W�^� °¢g' \�``lljr`'�S 9 0y) a2k a 45,y Ttlag., e ti; w!ox i ✓ e 1k l .- -0 as 3� � 45109 F97 i. 10< py4 nyG"4 h �' q q �'ys' lj a,✓ \ /� 49K'-O a, a fob'`" ad n�NI 4. 13$ d Cr' 48-102A 0.F 192J'1`� 5-10 :.�ry45-10M185 / 4 A b. 6. o f 4\ e1-124E8 \ T lr 64-120 'ta 64- a ,� I aPstu 61-t24E6 p k-2�ikrypP a �� b'l�Yr LOCATION MAP SCALE: N.T.S. PROJECT NOTES: DEVELOPER: W4 Development 2500 Daniel's Bridge Road Building 200, Suite 3A Athens, GA 30606 Contact: Greg DeBacker Phone: (706) 548-1151 ENGINEER: Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 Contact: Jeff Carter, P.E. Tel. (770) 725-1200 jeff@carterengineering.net Property Location: 2100 Rio Hill Center, Charlottesville, Albermarle County, Virginia 22901 Parcel No.: #04500-00-00-093C0 Conditional Approval: ZMA 1987 - 00007 and SDP 1988- 00001 Current Zoning: PD-SC (Planned Development Shopping Center) Proposed Zoning: PD-SC (Planned Development Shopping Center) Setbacks: Front:40-feet Rear:20-feet Side: 15-feet Proposed use: Carwash with associated utilities and parking Proposed Building Height 20 Feet Project Tract 1.05 acres Disturbed Area 0.86 acres Boundary and topographical Information obtained from field run survey by Hurt & Proffitt dated April 30, 2019. Phone (434) 847-7796 Contour interval is 1 Feet (NAVD 88) F.E.M.A. Flood Insurance Rate Map No. 51003C 0278D, dated February 02, 2006 indicates that this property is located in "Zone X". The underground utilities shown hereon have been located from field information and existing drawings. The surveyor nor engineer warrants that the underground utilities shown comprise all such utilities in the area, either in service or abandoned. The surveyor nor engineer warrants that the underground utilities shown are in the exact location indicated. The surveyor nor engineer has physically located all the underground utilities. It is the responsibility of the contractor to field locate all utilities prior to commencing work and notify engineer if a discrepancy is found. The contractor shall verify the invert elevations of all existing storm and sanitary sewer structures prior to commencement of storm and sanitary sewer construction. UNDERGROUND UTILITIES DISCLAIMER Information regarding the reputed presence, size, character and location of existing underground utilities and structures related to underground utilities is shown heron. There is no certainty of the accuracy of this information and it shall be considered in that light by those using this drawing. The location and arrangement of underground utilities and structures related to underground utilities shown hereon may be inaccurate and utilities and structures related to underground utilities not shown may be encountered. The owner, his employees, his consultants and his contractors shall hereby distinctly understand that the surveyor is not responsible for the correctness or sufficiency of this information regarding the underground utilities and structures related to underground utilities shown hereon. v v Know what's below Cali before you dig dial 811 z 2D F I.- U a w V w Or 0 o a J m Ol Z Ln LD a 0 O w 4t-1 p,LTH ED JAMES J, CARTERS U No. 41920 NAL CARTER ENGINEERING CONSULTANTS Carter Engineering Consultants, Inc. I 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 P: 770.725.1200 F: 770.725.1204 www.carterengineering.net U) z Qa J Z z> W_J J z 5J > IIJ L I:L w O O G ^^ 1..� �. O Q p W >LU U W W Z W\ 0 LU J J LU O LU O 0 � N V 1 PROJECT NAME: W4 DEVELOPMENT CHARLOTTESVILLE, VIRGINIA SHEETTITLE: EXISTING CONDITIONS & DEMO PLAN SHEET NUMBER: 2 PROJECT NUMBER: 19016W4D DATE: 07/05/19 I ' S I SCT RIO HILL, LLC, / I C/O ROSENTHAL PROPERTIES I TM# 04500-00-00-094AO I I DB 4134, PG 199 I 3 I ! W ' I I GRATED DROP INLET RIO HILL CENTER I ' I U TOP=488.7' I I ' U INV. OUT=479.5' I ' Ic� PROPOSED DUMPSTER I EXISTING ENCLOSURE WITH HEAVY DUTY SIGN EASEMENT I m DUMPSTER CONCRETE PAD. i I / w PK NAIL D ___ _.__�- ___ �- _ _ _ _ _ 24 18' 10"E _ 191.25' _ - _ L I � / I � 1 1 I I � I SCT RIO HILL, LLC, C/O ROSENTHAL PROPERTIES I TM# 04500-00-00-094AO I DB 4134, PG 199 1 A 1 j I � 1 I � I I / / l 1 � EXISTING 11 SANITARY I ' EASEMENT ' AUTO SENTRY AND GATE CONCRETE ISLAND (TYP.) I ' EX INV. OUT WITH FLARED I END SECTION=470.4' 1A h I I �. eo / I STORMWATER EASEMENT I IN/ D OHP OHP OHP OHP OHP OH\ - EX DROP INLET Fr\\ TOP=486.1' INV. IN=475.3' RCIO INV. OUT=474.1' 1 S24 19' 26"W Luc r- �UC c o c lA o n v c Ci EX GRATED DROP INLET TOP=484.3' INV. IN=475.8' INV. OUT=475.7' I I 0 0 0 a I II / I I I 1 I 1 i I� 19' 26' 119, I I 1 1 29 VAC -BOOM I I PARKING SPACES I II I I I / / I I A = 8'06' 15" L = 140.14' R = 990.77' C. = 140.02' C.B. = S59'24'42"E 11' EXISTING UTILITY EASEMENT I �I II I VAC -BOOM CANOPY (TYP.) ry I I E 1 (2)11' X 18' H/C CONC. PARKING SPACE W/ 5' WIDE STRIPED UNLOADING VAC BOOM CANOPY (TYP.) I I II --T - •� - -- - ------ -iWA- • a a . 3• a. - �t - f 1� � si :� _41 � 9 i--,'=� - - i Y •_ - � Li-s-P-� I 3' I f '` • '°.., ' r : •`. : 4 • 7�0"•�ONCfZETf,'SIdf�A//AFLK I I Imo, EX 15" RCP PROPOSED CARWASH - ��/;�'' EX DROP INLET 3,739 S.F. JL / '�' I TOP=488.2' 3 INV. IN=482.3' INV. OUT=481.3' F.F.E. = XXXX.XX j� I _ / // GQ EXISTING ;'�/O`~ DRAINAGE? /', <D EASEMENT G OHP OHP OH: -OHP OHP OHP OHP�`O,Hff / t E< OX G OHP -UG T�Gj/L UG E- _ -UG E- �-- EX 15" RCP ---------------------------------------- --_-------------- - 1 /- ion- EX JBOX -- ---------------- � � on- -7- _ -- ------ - - - - 214.98'- EX MANHOLE NOT FOUND / / I UGT� BUG T- -UG 1°T- - -UG T - - -UG T - -UG T - - -UG T - -74AG T p I o D ,--P-UGT D U.S. ROUTE 29 (SBL) SEM/NOLE TRAIL (VARIABLE WIDTH) EX DROP INLET -� I TOP=487.1' INV. OUT (15" RCP)=481.4' i I I I ) N' Know what's below Call before you dig dial811 - d3-1 ❑/ pdpW OB�p 45 81 Fie. S5 SB ��Q ,\ 9 t i g � ti� as.sac y�eq qf� M1S of ° ' � � �r Bdxr 2F n�`� nry vsF�'6 45B7 04 1.-Ca rrsbrook_ .d 4,5-7�?. SS-IItiA1 d �. 45--112 5 ! 45-afiA .45-68A d5-SI �ry ^ a581-05-0�} ,roY. 45.-88B 45-86 qs r1T2G �� o �p e 45-90Aa 45-88 >�C, 45-112C `yh yp: 45 90 q 00903 40 o a o #5 -20 ;4tr., , Ji 45-29A6 -91 �Brt `w� 45k09E. A5 S09 d� 45®t Of-OA-4 '°erg S P S Agn or-Hurr e7'� Sea !1 o. d� llA M" 4 45-95 v,q roVK11'l ET=E. �I �-r: 45 2FA /' -..45C OT 0M' 45. 2'I was i>o 4s 4441 r� "d �,4sr �,o eA��Q T �5 IJ_ ry asc� 45-17G - 1 � 45 94B denNegbr`3�,.:, k ❑ s a K a a .7- Ps a,Tg 45709 'WSJ Yn1,096U yi0< 1 /"''\M1fi �.l I�{y; Hrwt IN cJ ! 3\9-102A a5 102 b 45-106/ I --1`04B5 orLlb I124E3 5-� ClS'E-t24E5 0 J40'4 tip�/q^ if t2 s J m - _ I'xE? LOCATION MAP SCALE: N.T.S. PROJECT NOTES: DEVELOPER: W4 Development 2500 Daniel's Bridge Road Building 200, Suite 3A Athens, GA 30606 Contact: Greg DeBacker Phone: (706) 548-1151 ENGINEER: Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 Contact: Jeff Carter, P.E. Tel. (770) 725-1200 jeff@carterengineering.net Property Location: 2100 Rio Hill Center, Charlottesville, Albermarle County, Virginia 22901 Parcel No.: #04500-00-00-093C0 Conditional Approval: ZMA 1987 - 00007 and SDP 1988- 00001 Current Zoning: PD-SC (Planned Development Shopping Center) Proposed Zoning: PD-SC (Planned Development Shopping Center) Setbacks: Front:40-feet Rear:20-feet Side: 15-feet Proposed use: Carwash with associated utilities and parking Proposed Building Height 20 Feet Project Tract 1.05 acres Disturbed Area 0.86 acres Boundary and topographical Information obtained from field run survey by Hurt & Proffitt dated April 30, 2019. Phone (434) 847-7796 Contour interval is 1 Feet (NAVD 88) F.E.M.A. Flood Insurance Rate Map No. 51003C 0278D, dated February 02, 2006 indicates that this property is located in "Zone X". The underground utilities shown hereon have been located from field information and existing drawings. The surveyor nor engineer warrants that the underground utilities shown comprise all such utilities in the area, either in service or abandoned. The surveyor nor engineer warrants that the underground utilities shown are in the exact location indicated. The surveyor nor engineer has physically located all the underground utilities. It is the responsibility of the contractor to field locate all utilities prior to commencing work and notify engineer if a discrepancy is found. The contractor shall verify the invert elevations of all existing storm and sanitary sewer structures prior to commencement of storm and sanitary sewer construction. UNDERGROUND UTILITIES DISCLAIMER Information regarding the reputed presence, size, character and location of existing underground utilities and structures related to underground utilities is shown heron. There is no certainty of the accuracy of this information and it shall be considered in that light by those using this drawing. The location and arrangement of underground utilities and structures related to underground utilities shown hereon may be inaccurate and utilities and structures related to underground utilities not shown may be encountered. The owner, his employees, his consultants and his contractors shall hereby distinctly understand that the surveyor is not responsible for the correctness or sufficiency of this information regarding the underground utilities and structures related to underground utilities shown hereon. PARKING DATA Parking Required: Requirement: One (1) space per each one hundred (100) square feet of retail sales area for the first five thousand (5,000) square feet and one (1) space per each two hundred (200) square feet of retail sales area above five thousand (5,000) square feet. For purposes of this paragraph, 'retail sales area'shall be deemed to be (1) eighty (80) percent of the gross floor area; or (2) at the request of the applicant, the actual retail sales floor area as shown on floor plans submitted by the applicant delineating the actual retail sales area, which plans shall be binding as to the maximum retail sales area used. Retail Sales Area = 3,739 Square Feet of Building = 2,991 Square Feet (80%) Required Parking = 29 Parking Spaces Required (2,991 / 100) Provided Parking = 29 Parking Spaces Provided Handicap Parking = 2 Provided (2 Required) SITE DATA Site Information: Total Tract Area = 45,787 sf 1.05 ac (100.00% Existing Impervious Area = 19,002 sf 0.44 ac (43.62%) Existing Landscape Area = 26,785 sf 0.61 ac (56.38%) Total Impervious Coverage = 24,661 sf 0.57 ac (53.86%) Structure Coverage = 3,739 sf 0.09 ac (08.17%) Vehicular Coverage = 19,842 sf 0.46 ac (43.34%) Pedestrian Coverage = 1,080 sf 0.02 ac (02.35%) Proposed Landscape Area = 21,126 sf 0.48 ac (46.14%) Total Coverage Area = 24,661 sf 0.57 ac (53.86%) z 2 F F U a w V w W p o a J on a) Z W Ln LD Q 0 0 Q w 4t-I N��p,LTH o JAMES JI CARTERS U No. 41920 A. NAL CARTER ENGINEERING CONSULTANTS Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 P: 770.725.1200 F: 770.725.1204 www.carterengineering.net z Qa J /z V zw W J z 5J UJ c/1 w O O G ^^ 1..� L. O Q W >LU U w J w w W\ 0 U J LU O LU O O � N PROJECT NAME: W4 DEVELOPMENT CHARLOTTESVILLE, VIRGINIA SHEETTITLE: SITE PLAN SHEET NUMBER: 3 PROJECT NUMBER: 19016W4D DATE: 07/05/19 1 ' S ' I � 1 I I I� ' I I W 1 U' C LJ GRATED DROP INLET ' I L` TOP=488.7' I , Q INV. OUT=479.5' I 0 I ' z_ I ~ I w EX PK NAIL l� D I ' I I � I I � I I � I SCT RIO HILL, LLC, I I C/O ROSENTHAL PROPERTIES I TM# 04500-00-00-094AO N DB 4134, PG 199 0� 1 C 1 j I I 1 I � 1 EXISTING I SANITARY I EASEMENT ' I I � I� 1 EX INV. OUT WITH FLARED I END SECTION=470.4' 21 � STORMWATER EASEMENT I ------- 7� j 1 I IN GRATE INLET #002- PROPOSED PIPE No. 4- 50 L.F. - 18" 0 HDPE SLOPE = 1.0% PROPOSED JUNCTION BOX A-1- PROPOSED PIPE No. 5 5 L.F. - 18" 0 HDPE SLOPE = 1.0% EXISTING STORM DROP INLET A-0. LEAVE EXISTING STRUCTURE IN PLACE AND ADJUST RIM VERTICALLY TO MATCH FINISH GRADE. RIM = 486.10 EXISTING FL IN (SE) = 475.30 PROPOSED FL IN (N) = XXX.XX IN X P INL Fr\\ =48 INV. 1=475.3' RCP `'I, I . OUT=474.1' S24 19' 26"W Uc T� Luc r- �UC p O p p p EX GRATED DROP INLET TOP=484.3' INV. IN=475.8' INV. OUT=475.7' I I I I I GRATE INLET#001 PROPOSED PIPE No. 2 109 L.F. - 18" 0 HDPE SLOPE = 1.0% I /- CURBINLET#002 ' I 6" 0 PVC - SLOPE 1% MIN. s nr CA Ift- PROPOSED PIPE No. 3 - 0 0 41 L.F. - 18" 0 HDPE SLOPE = 1.0% SCT RIO HILL, LLC, / C/O ROSENTHAL PROPERTIES I / TM# 04500-00-00-094AO I DB 4134, PG 199 3 I I VVVV 3� I RIO HILL CENTER I j I I 3 I 1 EXISTING _ SIGN EASEMENT I 24 18' 10"E 191.25' I I I I I II I I D I I I II D I I{ D I I I I I v I � ►I �I �I I I �I -------------------------- 750 GAL. OIL AND I I WATER SEPARATOR I I (SEE DETAIL) 3 I A = 8'06' 15" L = 140.14' R = 990.77' C. = 140.02' C.B. = S59'24'42"E EXISTING UTILITY EASEMENT SAMPLE MANHOLE (SEE DETAILS) I I O 3 e �I I III O � I GAL. 20 , 0 GA 8 C-------------- 'D i, REFER TO DETAILS I O PROPOSED PIPE No. 1 I / I SLOPE = 1.0% � HDPE PROPOSED CARWASH 3,739 S.F. F.F.E. = XXXX.XX ELE i EXISTING Z..W 2 W _ 1 W - 1"W - 2.W - 2.W - r _ 1"W - 2..W - Z..W-&RAN7A4 2..W E EME`LTE OHP OHP OHP OHP OHP OHP ELE OHP `-UG ----------------------------�- EX 15"_RCP ---------------------- / ----- I - 214.98r EX MANHOLE NOT FOUND / _ UG 1°T- -UG T - - -UG T - -UG T - -UG T - �UG T p I o D p---P-UG T U.S. ROUTE 29 (SBL) SEM/NOLE TRAIL (VARIABLE WIDTH) EX DROP INLET -� I TOP=487.1' INV. OUT (15" RCP)=481.4' i I I I ) JG OHP / EX OX �F ' UGE-} - Gn JBO > an_ _ T UGT� O CURB INLET #001 --------------------- EX 15" RCP EX DROP INLET TOP=488.2' INV. IN=482.3' INV. OUT=481.3' e PROPOSED 2" WATER TAP -2" DOMESTIC WATER METER WITH RPZ BACKFLOW PREVENTER - PROPOSED ELECTRICAL TRANSFORMER - PROPOSED UNDERGROUND ELECTRICAL SERVICE -2" DOMESTIC WATER SERVICE 45-7 GO(45-76 � I rn� ah ry 4s.s9c y>M1eJ F4�\M1S o e u 451 1 45-85+ 45 84A+ 45-51 vsa C F`'e 45Ei 04 T.-Ca rrsbrook_ 'e 45-7?. 45-&tiAt d 45-112 _ 5 ! 45-a fiA .45-RA 45-81 4561-01-m- ,roY. 45.-8aB 45-80 7T2G ��� o� �a �e 45-90Aa 45-88 >�C, ss-TTse i p : 45 90 a d0'043 : 40 W o -28 45-29A0 -91 �Brt `w� 45 709E. 45 109 d� 45®i 01-DA-4gP0 w J 11t ,°s7+ Ra. P Y !S Agnor-Hurt e7�� c 45-9aA c i,.o Bi:arbd: i1'qC✓`-45. 4 45-95 v,q ROVI±•511 Ef=E. �I J-r: 07 OM' 10 QM 8 45-94;. 45-94A. r-c..aybrlp�, s i'W'�'odhrook �"oM,•.ss� 45. 27 was Y>o 4s 4441 r� "deA�rQ T T s. 1 rye, 45-173 o- 4 .. 1^e d U 's 45ratera tf 6gr�ry u/ v ' 4 1 � � �,ppec.� �Y y P � �vF7°RY'�'ao�denN`�'�br \�,��:+0 ��� `/3 ��,.:, k ❑ ` -., �; s dp pJS,"�,,cjJ RCA1 39-102A A`i 102b� 45-106/104B5 .Iv 4 \ 02-fi U rv'6 p�si e z, 1124E3 l� 1� Ti 125 5 Itu 64-120 y� 1 4RStu G 7A 6 6 hP a ,4 �!1 f) `Pay�1 M 11 F 114: I &5 '2-0 5iT- \'F LOCATION MAP SCALE: N.T.S. PROJECT NOTES: DEVELOPER: W4 Development 2500 Daniel's Bridge Road Building 200, Suite 3A Athens, GA 30606 Contact: Greg DeBacker Phone: (706) 548-1151 ENGINEER: Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 Contact: Jeff Carter, P.E. Tel. (770) 725-1200 jeff@carterengineering.net Property Location: 2100 Rio Hill Center, Charlottesville, Albermarle County, Virginia 22901 Parcel No.: #04500-00-00-093CO Conditional Approval: ZMA 1987 - 00007 and SDP 1988- 00001 Current Zoning: PD-SC (Planned Development Shopping Center) Proposed Zoning: PD-SC (Planned Development Shopping Center) Setbacks: Front:40-feet Rear:20-feet Side: 15-feet Proposed use: Carwash with associated utilities and parking Proposed Building Height 20 Feet Project Tract 1.05 acres Disturbed Area 0.86 acres Boundary and topographical Information obtained from field run survey by Hurt & Proffitt dated April 30, 2019. Phone (434) 847-7796 Contour interval is 1 Feet (NAVD 88) F.E.M.A. Flood Insurance Rate Map No. 51003C 0278D, dated February 02, 2006 indicates that this property is located in "Zone X". The underground utilities shown hereon have been located from field information and existing drawings. The surveyor nor engineer warrants that the underground utilities shown comprise all such utilities in the area, either in service or abandoned. The surveyor nor engineer warrants that the underground utilities shown are in the exact location indicated. The surveyor nor engineer has physically located all the underground utilities. It is the responsibility of the contractor to field locate all utilities prior to commencing work and notify engineer if a discrepancy is found. The contractor shall verify the invert elevations of all existing storm and sanitary sewer structures prior to commencement of storm and sanitary sewer construction. UNDERGROUND UTILITIES DISCLAIMER Information regarding the reputed presence, size, character and location of existing underground utilities and structures related to underground utilities is shown heron. There is no certainty of the accuracy of this information and it shall be considered in that light by those using this drawing. The location and arrangement of underground utilities and structures related to underground utilities shown hereon may be inaccurate and utilities and structures related to underground utilities not shown may be encountered. The owner, his employees, his consultants and his contractors shall hereby distinctly understand that the surveyor is not responsible for the correctness or sufficiency of this information regarding the underground utilities and structures related to underground utilities shown hereon. Know what's below Cali before you dig dial 811 Z 0 F F U aw V w Cr p 0 a J m Z UJ Ln O Q 0 Q w p,LTH 6FTAo �0 o JAMES J, CARTERS U No, 41920 0- NAL CARTER ENGINEERING CONSULTANTS Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 P: 770.725.1200 F: 770.725.1204 www.carterengineering.net z Q J a_ Z zw W J z 5J > W L w l__ O O ^^ 1..� �. O Q p W >� U w W Z LU 0 LU U J J LU O LU O O � N V / PROJECT NAME: W4 DEVELOPMENT CHARLOTTESVILLE, VIRGINIA SHEETTITLE: UTILITY PLAN SHEET NUMBER: 4 PROJECT NUMBER: 19016W4D DATE: 07/05/19 1 ' S I SCT RIO HILL, LLC, / I C/O ROSENTHAL PROPERTIES I TM# 04500-00-00-094AO I I I I I DB 4134, PG 199 I 3 ------ Ld I I I I 496-- ----------------- - T I n - 495- - V \ -__ - / - 3 I w / /�/ - -- ---- 494-- - - ----- --------------------\\\\ \� GRATE,EJ/6�CP/YNa-T--_-p-�-n--u-'I ---C E - \ / w /I TOP / 4 / /'-- ---- 2----f�l0-flit ErL TGCL_�----I � I '---------� \ 1-� /------- I ' \\ \\\ I X//� // // / \� // /�/ /�/ //S GN EASEMEI / P K AIL I D - - / 1 49 2 491 - / 24 18' 10"E _ /' 191.25' - / - / �r _ / Xv 4 49$ I I / I o 11 / I / I ' I I / i �� I / 1 C3 �I t I 494 I I I I I I Il 4, 1� 1 to 493 .0.I I � co ca 1 q l� l� `� � 1 1 II P 1 \ I/ I i / I I /' �� \ R �9 ,6 I SCT RIO HILL, LLC, 11 I 1 11 II II I II 11 I I� 1 I 1 C/O ROSENTHAL PROPERTIES 1 I I 1 I I I I I I I I I 1 1 492 � TM# 04500-00-00-094A0 I I I I I I III I / / / I I ,I DB 4134, PG 199 I I II II II I II 11 I I 1 °`V' ` I I II I I I`\--- \-492_\ 11 ', II I 11 ; II II �I II N'Ij� i I I I _ / I 492 / \----- ---I �� ��\\�� II II II 11 11 II I� III I 1 491 / l I \ N, \ IN I I 491 I anti , I IJ / / I i GRATE INLET i �I I I�XIhIN01 I I I ------L-------L--- 3 A = 8'06' 15" L = 140.14' R = 990.77' C. = 140.02' C.B. = S59'24'42"E [A�ITRY 1 I I 490 1 \ PROPOSED PIPE No. 2 ! EXISTING UTILITY EASEMENT I AEt EINTI j II I �' N, 109 L.F. - 18" 0 HDPE I I I I I SLOPE = 1.0% I CURB INLET#002 48980 1'I I � � II I Q I � \ 3 489.80 \ I 4 1W f O 489.85 1489.50 74.9L39] 490.39 490.39 I w EX INV. OUT WITH FLARED // / / // / // PROPOSED PIPE No. 3 = i1 - - - - - - - - - 7/ - - - - - - - - - - - - - - END SECTION=470.4' /� / / / / / / / / h I; \ - 41 L.F. - 18" HDPE I I I I I I I I O SLOPE = 1.0% I - JI I I / ----------------- 2 "go, 7 I_ - - "I IN/ /S1' 490.00 STORMWATER EASEMELIT--�, T- / / ZIN. I I PROPOSED PIPE No. 1 55L.F.-18"0HDPE _ _ _ _ / SLOPE = 1.0% �AFN,l/ / I CURB INLET#001 I -F tri 490.00 4 3,739 S.F. 489.00 F.F.E. = XXXX.XX - - _----r=-- / _ i/i GQ � � i� 489 I 488-- DRAINAGE ---n=-- �- - A8� --- _ - _n- - -\EASEMENT 1�� /� 487 P \HP OHP OHP OHP OHP OHP OtOHP ❑ -486 E% OHP OHP OHP N,{ OHP �\ GRATE INLET #002- PROPOSED PIPE No. 4- 50 L.F. - 18" 0 HDPE SLOPE = 1.0% PROPOSED JUNCTION BOX A-1- PROPOSED PIPE No. 5 5 L.F. - 18" 0 HDPE SLOPE = 1.0% EXISTING STORM DROP INLET A-0. LEAVE EXISTING STRUCTURE IN PLACE AND ADJUST RIM VERTICALLY TO MATCH FINISH GRADE. RIM = 486.10 EXISTING FL IN (SE) = 475.30 PROPOSED FL IN (N) = XXX.XX --= UGT -- EX 15" RCP EX DROP INLET TOP=488.2' INV. IN=482.3' INV. OUT=481.3' - / L \aa� / \ / / UG E- _ -UG E --- L 1S -�\: ��� / EX JBOX ►--4���5',RCP______ --- i =48 - / \\ INV. 1=475.3' - Cp ! / I ---------------- -------------_--------- ---; -485- _ ----f _�___ _ _____________ - - -= \ ` -- _ _ ��---- -7=21 EX MA HOLE NOT C3 / N \ I _---- _----S24 19' 26"W------//�----_ I FOUND_ _ \ ;UG BUG T- -UGT / --_ ---- T- _UC1�-UGT_-UCT UGT--UG TVV p�Ir/ RUC T� -UGT D � EX DROP INLET I EX GRATED DROP INLET TOP=487.1' TOP=484.3' INV. OUT (15" RCP)=481.4' INV. IN=475.8' I INV. OUT=475.7' I U. S. ROU TE 29 (SBL) SEMINOLE TRAIL (VARIABLE WID TH) 45-7G-i..V9'9 \ R8^�.A 45 81 0^ 5 S8 � i4576 3 I rn� a5 ry 4s.s9c y>M1eJ F4�\M1S o e u 451 1 45-85+ 45 84A+ vsF45-58C1 • � .� �r a°"r p2F hF\/ .:ry `'e 45Ei 04 t.-Ca rrsbrook_ 'e 45-7?. 45-IItiAt d 45--112 _ 5 ! 45-a fiA .45-08A 45-81 4561-01-m- ,roY. 45.-8aB 45-80 �s r1T2G �� � o� �p � e 45-90Aa 45-88 >�C, ss-TTse U. i p: 45 90 a d0'243 40 W o #5 -20 ;4ts, Ji �C 45-29A6 -91 �Brt `w� 45 k09E. 45 109 d� 45®i 01-DA-4gP0 w J 11t ,°sv+ Ra. P Y !S Agnor-Hurt e7�� c 45-9GA c i,.o Bi:arbd: i1'gC:!•45. 4 45-95 v,q roVK111 Ef=E. �I J-r: Ot OM' 10 QM 8 45-94;. 45-94A. r-c..aybrlp�, s i'W'�'odhrook �"°M,•.ss� 45. 27 was Y>o 4s 444t r� "deA�rQ T T IJ_ ry asc� s. 4 rye, 45-173 144- 1 � \��b5pi ,��:+0 ��� `3 r+ �,.:, k ❑ ` -., �; 4sc-na,00 noa d�+\ pJS,"�cJ RCA1 45-102A A`i 102b� 45-T06/ I �.,-10,4B5 b�r3.`ye> ^` M. b �'� /N 5..t1 p2_fi U U. Ue o rv'6 p, z 1 Rg'.l1i � ti? ° /.. h // /� �,24E3 � 5i121 �. 5 to 61-120 y� 1 4R51UVYfl11G/: ��YPaly�1 `p �`° 1 tM c t2 I 2e Or e� ,I it 2i1.�- LOCATION MAP SCALE: N.T.S. PROJECT NOTES: DEVELOPER: W4 Development 2500 Daniel's Bridge Road Building 200, Suite 3A Athens, GA 30606 Contact: Greg DeBacker Phone: (706) 548-1151 ENGINEER: Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 Contact: Jeff Carter, P.E. Tel. (770) 725-1200 jeff@carterengineering.net Property Location: 2100 Rio Hill Center, Charlottesville, Albermarle County, Virginia 22901 Parcel No.: #04500-00-00-093C0 Conditional Approval: ZMA 1987 - 00007 and SDP 1988- 00001 Current Zoning: PD-SC (Planned Development Shopping Center) Proposed Zoning: PD-SC (Planned Development Shopping Center) Setbacks: Front:40-feet Rear:20-feet Side: 15-feet Proposed use: Carwash with associated utilities and parking Proposed Building Height 20 Feet Project Tract 1.05 acres Disturbed Area 0.86 acres Boundary and topographical Information obtained from field run survey by Hurt & Proffitt dated April 30, 2019. Phone (434) 847-7796 Contour interval is 1 Feet (NAVD 88) F.E.M.A. Flood Insurance Rate Map No. 51003C 0278D, dated February 02, 2006 indicates that this property is located in "Zone X". The underground utilities shown hereon have been located from field information and existing drawings. The surveyor nor engineer warrants that the underground utilities shown comprise all such utilities in the area, either in service or abandoned. The surveyor nor engineer warrants that the underground utilities shown are in the exact location indicated. The surveyor nor engineer has physically located all the underground utilities. It is the responsibility of the contractor to field locate all utilities prior to commencing work and notify engineer if a discrepancy is found. The contractor shall verify the invert elevations of all existing storm and sanitary sewer structures prior to commencement of storm and sanitary sewer construction. UNDERGROUND UTILITIES DISCLAIMER Information regarding the reputed presence, size, character and location of existing underground utilities and structures related to underground utilities is shown heron. There is no certainty of the accuracy of this information and it shall be considered in that light by those using this drawing. The location and arrangement of underground utilities and structures related to underground utilities shown hereon may be inaccurate and utilities and structures related to underground utilities not shown may be encountered. The owner, his employees, his consultants and his contractors shall hereby distinctly understand that the surveyor is not responsible for the correctness or sufficiency of this information regarding the underground utilities and structures related to underground utilities shown hereon. v v Know what's below Cali before you dig dial 811 z O F F U a w V w W O 0 a J m Z -' Ln O a 0 O w = t .1 p,LTH o JAMES JI CARTERS U No, 41920 NAL CARTER ENGINEERING CONSULTANTS Carter Engineering Consultants, Inc. I 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 P: 770.725.1200 F: 770.725.1204 www.carterengineering.net V J z Q J a_ Z_ (D zLL W J J z 2> LU I:L w OO J ^^ 1..� �. Q p - W >LU U w J W Z LU 0 LU U J J W O �..0 0 0 � N PROJECT NAME: W4 DEVELOPMENT CHARLOTTESVILLE, VIRGINIA SHEETTITLE: GRADING AND DRAINING PLAN SHEET NUMBER: 5 PROJECT NUMBER: 19016W4D DATE: 07/05/19 TREE MANAGEMENT CALCULATIONS: GENERAL LANDSCAPE REQUIREMENTS: Street trees shall be planted with even spacing in a row within the public street ri ht-c -wa or adjacent to the public street ri ht-c -wa i not permitted therein b 9 f Y J P 9 f Yf p Y the Virginia Department of Transportation, and with the private street right-of-way. One (1) large street tree shall be required for every fifty (50) feet of street frontage, or portion thereof, if twenty-five (25) feet or more. Where permitted, one (1) medium tree shall be required for every forty (40) feet or road frontage, or portion thereof, if twenty (20) feet or more. If required street trees cannot be planted within the parking setback or within ten (10) feet of the street right-of-way due to sight distance, utility easements, or other conflicting requirements, then the planting strip shall be enlarged to accommodate the trees. If this requirement creates a hardship by causing the relocation of required parking spaces, then the additional planting area may be counted toward the interior landscaping requirement. Seminole Trail: (power lines present) 249.25 Linear Feet Large Trees Required: 6 Small Trees Required (249.25 / 40) Large Trees Provided: 6 Small Trees Provided Woodbrook Drive: 213.63 Linear Feet Large Trees Required: 4 Large Trees Required (213.63 / 50) Large Trees Provided: 4 Large Trees Provided Shrubs along public streets: When a parking area is located so that the parked cars will be visible from an off -site street the agent may required additonal planting of low street shrubs between the street and the parking area, subject to the following: 1. Shrubs shall be a minimum of twelve (12) inches in height when planted 2. Shrubs shall be in a single row planted five (5) feet on center. 3. The agent may authorize different landscaping designed to minimize the visual impact of the parking area. A hedge of evergreen shrubs planted no greater than five (5) feet on -center and being a minimum of 12" in height at time of planting has been proposed along Seminole Trail and Westbrook Drive. Parking Area Landscape Requirement An area of at least five (5) percent of the paved parking and vehicular circulation area shall be landscaped with trees or shrubs. Neither the areas of street trees and shrubs required by sections 32.7.9.5(d) and I nor shrubs planted between a parking area and a building on the site shall be counted toward the minimum area landscaped areas for a parking area. Vehicular Area: 19,842 Square Feet Landscape Area Required: 992.1 Square Feet (5%) Landscape Area Provided: 21,126 Square Feet (46%) The plant materials may be a mixture of shade trees and shrubs and shall include one (1) large or medium shade tree per ten (10) parking spaces or portion thereof, if five (5) spaces or more. Parking Spaces Provided: 29 Parking Spaces Trees Required: 3 Trees Required (29 / 10) Trees Provided: 3 Trees Provided Tree Canopy Requirements Each commercial or industrial use site shall have a tree canopy covering a minimum of ten (10) percent of the property. Tree Canopy Required: 4,578.7 Square Feet (10%) Tree Canopy Provided: 7,330 Square Feet (16%) Existing to Remain 4,291 Square Feet Canopy Area (4) 329 Shumard Oak 1,316 Square Feet Canopy Area (3) 366 Lacebark Elm 1,098 Square Feet Canopy Area (5) 125 Trident Maple 625 Square Feet Canopy Area PLANTING NOTES: 1. The contractor shall locate and verify all existing and new utility line locations prior to planting, and shall report any conflicts to the landscape architect. The contractor will be responsible for the protection of all underground utilities during the life of the project. 2. The contractor is responsible for repair of any damage incurred during the execution of work. 3. The contractor shall stake all tree locations in the field and the staked locations shall be reviewed and approved by Carter Engineering. Carter Engineering may make minor adjustments to the layout without incurring additional costs to the project. 4. Mulch all plant areas with 3" layer of double ground shredded hardwood mulch. 5. Any proposed substitutions of plant species will be with plants with equivalent overall form, height, branching habit, flower color, leaf color, fruit color, and time of bloom, as approved by Carter Engineering. 6. Substitutions shall not be made unless drawings and/or written requests are submitted to Carter Engineering for approval. Carter Engineering shall determine equality based upon complete information submitted b the contractor. P Y 7. Trees: provide specimen balled and burlapped, or as specified, trees of height, size, caliper, genus, species, cultivar and branching configuration indicated. The root system of each shall be well provided with fibrous roots. All parts of plant shall be moist and show active green cambium when cut. they shall be free of disease, insect pests, eggs or larvae. All plants to be moved balled and burlapped, must be moved with the root systems as solid units with balls of earth firmly wrapped with untreated burlap, firmly held in place by a stout cord or wire, drum laced, boxed, or in containers. 8. Pruning and shaping: prune, thin out, and shape plants in compliance with American Hort's 'American Standard for Nursery Stock' to preserve the natural character and only as approved by Carter Engineering design team. Retain required height and spread. Do not alter shape and do not cut leaders. Remove all dead wood, suckers, broken or bruised branches, and crossing branches. 9. Stakes and Guys: to be round cedar posts. 10. The Carter Engineering representative reserves the right to reject plant material at the nursery or at the site. 11. The trunk flare (at the base of the tree) shall be properly exposed for all plantings. 12. Keep root balls intact prior to and during planting operations. Plants with broken or damaged root balls shall be rejected and immediately removed from the site. Keep root balls damp and protected from damage due to sun and wind. Do not shave root balls. 13. Plant soil mixture will be used to backfill the planting area. Install plants simultaneous) with P 9 P Y installation of planting soil mixes. 14. Tree planting: see tree planting detail and notes herein for additional information related to P 9 P 9 planting pit dimensions, planting operations, backfilling, and tree staking. 15. Container stock planting: plant container grown stock the same as specified for balled and burlapped stock, but remove containers completely. 16. Soil shall be free of all debris, construction material, and slurry. Landscape areas shall be backfilled with planting soil mixture per details and specifications. 17. Obstructions: if obstructions or other conditions detrimental to healthy plant growth are encountered notifyCarter Engineering immediate) and request additional instructions. 9 9 Y q 18. Watering and drainage: fill excavations with water and allow water to percolate out before planting. If planting pits do not percolate or drain properly, notify the Carter Engineering and request additional instructions prior to planting. Do not plant into poorly draining planting pits; poorly draining planting its may hold water and drown plants. P Y 9P 9P Y 19. Flood all plants with water twice within the first 24 hours after planting. 20. All plant material shall be mulched after planting. Backflll to allow room for mulch after settling,and lace mulch in dish after first watering and within one week of planting. See P 9 P 9 planting details for mulch thickness. 21. All plants shall be plumb vertically after settling or as directed by Carter Engineering. 22. Planting restrictions: plant during one of the following periods. • Spring planting shrubs roundcover, perennials) March through May P 9P 9( ,9 .P ) 9 Y • Fall planting shrubs (shrubs, groundcover, perennials) - Sept. through November • Tree planting - September through April 23. Installer agrees to repair or replace plantings and accessories that fail in materials, workmanship or growth within 18-months of substantial completion. Failures include, but are not limited to: • Death and unsatisfactory growth, except for defects resulting from the lack of adequate maintenance by owner. • Structural failures including plantings falling or blowing over. 24. The contractor shall verify the quantities listed in the plant legend. Contractor is responsible for installing all plants shown on planting plans. In case of discrepancies Carter Engineering should be contacted. 25. All groundcover quantities shall be determined using the information provided in the groundcover quantity and spacing chart within the Landscape Drawing Set. GENERAL LANDSCAPE NOTES: 1. Landscaping shown on this plan shall be maintained in compliance with county and/or city landscape ordinance. 2. All disturbed ground shall have ground cover or mulch and/or grassing. 3. Trees selected for planting must be free from injury, pests, disease, nutritional disorders or root defects, and must be of good vigor, so as to assure a reasonable expectation of survivability. 4. Plants that are diseased, unsurvivably damaged or are dead shall be removed and replaced with a plant of the same species, variety, and cultivar, as acceptable to the code enforcement director. 5. Other landscape materials shall be maintained in proper repair and shall be kept clear of refuse and debris. 6. Arbor Tie or similar nylon tree strapping/guying material shall not be used in a way that will girdle tree trunks if left in place. 7. No trees or shrubs will be installed in the right-of-way on public roads or in the access and utility easements for private streets. GROUNDCOVER SPACING & QUANTITY PLANT SPACING PLANT SPACING MULTIPLIER (PLANTS PER SF) 12" 1.15 15" .74 18" .51 24" .29 Double Knockout Rose Rosa radtko • Densa' Inkberry Holly Dwarf Yaupon Holly Sod As Directed by Owner Ilex glabra 'Densa' Ilex vomitorio 'Stoke's Dwarf' Kanjiro' Camellia Peach Drift Rose Big Blue' Creeping Lilyturf Camellia sasanqua 'Kanjiro' E) Rosa 'Meiggil' Liriope muscari 'Big Blue' x > • 'PANACHE' SHUMARD OAK ALLEE LACEBARK ELM 'AERYN' TRIDENT MAPLE Quercus shumardii 'PanacheUlmus arvifolia 'Emer II' Acer buer erianum Aer n' Street Tree Parking Lot Tree Street Tree (Power Lines) LANDSCAPE SYMBOLS (1) ALLEE LACEBARK ELM (140 SF) 'BIG BLUE' CREEPING LILYTURF (5) DWARF YAUPON HOLLY (11) PEACH DRIFT ROSE (13)'DENSA' INKBERRY HOLLY y S PLANT SCHEDULE TOTAL BOTANICAL NAME COMMON NAME CAL./GAL. SPACING TYPE HT./SPR. REMARKS QTY MINIMUM CAN OPY TREES 4 Q uercusshumardii'Panache' Panache'Shumard Oak 2" Cal. As Shown B &B / S' Straight htCentral Leader to Min. Ht. Well Spaced Branches S g P mmetrical Crown Y 3 Ulm us parvifolia'Emerll'A/lee Emerll' Lacebark Elm 2" Cal. As Shown B&B 1 10'/5' Straight Central Leaderto Min. 6' Ht., Well Spaced Branches, Symmetrical Crown UNDERSTORY/FLOWERING TREES 6 Acerbuergerionum 'Aeryn' Aeryn' Trident Maple 2" Cal. As Shown B & B 10' / 5' Straight Central Leaderto Min. 6' Ht., Well Spaced Branches, Symmetrical Crown EVERGREEN SHRUBS 10 Comelliasasanqua'Kanjiro' Kanjiro' Ca mil la 7GaI. As Shown Container 36"/30" Full Pot, Well Shaped 58 Ilex glabra'Densa' Densa' I nkbe rry H ol I y 3GaI. As Shown Container 18"/ 18" Full Pot, Well Shaped 10 Ilex vomitoria'Stokes Dwarf' Stokes Dwarf' Yaupon Holly 3 Gal. As Shown Container 18"/ 18" Full Pot, Well Shaped DECIDUOUS SHRUBS 21 Rosa'Meiggil' Peach Drift Rose 3 Gal. As Shown Container 181./ 18.. Full Pot, Well Shaped 21 Rosa'Radtko' Double Knockout Rose 3 Gal. As Shown Container 18"/ 18" Full Pot, Well Shaped GROUNDCOVERS (in square feet) 835 Liriopemuscori'Big Blue' Big Blue' Lilyturf )Gal. 181,O.C. Container 1 12"/12" 1 Full Pot, Well Shaped I' g I TURF GRASS (in square feet) ' W I 8,655 Sod -as directed by owner ' m 1 GRATED, DROP- INLET U, TOP,-488.7' - -- INV. OUT =479.5' I Q !a O ' z -- V)- - ---r-1 ' - --- � wCt - T � FAIL /FIV� - _ 492 49 �49449 Sod - as directed by owner I SOD RIO HILL CENTER I I I 3 EXISTING SIGN EASEMENT I Are ♦ Ili , N24 18' 10"E 191.25 - - - L 49S _ _ NEW PROPOSED TREE LINE (TYPICAL) (6) 'KANJIRO'CAMELLIA I�I (3,060 SF) SOD - AS DIRECTED BY OWNER / QAK ° ` 4,291 SQUARE FEET EXISTING OAK AND I I I HARDWOOD CANOPY TO REMAIN i / ( L`X 240/ I I 3 I 1 7'_ LIMITS OF DISTURBANCE (TYPICAL) TREE PROTECTION FENCE (TYPICAL) '/ // II // 1 EXISTING TREE TO BE REMOVED (TYPICAL) I I I 4 / I \t (195 SF)'BIG BLUE' CREEPING LILYTURF / 93 E> 26'PI F_ �1R I \ / / / " I I / (3) DOUBLE KNOCKOUT ROSE (4)'PANACHE' SHUMARD OAK V'V SCT RIO HILL, LLC,\�1�g'KS C/O ROSENTHAL PROPERTIES / 492 / - _ - K - 'PA- I I TM# 04500-00-00-094AO / DB 4134, PG 199 - ; 492 \ / - - - - - - r,� (29)'DENSA' INKBERRY HOLLY L�. (5) DOUBLE KNOCKOUT ROSE l = L = 140.14' / - R = 990.77' ' ) \ C. = 140.02' / � I C.B. = S59'24'42"E PIN IU EXISTING ' / � 4 SANITARY ; �' 90 I �� • 1 EXISTING UTILITY EASEMENT EASEMENT ' / � . a I I X I I1 \ 5 DOUBLE KNOCKOUT ROSE 1 f o I r r _- / / li . I EX I%�g„ PINE 7 `6'65 M 6° 6'S6 6.96 655 55 B15 615 ��� � � ° • a S ! / 6.55 6'S6 6 6 I y i � �I I O fff �• I I ,(670 SF) SOD - • . - 1 Cr> 1 1!'� , I 9- w EX INV. OUT WITH FLARED h ' AS DIRECTED BY- - B ------ --- _ Iy 9 �J END SECTION=470.4' /� iq _ OWNER �' _ 1 - ___ Q N Z \ �/ ^EX 18'HOLL r •\ ° ,5 �'' 5�1_0W 00\J, 1 O \� 1 ALLEE LACEBARK ELM - 1 3 ra t yl�• s (190 SF)'BIG BLUE' CREEPING'LILYTURF / w- x 1 ALLEE LACEBARK ELM 110 SF SOD - AS DIRECTED BY OWN. - (= R ( , I y 200 SF 'BIG BLUE' CREEPING LILYTURF 2 'DEN A' INKBERRY HOLLY Y �/ O S L � ,`', \_I (175 SF) SOD - AS DIRECTED BY OWNER (1)'KANJIRO' CAMELLIA � � S � - � �;\- � �� ! I '� � � � � � •" • � _ (1)'KANJIRO' CAMELLIA C A _ EX (5) DOUBLE KNOCKOUT ROSE STORM (10)'DENSA' INKBERRY HOLLY I ' / (4)'DENSA' INKBERRY HOLLY (3) DOUBLE KNOCKOUT ROSE PROPOSED CARWASH ASH }, OSfj'BIG BLUE' CREEPING LILYTURF �, .''i�• - v,739 S.F. , � V. IN (5)DWA RF YAUPON HOLLY F.F.C. - XXXX.XX f NV. L (1) 'KANJIRO'CAMELLIA (10) PEACH DRIFT ROSE (1 AMELLIA 0' C ) 'KANJIR Ti I (6)'AERYN' TRIDENT MAPLE '---- / u z-w 40 - z"w z°w z,w z,W - rw - z..W - 2..W rw - -�- - -�- - -n- - -n- - - - - AS DIRE ITED BY Ep§$E `E T� / E � ` j4P❑HP OW E ❑HP LE N P r P - - pp e • DROP tNLT • UG E- - -UG E- ,. P=486.1' - 15 RCP _ NV. IN=475.3' ---- -- - --- - - ----- ----------- ---- --- on- JBOX _ _ _ II T ry INV OUT=474.1' l -- -- ---- I r on -- EX S24 19' 26"W 214.98 EX MANHOL NOT D FOUN G -UG T- - UG T.-- --UC _ -UG T- T� -UG / T , T D BUG -UG T- - -UG T- -UG T- ' UG D I D D M -uc T D D p p lA p p p D p p D p D p p D p uk p V p D Dp p 110 EX DROP INLET I EX GRATED DROP INLET TOP=487.1' TOP=484.3' INV. OUT (15" RCP)=481.4' INV. IN=475.8' I INV. OUT=475.7' I U. S. ROU TE 29 (SBL) SEMINOLE TRAIL (VARIABLE WID TH) ) Know what's below Call before you dig ��� dial811 45-7 Q -&GA,` 45-asA 45-86 45-88e y 45-90Aa 45 88 '10 90 - f -C 45 #5-28 45 -91 `y7`9 45-29A6 R: w �'y 9 C a 95AJno !Hurt i 45 2FA 45 95 45-9 45 27 I?S rr> M1s 44A1 .QUO 0 - '- 41�o-ry 4.5-94H a;19, a„ 4 45 t 09 r s � � -102A A`i-102b 45-ti y�/ re � e �'o Nareh j8e'�.rp'I 4i 2 Libra, ,; > ItuQv 84 -, 20 y' 1 ARStU U 7A re 6 Mn PROJECT NOTES: s r`'e 45Bt 04 ,.-Ca resbrolok- � �es@ 45--112 _ 5 45-68A :L � 4581-04-0B-, f2G V o- c1 R o 0 4 _MA +`u"vB'odurook Ls �, J Np I t24E3 ,� �F+�._�6T-t24E6 e ie- 1Es i m&8 LOCATION MAP SCALE: N.T.S. 5,zs1 DEVELOPER: W4 Development 2500 Daniel's Bridge Road Building 200, Suite 3A Athens, GA 30606 Contact: Greg DeBacker Phone: (706) 548-1151 ENGINEER: Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 Contact: Jeff Carter, P.E. Tel. (770) 725-1200 jeff@carterengineering.net Property Location: 2100 Rio Hill Center, Charlottesville, Albermarle County, Virginia 22901 Parcel No.: #04500-00-00-093CO Conditional Approval: ZMA 1987 - 00007 and SDP 1988- 00001 Current Zoning: PD-SC (Planned Development Shopping Center) Proposed Zoning: PD-SC (Planned Development Shopping Center) Setbacks: Front:40-feet Rear: 20-feet Side: 15-feet Proposed use: Carwash with associated utilities and parking Proposed Building Height 20 Feet Project Tract 1.05 acres Disturbed Area 0.86 acres Boundary and topographical Information obtained from field run survey by Hurt & Proffitt dated April 30, 2019. Phone (434) 847-7796 Contour interval is 1 Feet (NAVD 88) F.E.M.A. Flood Insurance Rate Map No. 51003C 0278D, dated February 02, 2006 indicates that this property is located in "Zone X". The underground utilities shown hereon have been located from field information and existing drawings. The surveyor nor engineer warrants tha t the underground utilities shown comprise all such utilities in the area, either in service or abandoned. The surveyor nor engineer warrants that the underground utilities shown are in the exact location indicated. The surveyor nor engineer has physically located all the underground utilities. It is the responsibility of the contractor to field locate all utilities prior to commencing work and notify engineer if a discrepancy is found. The contractor shall verify the invert elevations of all existing storm and sanitary sewer structures prior to commencement of storm and sanitary sewer construction. UNDERGROUND UTILITIES DISCLAIMER Information regarding the reputed presence, size, character and location of existing underground utilities and structures related to underground utilities is shown heron. There is no certainty of the accuracy of this information and it shall be considered in that light b those using this drawin . Th location g y g g e l cat on and arrangement of underground utilities and structures related to underground utilities shown hereon may be inaccurate and utilities and structures related to underground ound Y g utilities not shown may be encountered. The owner, his employees, his consultants and his contractors shall herebydistinct) understand that h y d t a the surveyor is not responsible for the correctness or sufficiency of this information regarding the underground utilities and structures related to underground utilities shown hereon. PARKING DATA Parking Required: Requirement: One (1) space per each one hundred (100) square feet of retail sales area for the first five thousand (5,000) square feet and one (1) space per each two hundred (200) square feet of retail sales area above five thousand(5,000) s uare feet. For purposes o this paragraph, 'retail f p f p p f P 9 p, sales orea'shall be deemed to be (1) eighty (80) percent of the gross floor 2 t the request o the applicant, the actual retail sales floor area; or (J a e q f pp f area as shown on floor plans submitted by the applicant delineating the actual retail sales area, which plans shall be binding as to the maximum retail sales area used. Retail Sales Area = 3,739 Square Feet of Building = 2,991 Square Feet (80%) Required Parking = 29 Parking Spaces Required (2,991 / 100) Provided Parking = 29 Parking Spaces Provided Handicap Parking = 2 Provided (2 Required) SITE DATA Site Information: Total Tract Area = 45,787 sf 1.05 ac (100.00%) Existing Impervious Area = 19,002 sf 0.44 ac (43.62%) Existing Landscape Area = 26,785 sf 0.61 ac (56.38%) Total Impervious Coverage = 24,661 sf 0.57 ac (53.86%) Structure Coverage = 3,739 sf 0.09 ac (08.17%) Vehicular Coverage = 19,842 sf 0.46 ac (43.34%) Pedestrian Coverage = 1,080 sf 0.02 ac (02.35%) Proposed Landscape Area = 21,126 sf 0.48 ac (46.14%) Total Coverage Area = 24,661 sf 0.57 ac (53.86%) Z O F F U a w Y = U w W p 0 Q J ca a, Z O at� Ln w PLTH ED JAMES JI CARTERS U No, 41920 NAL CARTER ENGINEERING CONSULTANTS Carter Engineering Consultants, Inc. 3651 Mars Hill Road, Suite 2000 Watkinsville, GA 30677 P: 770.725.1200 F: 770.725.1204 www.carterengineering.net z Qa J Z 1 oC z> Ww J z 5> J UJ w 5 O C) J 0 J u O LUU > w W Z LU 0 U J J W V = p O O LU N 1 V / PROJECT NAME: W4 DEVELOPMENT CHARLOTTESVILLE, VIRGINIA SHEETTITLE: LANDSCAPE PLAN SHEET NUMBER: 12 PROJECT NUMBER: 19016W4D DATE: 07/05/19