HomeMy WebLinkAboutSDP201900063 Review Comments Final Site Plan and Comps. 2019-12-23County of Albemarle Department of Community Development Memarandnm To: Justin Shimp, P.E. (justin(iDshimp-en ing eering com) From: Andy Reitelbach, Senior Planner Division: Planning Services Date: December 23, 2019 Subject: SDP2019-00063 — Pantops Corner Self -Storage — Final Site Plan The Planner for the Planning Services Division of the Albemarle County Department of Community Development will recommend approval of the plan referred to above when the following items have been satisfactorily addressed. (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.) [Each comment is preceded by the applicable reference to the Albemarle County Code.] New Comments — First Review of Pantops Corner Self -Storage Final Site Plan (SDP2019-00063): 1. [General Comment] This parcel is potentially within the Monticello Viewshed. It is recommended that you contact Liz Russell at Monticello to discuss this project if you have not already done so. 2. [General Comment] Provide the site plan application number for this project, SDP2019-00063. 3. [General Comment] Delete sheet C 12 from the sheet index if not proposed to be included. 4. [General Comment] Revise the boundary layout and existing conditions sheets to include the recently approved SUB2019-00059 and SUB2019-00129, including new property lines and all easements. 5. [General Comment] Reference SDP2018-00089 on the revised conditions sheet, as the road, including the sidewalk, and the street trees are being provided with this site plan. 6. [4.20] The last part of the note about stepbacks on the cover sheet appears to have been cut off. Provide the entirety of the note. 7. [32.5.2(a)] Include on the cover sheet that portions of this property are located within a state dam break inundation zone. 8. [32.5.2(a)] Include on the cover sheet that this property is located within the ACSA jurisdictional area. 9. [4.15] Remove the proposed monument signs from all sheets on which they are shown. Signs are approved through a separate application and process. 10. [35.5.2(n)] Provide a stop sign at the exit of the parking lot onto Pantops Corner Way. 11. [30.7] The retaining walls at the rear of the property must be stepped in accordance with the Steep Slopes — Managed overlay district, where no retaining wall can be over 6 feet in height. 12. [32.5.2(n); SUB2019-000591 The retaining wall at the southwestern corner of the building should not be in the 7' parking easement. Otherwise, provide documentation permitting such improvements in this easement. 13. [General Comment] Provide construction easements for the western side of the property where the retaining walls are proposed to go, or demonstrate that construction and grading can occur on the subject property. 14. [32.5.2(a)] The site plan indicates that there is an I V landscaping strip on the southern side of the property. However, there is another note indicating a 10' setback with the property line. Clarify this apparent discrepancy. 15. [32.5.2(a)] The northeastern corner of the building, closest to the entrance, appears to barely cross the minimum front setback line. Revise. 16. [32.5.2(i)] The retaining wall at the northern end of the property needs to be removed from the Pantops Corner Way access easement. Otherwise, provide documentation demonstrating that this retaining wall is permitted within the easement boundaries. 17. [32.7.91 Identify the dashed line depicted between the north end of the parking lot and the curved retaining wall. 18. [32.7.9 The tulip poplar at the southwestern corner of the building should not be in the 7' parking easement and needs to be removed. Otherwise, provide documentation permitting such landscaping in this easement. 19. [32.7.91 Provide the street landscaping calculations on the landscape plan. Some of this landscaping may be provided by SDP2018-00089. If so, reference what is being provided by that site plan. 20. [32.7.91 The site area under required landscaping (tree canopy required) does not match what is stated on the cover sheet. Clarify this discrepancy. 21. [32.7.91 Remove the northern bayberry and mountain pieris from the canopy total. Any vegetation 5 feet or less in height at 10-year maturity cannot be counted toward total canopy square footage. Comments from SDP2019-00008 — Pantops Corner Self -Storage Initial Site Plan Action Letter: The original comments from the review and action letter for SDP2019-00008 are in gray font. Follow-up comments from the review of the final site plan, SDP2019-00063, are in bolded black font. Please address these follow-up comments as well. [32.4.2.1 (f)] The mailing notification fee of $215.00 has not been paid. The fee must be paid prior to Friday, April 19', in order for the initial site plan to be approved. Comment addressed. 2. [ARB] Please see the attached ARB comment letter for items that must be addressed prior to initial site plan approval. Although the initial site plan will be approved, all comments from the ARB must be addressed prior to approval of the final 2 ARB approval required before approval of the final site plan can be granted. 3. [Fire & Rescue] Please see attached comments from Shawn Maddox. Please revise the plans so that Fire & Rescue comments are satisfactorily addressed. A fire access lane of 26' in width is required at the front of the structure, and Pantops Corner Way cannot be used for this access. Please see the attached comments and email from Shawn Maddox of ACFR regarding this item. Approval from Albemarle County Fire -Rescue (ACFR) required before approval of the final site plan can be granted. 4. [32.5.1 (c)] Please show all existing utility easements on the drawings. Include a label or call out for each easement stating whether the easement is public or private, the owner of record and the recorded instrument number, and easement width where existing easements are visible on the plans. Provide the deed book and page numbers of the utility easements from the recently recorded easement plat, SUB2019-00059. 132.5.2 (a) and 4.20 (a)] Please amend the building setback notes on Sheet 1 as follows: a. Minimum front setback = 10 feet from the right-of-way or the exterior edge of the sidewalk if the sidewalk is outside of the right-of-way. b. Maximum front setback = 30 feet from the right-of-way or the exterior edge of the sidewalk if the sidewalk is outside of the right-of-way. Comment addressed. 6. 132.5.2 (a) and 4.20 (a)] Please state the required off-street parking and loading setbacks on Sheet 1. a. Minimum off-street parking/loading front setback = 10 feet from any public street right-of-way. Comment addressed. 7. 132.5.2 (a)] Please show and label all minimum and maximum setback lines of the final site plan site layout drawings. The setbacks should be shown in accordance with Section 4.20 of the Zoning Ordinance. Comment addressed. [32.5.2 (a)] Boundary line adjustment plats were recently approved for these parcels. Please show and label all existing parcel boundaries with dimensions on the final site plan, and update the deed book and page numbers of the recorded instruments on the plans and the site data table on Sheet 1. Include all revised acreage on Sheet 1. In addition, it appears that another boundary line adjustment plat will need to be approved and recorded prior to the approval of this plan for the shared property line with the adjacent Wawa parcel. Revise this site plan with the new parcel boundaries and legal references from the approved BLA plat, SUB2019-000129, including on the site layout sheets and in the source of title note on the cover sheet. 9. [General Comment] Because this project involves improvements that are located on other parcels, these other parcel numbers and the site information data for these parcels should also be included. (Parcels 78-58G1 and 78-5A). Revise with the appropriate information from the new parcel boundaries of 78-58G1 and 78-5A. 10. [General Comment] A public access easement will be required to be recorded for Pantops Corner Way prior to the approval of this site plan. Please be aware that the required access easement crosses into TMP 78-58C, as shown on this plan, so that property owner will also need to be included in the easement recordation. Comment addressed. 11. [General Comment] The road plans and the final site plan for Pantops Corner/Pantops Corner Way must be approved before the final site plan for this site can be approved. In addition, the final site plan for the Wawa on TMP 78-58A may have to be approved prior to this final site plan, depending on the chronology of BLA, easement, and site plan approvals. The final site plan for SDP2018-00089, Pantops Corner, will have to be approved prior to approval of this site plan. Road plans have already been approved. 12. [General Comment] The Existing Conditions sheets may have to change depending on what the approved final site plans for Pantops Corner Way and Pantops Corner (hotel site) show. Revise this sheet to depict the new existing conditions based on approval of SUB2019-00059 and SUB2019-00129. 13. [General Comment] The Existing Conditions sheet, sheet 4, shows trees and sidewalk being demolished on parcel 5E to construct the entrance for the proposed self -storage use. Because these improvements are required by the site plan for Pantops Corner (SDP2018-00089), an LOR will be required for SDP2018-00089 to remove these items from that site plan once the self -storage project moves forward. Comment no longer applies. 14. 132.5.2 (a)] Please add the full Action Letter, Proffer Statement, and associated exhibits approved with ZMA2013-02 to the final site plan drawings. a. State the ZMA approval date by the Board of Supervisors — December 11, 2013 Comment addressed. 15. [32.5.2 (a)] Please state that TMP 78-58G1 lies within the FH, Flood Hazard Overlay District on Sheet 1 under "Zoning." Comment still applies. 16. [32.5.2 (a)] Please state that portions of TMP 78-58G1 lie within the Managed and Preserved Steep Slopes Overlay District under "Zoning" on Sheet 1. Please state that portions of TMP 78-5E lie within the Managed Steep Slopes Overlay District under "Zoning" on Sheet 1. Comment still applies, though it appears no portions of 78-58G1 lie within the Managed Steep Slopes overlay district. 17. [32.5.2 (a)] Revise sheet 2 to show the temporary construction easement that is shown on the approved BLA plat for SUB2019-00002, between revised parcels 5E and 5C, leading toward 5F. Comment still applies. 18. [32.5.2 (a)] Revise the Source of Title section with the most recent recorded plat and deed information. Comment still applies, as easement and boundary line adjustment plats have recently been approved for this property. 19. [32.5.2 (b)] Revise the proposed use of this site on the cover sheet to "Light Warehousing," as that is how this use is defined in the Zoning Ordinance. Revise the proposed use of this site on the cover sheet to "Self-service storage facility." The "Definitions" section of the zoning ordinance (Section 3) has been amended by the Board since the initial site plan was reviewed. 20. 132.5.2 (b)] Please state the gross square footage of each proposed structure, and proposed acreage of each use on the final site plan, as this site plan is incorporating TMP 78-58G1 and TMP 78-5A, in addition to 78-58E. Comment addressed. 21. 132.5.2 (b)] Sheet 5 of the plan states that there are "16 spaces" in the building. Clarify what these 16 spaces are. Are they indoor parking spaces, storage spaces, or some other type of space? Comment addressed. 22. [4.12.7] Light warehousing is an unscheduled use in the parking section of the zoning ordinance. As such, the Zoning Administrator shall determine the required number of parking spaces for this use. Please submit a request to the Zoning Administrator for a determination on the number of parking spaces required by this light warehousing use. Comment not addressed. Please submit a request to the Zoning Administrator for a determination on the number of parking spaces required by this use. 23. [32.5.2 (h)] Please show the boundaries of the FH Flood Hazard Overlay District and the state dam break inundation zone on 4 TMP 78-58G1 where visible on the plans. Provide a label and include this feature in the legend. Comment not addressed. 24. [32.5.2 (b)] No loading spaces are shown on the site plan. Loading spaces shall be provided in accordance with Section 18- 4.12.13. These loading spaces must meet the design standards specified in Section 18-4.12.18 of the Zoning Ordinance. Comment not addressed. 25. [32.5.2 (b)] No dumpsters are shown on the plan. In accordance with Section 18-4.12.13(e), dumpster pads must be provided on this parcel. Comment not addressed. 26. [4.12.19 and 32.7.9.7 (a)(3)] Please provide a profile view detail with dimensions and materials of the dumpster pad enclosure to verify compliance with the screening requirements contained in the Zoning Ordinance. Please note that fences or other constructed screening measures must be a minimum of six feet (6') in height, as specified in 32.7.9.7 (e). Comment not addressed. 27. 132.7.3 (b)] Please show the locations of all proposed mechanical equipment and utility hardware. Please provide information so that the agent can verify they will be screened from public view. Comment addressed. 28. [32.5.2(i)] After it is recorded, please provide the deed book and page numbers for the access easement across Pantops Corner N, Comment not addressed, easement plat and boundary line adjustment plats have now been approved, and deed book and page numbers need to be provided. 29. [32.5.2(i)] Provide the width of the sidewalk along Pantops Corner Way. Indicate what portions of the sidewalk are existing, and what portions of the sidewalk are to be constructed with this site plan. Reference SDP2018-00089 30. [32.5.2 (m)] Show the distance to the nearest existing street intersection from the proposed ingress and egress. Comment not addressed. 31. [32.5.2 (n)] Provide the maximum footprint of the proposed building. Comment addressed. 32. [32.5.2 (n)] The site plan states that the square footage for each of the four floors above ground -level are the same size. However, at least the fourth floor, and maybe the third depending on building height, will have to be stepped back to meet the stepback requirement. Thus, this floor will be a smaller area than the lower floors are. Revise the square footage of the building, on both sheets 1 and 5, to take the reduced size of this stepped back floor into account. Provide the proposed height of the structure at the front facade, because it will need a stepback if it is 40 feet or more in height. 33. [32.5.2(a)] Show on the site plan where the proposed stepback for this structure will occur. A stepback will be required along the entire frontage of this building, as determined by Zoning, once the height of the building reaches the height requirements for stepbacks as described in section 4.20 of Chapter 18 of the Zoning Ordinance. Comment addressed if proposed building height less than 40 feet. 34. [32.5.2 (n)] Pedestrian crosswalks and accessible ramps must be provided at all locations within the site where ramps connect sidewalks on opposite sides of vehicular travel ways and streets. a. Please label the dimensions and surface materials in compliance with the County's design standards. b. There are several crosswalks across Pantops Corner Way where ramps are needed. c. In addition, provide ramps and a crosswalk at the entrance to this site, from Pantops Corner Way. d. The sidewalk along Pantops Corner Way near the entrance to this site also needs to be shown extending fully to the entrance to this site. It appears that the sidewalk was removed as apart of the demolition process for this project, but was not fully replaced with the proposed improvements shown on sheet 5. e. There also need to be ramps on the sidewalks directly adjacent to the building, leading from the parking lot to the office location. Comments addressed. 35. [32.5.2 (k)] Please label all existing and proposed sewer and drainage easements by type and include a size/width measurement. For existing easements, state the deed book and page of the recorded instrument. Provide legal references from recently recorded plats. 36. [32.5.2 (1)] Please label all existing and proposed utility easements by type and include a size/width measurement. For existing easements, state the deed book and page of the recorded instrument. Provide legal references from recently recorded plats. 37. 132.5.2 (n)] Please state the proposed surface materials for all parking lots, travel ways, walkways, etc. in a label on the site plan drawings. Comment addressed. 38. [32.5.2 (n)] Identify the narrow hatched area adjacent to the north side of the building. Is this a proposed loading area, a marked accessible way between the sidewalks, or some other improvement? Comment not addressed. 39. [32.5.2 (n)] Please state the height of all proposed fences and retaining walls in the labels used on the drawings. Profile view details of all proposed fences, retaining walls, and constructed screening measures will be required with the final site plan. Each will need to show the types of materials used and dimensions. In addition, safety railings will be needed between the parking lot and the adjacent retaining walls. Comment not fully addressed. 40. 132.5.2 (e)] Please provide more details about the existing landscape features as described in Section 18-32.7.9.4(c). a. The Albemarle County Conservation Plan Checklist and Chapter 3.38 of the Virginia Erosion and Sediment Control handbook. The Conservation Plan Checklist will need to be signed by the owners and provided as an exhibit on the final site plan. Comments addressed. 41. [32.7.2.31 Please ensure sidewalks and landscaping strips are provided along Pantops Corner Way. These items will likely be included in the Pantops Corner final site plan and road plans. However, please be sure that everything shown on this plan exactly matches what is shown in the approved road and final site plans for Pantops Corner. Comment still applies until SDP2018-00089 is granted final approval, ensuring these elements are included. 42. [32.7.9] A full landscape plan will need to be included in the submission of the final site plan. In addition to interior landscaping, the street landscaping for this site will need to match the landscaping that is shown on the final site plan for Pantops Corner (hotel site) and associated road plans. Landscaping will also need to be approved by the ARB. a. 132.7.9.91 In the landscape plans, include a note stating that "all landscaping shall be installed by the first planting season following the issuance of the first certificate of occupancy within the development." b. [32.7.9.91 Add a note to the landscape plans stating, "All landscaping and screening shall be maintained in a healthy condition by the current owner or a property owners' association, and replaced when necessary. Replacement material shall comply with the final site plan approved landscape plan." Comments not addressed. 43. 132.7.8 and 4.17] The final site plan lighting plan must meet the minimum requirements of Section 4.17 of the Zoning Ordinance. a. [4.17.4] Please provide a luminaire schedule stating the quantity of each outdoor luminaire proposed, the model number, the fixture type, wattage emission, etc. 6 b. 14.17.4 (a)] Please provide documentation from the manufacturer that all proposed outdoor luminaries exceeding 3,000 lumens are full -cutoff fixtures. c. Please state the pole height of all outdoor luminaires. d. [4.17.4 (b)] Please show foot-candle measurements within the development and along all existing and proposed street right of ways and property boundaries. The spillover of lighting from luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one-half (%2) foot candle. e. Please add a note to the lighting plan which states, "Each outdoor luminaire equipped with a lamp that emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away from adjoining residential districts and adjacent roads. The spillover of lighting from luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one-half footcandle." Comments addressed. 44. 132.6.2 (d) and Chapter 141 Please submit an easement plat and application to the County that shows all new easements proposed by the site plan. This includes all new drainage, stormwater, public access easements, etc. The easement plat must be reviewed, approved, and recorded prior to approval of the final site plan. Comment addressed. 45. [ZMA201300002, 14-234 (E), 14-317, and 14-422 (C)] As part of the easement plat application, a public access easement will need to be platted over the Pantops Corner Way and Road B private street right-of-ways. A private street maintenance agreement will need to be approved by the County Attorney and recorded with the easement plat. As required by Proffer #1 of ZMA2013-02, an access easement shall be provided subject to an agreement between the respective property owners to share the cost of maintenance and construction for shared portions of the private road. A template for private street maintenance agreement can be found on the CDD website. Comment addressed. 46. [32.6.2 (h)] Please provide a signature panel with a line for each member of the Site Review Committee. Comment addressed. 47. [32.5.2(i)] Provide the right-of-way width for State Route 20, as well as the width of the access easement on Pantops Corner Way and the edge -to -edge pavement width for Pantops Corner Way. Comment addressed. 48. [32.5.2(i)] Identification of public access easement along the proposed Pantops Corner Way must be shown on the site plan. Provide deed book and page number for recorded easement plat SUB2019-00059 and associated deeds and covenants. Please contact Andy Reitelbach in the Department of Community Development at areitelbach(c-r�,albemarle.org or 434- 296-5832 ext. 3261 for further information. Comments from Other Reviewers: Albemarle County Engineering Services (Engineer) — John Anderson, janderson2(kalbemarle.org_— Requested changes; please see the attached memo. Albemarle County Information Services (E911) — Andy Slack, aslack(c�r�,albemarle.org — No objections at this time. Albemarle County Building Inspections — Michael Dellinger, mdellingergalbemarle.org — No objections at this time. Albemarle County Architectural Review Board (ARB) — Margaret Maliszewski, mmaliszewskigalbemarle.org — Requested Changes; please see the comments below: An ARB resubmittal of both site and architectural drawings is required for staff review. Address all issues listed in the July 16, 2019 ARB action letter. Albemarle County Fire -Rescue (ACFR) Shawn Maddox, smaddox@albemarle.org — Requested changes; please see the comments below: 1. FDC must be shown on the plan and located within 100' of a hydrant. The hydrant being used for the FDC should not require the traffic on Pantops Corner Way to be impeded by its use. 2. A Knox Box is required. Please add a note indicating this requirement and that the location can be coordinated with the fire marshal's office. 3. The fire lane should be marked due to the limited access to the site. 4. Provide the ISO needed fire flow for the structure and also provide the available fire flow on the site. Albemarle County Service Authority (ACSA) — Richard Nelson, rnelson@serviceauthority.org — Requested changes; please see the comments below: Show water meter. Provide fixture counts. Virginia Department of Transportation (VDOT) — Adam Moore, Adam.Moore@_ydot.vir ig nia.gov —No objections at this time; please see the attached memo. COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, Room 227 Charlottesville, Virginia 22902-4596 Phone (434) 296-5832 Fax (434) 972-4126 Site Plan Review Project title: Pantops Corner Self Storage — Final Site Plan (FSP) Project file number: SDP201900063 Plan preparer: Justin Shimp, Shimp Engineering, 912 E. High Street Charlottesville, VA 22902 f iustin(a,shimp-engineering com] Owner or Rep: Pantops Corner LC, 12704 Crimson Court, Suite 101, Henrico,VA 23233 Applicant: Landstriker LLC, 250 W. Main St. Suite 201, Charlottesville, VA 22902 Plan received date: 6 Nov 2019 Date of comments: 26 Nov 2019 Plan Coordinator: Andy Reitelbach Reviewer: John Anderson SDP201900063 — Engineering Initial Site Plan review comments, below. New FSP review comments begin with item 34. ISP201900008, items L-33.: If grayscale, ISP comment addressed, NA, or withdrawn with FSP submittal. If normal text, ISP comment persists as a Final Site Plan (FSP) comment. Sheet 1 (Title Sheet) 1. Include ref. to WP0201800088 plan title (VSMP Major Amendment Plan for Pantops Corner), and narrative explaining this ISP's reliance on this plan for meeting state stormwater quality and quantity regulations. (FSP) Persists. 2. Include ref. to SUB201900024 plan title (Road Plan for Pantops Corner) and narrative explaining this ISP's reliance on this plan for design details for a private road offering public access between U.S. Rt. 250 (Richmond Road) and SR 20 (Stoney Point Road), required by ZMA 2013-00002 Interconnectivity proffer (# 1). (FSP) Persists. 3. Label "Road A" on this plan set (ref. Interconnectivity proffer). (FSP) Withdrawn. 4. Final site plan approval requires SUB201900024 approval, and that this p.i-,,at, read be built of beaded between U.S. 250 and SR20 (FSP) Road Plan approved 9/6/19. Note: Road Plan does not require bond. 5. Final site plan approval requires WP0201800088 approval. (FSP) WPO Plan approved 7/23/19. 6. In addition, all three plans, SDP201900008, SUB241900024, WP0201800088 must be consistent with one another. If design values change, for example, drainage on the road plan or impervious area (land use schedule) on the site plan, plans should be updated since storm runoff from three separately developed sites (Wawa, hotel, self -storage) are to be covered under WP0201800088, and since SDP201800089 (Pantops Corner hotel), SDP201900008 (self -storage), and SDP201900013 (Wawa at Pantops) rely on /require road plan design be approved with SUB201900024 (Road Plan for Pantops Corner). (FSP) Persists. Comment remains as reminder to ensure consistency across plans. No revision required; urge care when revising. It is our understanding an overall plan (.DWG) helps ensure consistency, that change to design updates related /affected plans. 7. Revise Flood Zone notation to ref. FEMA Flood Insurance Rate Map, eff. date of 5/16/1 (FSP) Withdrawn. Engineering Review Comments Page 2 of 3 Note: A CO for Pantops Corner Self -Storage will not be issued until Rt. 20 widening is complete. Design for this widening should be shown on Road Plans for Pantops Corner. To reiterate, Road plan approval is prerequisite for final site plan approval for Pantops Corner Self -Storage. Ref. ZMA 2013-00002, Proffer 3. (FSP) Withdrawn. Steep Slopes: label preserved and managed steep slopes on C3 and C4. A note on the title sheet is insufficient. (FSP) Persists. As follow-up: Label managed steep slopes on sheet C3, and show and label managed steep slopes on the Grading Plan (C6). Sheet 2 10. This sheet is confusing. If submitted as an exhibit, please re -title this sheet. Boundary Line Adjustments require separate application, file number assignment, and review and approval. Engineering reserves right to comment on a BLA application, once application plat is received. (FSP) NA. 11. Long dash -box line -type is not defined. Provide legend and include this line -type. If feature designated by this line -type has no bearing on boundary line adjustment, please remove. (FSP) NA. Sheet3 12. Label features; for example: relic sediment basin, active sediment basin (with Ref. to WPO#), existing or relic temporary construction access. (FSP) NA. 13. Label managed and preserved steep slopes. (FSP) Persists. Asfollow-up: Label managed steep slopes on sheet C3, and show and label managed steep slopes on the Grading Plan (C6). 14. Boundary of (existing conditions) TMP #78-5E does not match county real estate records. Show existing boundaries. If boundaries are to be revised, pursue revision via normal BLA process. (FSP) NA. 15. Sheet 4: Unless a salient feature, recommend remove long dash -box line -type. Also, item 11, above. (FSP) NA. Sheet 5 (Site Plan): 16. With ISP, label all parking lot internal radii. 17. Provide CG-12 on south side of site entrance. (FSP) Persists. Asfollow-up: Review /revise detectable surface /ramp configuration on south side of site entrance to align with detectable surface /ramp on north side. Angling ramp and detectable surface into Pantops Corner Way is unacceptable. Align with (crosswalk) direction of pedestrian travel. 18. Provide receiving CG-12 ramp on north side of entrance. 19. Provide pedestrian crosswalk striping at entrance. Provide striping detail. (FSP) NA. Request for striping detail withdrawn. 20. With FSP, label entrance with VDOT designation (CG-9a, for example). (FSP) Persists. 21. For FSP, compare design with Final Site Plan checklist, available on county website. 22. For FSP, compare design with Drainage Plan checklist, and provide complete drainage design. 23. For FSP, provide structural retaining wall design, not generic manufacturer's design; ref. Final Site Plan checklist, page 11, Grading, Retaining Wall Plans checklist. RW checklist attached. 24. For ISP, provide Landscape Schedule [18-32.5.2.p.]. Ensure proposed plantings in the —2.5' space between base of 10' high retaining wall and adjacent parcel to the west work, and are anticipated to thrive. (FSP) Withdrawn. Engineering defers to Planning on landscaping. 25. Check proposed contours between contour (labeled) 90 and south end of 10' retaining wall. Proposed contours may be missing. 26. Provide retaining wall easement. (FSP) Withdrawn. 27. Acquire temporary construction easement, if needed, to construct proposed retaining wall. (FSP) Withdrawn. 28. With FSP, provide refined contours on south side of proposed self storage building. Provide flow lines to indicate path of surface runoff. (FSP) Partially addressed. As follow-up: see item 35, below. 29. Show and connect roof leader lines with storm conveyance system. Engineering Review Comments Page 3 of 3 30. Prepare a private road maintenance agreement between Wawa, Pantops Corner hotel, and self -storage development for Planning Division review. (FSP) NA. Engineering defers to Planning. 31. With FSP, provide necessary typical civil details. 32. Please consider Sec. 18-32.6.2., Contents of a Final Site Plan, for design elements, calculations, etcetera. 33. Notes: a. An approved VSMP Plan Amendment is required prior to Final Site Plan approval. (FSP) WPO Plan approved 7/23/19. b. Please consider attached Final Site Plan, Drainage, and Retaining Wall plan checklists as aids to design. Checklists guide review. ADMIONAL Final Site Plan comments: 34. C2 — There appears slight line break in NE corner of TMP 78-5F. Please revise as needed. 35. C6 — Remove 7' parking easement linework. 36. C5 — Label sidewalk width fronting Pantops Corner Way. 37. Include VDOT Mill -pave detail showing mill /pave work to center of Pantops Corner Way. Alternatively, amend SUB201900024 by letter and full-size print plan sheet/s showing commercial entrance for Pantops Corner Self -Storage built with the Road Plan (with Pantops Corner Way). This would require Road Plan (Amendment) Application, fee, and Planning /VDOT /Engineering review. Albemarle has no preference, but given stage of road construction, in appears a reasonable alternative to construct curb /gutter and self - storage entrance with SUB201900024, rather than build curb/gutter, place surface asphalt, then demolish these sections, including asphalt to road centerline, in order to effect continuous asphalt (at self -storage) entrance. Road pavement will perform better if Pantops Corner Self -Storage entrance is constructed with Pantops Corner Way. Albemarle will insist on mill -pave to centerline of Pantops Corner Way, consistent with VDOT std. /specifications, if entrance requires demolition of asphalt surface pavement at curb line. Please feel free to call if any questions. Thank you J. Anderson 434.296-5832 -0069 SDP201900063 Pantops Corner Self -Storage FSP 112619 COMMONWEALTH of VIRGINIA DEPARTMENT OF TRANSPORTATION 1601 Orange Road Culpeper. Virgin a 22701 Stephen C. Brich, P.E. Commissioner December 05, 2019 Andy Reitelbach County of Albemarle Department of Community Development 401 McIntire Road Charlottesville, VA 22902 Re: SDP-2019-00063- Pantops Corner Self Storage - Final Site Plan Dear Mr. Reitelbach: The Department of Transportation, Charlottesville Residency Transportation and Land Use Section, has reviewed the above referenced plan as submitted by Shimp Engineering, P.C., dated November 04, 2019 and find it to be generally acceptable. If further information is desired, please contact Willis C. Bedsaul at 434-422-9866. A VDOT Land Use Permit will be required prior to any work within the right of way. The owner/developer must contact the Charlottesville Residency land Use Section at (434) 422-9399 for information pertaining to this process. Sincerely, IIt�V Adam J. Mao e, P. . Area Land Use Engineer Charlottesville Residency WE KEEP VIRGINIA MOVING