HomeMy WebLinkAboutSDP201900073 Review Comments Initial Site Plan 2020-01-08COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
Memorandum
To: Justin Shimp
From: Christopher Perez
Division: Community Development — Planning
Date: January 8, 2020
Subject: SDP201900073 Overlook Hotel - Initial Site Plan
This Memorandum states the reasons for disapproval by identifying the plan's deficiencies and citing the applicable sections of
the Zoning Ordinance or other applicable laws, and what corrections or modifications will permit approval of the plan. (The
following comments are those that have been identified at this time. Additional comments or conditions may be added or
eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Zoning Ordinance
(Albemarle County Code, Chapter 18) unless otherwise specified.]
1. [ZMA 2002-08, ZMA 1998-201 The proposed hotel use is not permitted nor in conformity with ZMA2002-08. The
rezoning amended the application plan to no longer include hotel in the land use summary. Additionally, the application
plan shows this area only as a tree conservation area and with no other uses shown. The application plan must be amended
through a rezoning to allow this use.
2. [ZMA 2002-08, ZMA 1998-201 The site shall not be granted access to Rte. 250; rather, it shall be served by Hansen Road
per the application plan. Discontinue the entrance onto Rte. 250.
3. [ZMA 2002-08, ZMA 1998-201 Depict and label the tree conservation easement on the property recorded in DB 2905 PG
351 and remove the proposed improvements from this area.
4. [SP2002-13 Condition #41 A portion of the site is preserved via the recorded landscape easement (DB2456 PG 682), which
provides screening of the adjacent parking area and reduces the impact of the loss of trees and softens the appearance of the
expanse of pavement. No development shall take place in this area and the trees shall remain for screening purposes. Depict
and label the existing screening trees in this area and remove the proposed improvements from this area.
5. [32.5.2(a), 4.201 Setbacks. The setbacks listed on the plan are incorrect. Revise the setbacks as follows:
The minimum front setback is 10' from the right-of-way or exterior edge of the sidewalk.
The maximum front setback is none on any lot, including a corner lot, abutting a principal arterial highway or interstate.
Side and rear: Adjacent to RA district boundaries, residential or Monticello Historic District
Building minimum 50', Maximum None
Parking minimum 20'. Maximum None
Undisturbed buffer: 20' buffer from adjacent residential areas.
Stepbacks apply to this building. For each story that begins above 40 feet in height or for each story above the third story,
whichever is less, the minimum stepback shall be 15 feet.
6. [32.5.2(a)] Provide the name of the owner, zoning district, tax map and parcel number, and present use of the abutting
parcel TMP 07800-00-08-OOOAO.
7. [32.5.2(e)] Landscape features. Provide the existing landscape features as described in Section 32.7.9.4(c).
8. [32.5.2(e)] Landscape features. On all plan view sheets provide labels identifying whether the existing wooded areas are
composed of evergreen, deciduous or a mix of types of trees.
9. [32.5.2(a)] Boundary Dimensions. Provide dimensions for all parcel boundaries.
10. [32.5.2(b)] Information Regarding the Proposed Use. On the coversheet of the plan list the maximum amount of impervious
cover on the site.
11. [32.5.2(b)] Proposed use. Provide the maximum amount of paved parking and vehicular circulation.
12. [32.5.2(a)] Clearly depict and label the managed slopes overlay district on the existing conditions sheet.
13. [32.5.2(d)] Include the existing managed steep slopes hatching in at least one plan sheet that shows all proposed
improvements to the site. Ensure that the steep slopes design standards are met for all improvements in the area of impacted
steep slopes.
14. [32.5.2(j)] Provide the deed book and page references for any and all existing water, sewer, wastewater or storm drainage
systems easements that are located on the property.
15. [32.5.2(k)] Revise the site plan to include the location of the proposed water lines.
16. [32.5.2(1)] Provide the location and width of any existing or proposed utilities and utility easements including telephone,
cable, electric and gas. Indicate the deed book and page reference for all exiting utility easements located on the property.
17. [32.5.2(m)] Show the distance to the centerline of the nearest existing street intersection from the proposed ingress and
egress.
18. [32.5.2(a)] Provide a list of all proffers that affect the site in the site plan.
19. [32.5.2(k)] Provide flow arrows in all storm drainage pipes.
20. [32.5.2(1)] Depict, label, and dimension all utility easements, including gas.
21. [32.5.2(n), 4.12.181 Dumpster pad. Dimension the dumpster pad.
22. [32.5.2(n), 32.6.20), 32.7.9.7, 4.12.19] Existing and Proposed Improvements. Provide dumpster enclosure detail.
23. [32.5.2(n)] Existing and Proposed Improvements. Provide dimensions on the travelway and parking spaces in the parking
deck.
24. [32.5.2(s)] Depict and label the landscape easements on the property recorded in DB 2731 PG 1.
25. [32.5.2(p)] Provide a complete landscape plan that meets all requirements of section 32.7.9.
26. [32.5.2(p), 32.7.9.8] Tree Canopy. Provide tree canopy calculations for the site.
27. [32.5.2(p), 32.7.9.6] Landscaping within parking area. Provide parking lot landscaping calculations. An area of at least five
percent of the paved parking and vehicular circulation area shall be landscaped with trees or shrubs. Neither the areas of
street trees and shrubs required by sections 32.7.9.5(d) and (e) nor shrubs planted between a parking area and a building
on the site shall be counted toward the minimum area landscaped area for a parking area.
28. [32.5.2(a)] On the site plan provide a description of each of the following requirements:
a. [ZMA2002-08, ZMA 1998-20 Requirement 11 A landscape plan providing full screening of all buildings and parking
areas visible from Monticello shall be provided as a condition of site plan approval for all development. The landscaping
plan may preserve existing trees or provide plantings which shall provide the necessary screening within 15 years. Note that
this applies to the currently submitted site plan and any impact this site plan would have on the existing screening of the
previously developed portions of the PD-MC development.
b. [ZMA2002-08, ZMA 1998-20 Requirement 21 A street tree plan providing a visual buffer for Hansen Road shall be
provided as a condition of site plan or road plan approval. Large street trees shall be planted on both sides of such road in
accordance with the Zoning Ordinance and shall be staggered on opposite sides of the road.
c. [ZMA2002-08, ZMA 1998-20 Requirement 31 All buildings shall be designed to provide rooftop style, treatment and
color schemes which assure minimal visual impact on the Monticello viewshed. Assurance of such style, treatment and
color scheme shall be a condition of final site plan approval. Such approval may be given by the Director of Planning and
Community Development after providing notice to the Thomas Jefferson Memorial Foundation and an opportunity for
Foundation comments to be considered.
d. [ZMA2002-08, ZMA 1998-20 Requirement 41 Approval and execution of the Four Party Road Improvement
Agreement substantially in accord with the document dated October 20, 1998 shall be required prior to the approval of any
development plan. Include the deed book and page number for this agreement in a note on the site plan.
SRC REVIEWERS
Albemarle County Engineering Services (Engineer)
John Anderson, janderson2kalbemarle.org — review comments attached.
Albemarle County Information Services (E911)
Brian Becker, Bbeckergalbemarle.org — No objection, review comments attached.
Albemarle County Building Inspections
Michael Dellinger, mdellin er e albemarle.org — review comments attached.
Albemarle County Department of Fire Rescue
Shawn Maddox, smaddox(&albemarle.org — review comments attached.
Architectural Review Board (ARB)
Kristopher Taggart, Ktaggartg_albemarle.org — review comments attached.
Albemarle County Service Authority (ACSA)
Richard Nelson, rnelsonnserviceauthority.org — review comments attached.
Zoning
Rebecca Ragsdale, rra sg dalegalbemarle.org — review comments attached.
Virginia Department of Transportation (VDOT)
Adam Moore, adam.moore(a)vdot.vir ig nia.gov — review comments pending to be forwarded once received.
Please contact Christopher Perez in the Planning Division by using cperezaalbemarle.org or 434-296-5832
ext. 3443 for further information.
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, Room 227
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
Site Plan Review
Project title: Overlook Hotel — Initial Site Plan
Project file number: SDP2019-00073
Plan preparer: Shimp Engineering, 912 E. High St. Charlottesville, VA 22902
Justin M. Shimp; justinAshimp-en in�g com
Owner or rep.: DJCM Investments, LLC, 1389 Richmond Road, Charlottesville, VA 22911
Plan received date: 2 Dec 2019
Date of comments: 16 Dec 2019
Plan Coordinator: Christopher Perez
Reviewer: John Anderson
SDP2019-00073
For Initial Site Plan Approval
1. Provide retaining wall (RW) preliminary height (ht.) on south side of hotel.
2. Certificate of plat, bk.-pg. 2905-346, aligns with SPD2019-00073, C2. Ref. plat, bk.-pg. 2905-351, and
revise C2 to show: 30' landscape, tree conservation, 15Tgas, 20' drainage and 20' sewer easements across
TMP 78-73A7.
3. Ref. plat at bk.-pg. 3045-566, and revise C2 with labels that identify `1,884 S.F. Overlap Area' along N
boundary of TMP 78-73A7; provide bk.-pg. ref. to this overlap strip.
4. Additional comments are possible once existing (recorded) sewer, drainage, landscape, gas, and tree
conservaiton easements are shown.
5. C2: Show nearest Ex. storm inlet on US Rte. 250.
6. Provide additional existing on -site contour labels.
7. Label commercial entrace radius.
8. Label VDOT right-of-way.
9. Provide conceptual stormwater quality narrative (purchase nutrient credits, on -site SWM, etc.).
10. Provide conceptual stormwater quantity narrative to supplement C4 UG system graphic linework.
11. Provide preliminary new development VaRRM.xls (post -developed) TP reduction (lb./yr); support item 9.
For Final Site Plan Approval
1. VSMP /WP02019-xxxxx approval is required prior to FSP approval. VSMP /WPO Plan may be submitted.
If not, please submit VSMP /WPO Application at earliest convenience.
2. SWM facility and any public drainage easements must be recorded prior to VSMP /WPO plan approval.
C3
3. Revise to include sidewalk width near US Rt. 250.
4. Label steep slopes (dashed) linework.
5. Label HC-parking space dimensions.
6. Label trails, if any.
7. Name /label walls.
8. Label CG-12.
9. Provide stop sign at site entrance.
Engineering Review Comments
Page 2 of 4
10. Dimension internal parking area/s: aisle, space width /length. Label 10'-1 V space in front of 22 internal
parking spaces, N side of hotel. If this is pedestrian space provide bumper blocks for these 22 spaces.
11. Recommend label internal parking area 'I -story parking.'
12. Label important site features: stairs (pedestrian connection to Abbey Road); loading area, etc.
13. Obtain, record, show and label off -site easement pedestrian connection to Abbey Road.
14. Provide /show distance to Hansen Rd. intersection. Distance appears to be approx. 280-ft. Ensure design
meets Min. VDOT entrance separation for Rt. 250 roadway classification, and speed.
15. Provide VDOT guardrail for parking spaces on N side of hotel (VDOT GR-1).
16. If sidewalk along N face of hotel is flush with asphalt pavement, provide wall (or other barrier) to separate
pedestrians and vehicle traffic. Else revise to show CG-2 /CG-6 with 5' sidewalk.
17. Dimension loading area. Ensure Min. vertical clearance is unobstructed by structures, or tree canopy.
18. Label parking aisle width at narrowest point (near curb R12.0' label).
19. Provide and label HC parking space signs.
C4
20. Provide spot elevations at site entrance to indicate whether US Rt. 250 street runoff enters the site.
21. Provide spot elevations to guide commercial entrance construction, given existing grade at US Rt. 250.
22. Proposed retaining wall, N side of building, approaches 30' ht. in places. Provide GR-1 for all parking,
north of hotel, and for the five parking spaces proposed along the west edge of the parking lot.
23. Provide and label CG-6. Ref. recent meeting /discussion (Ecovillage Charlottesville; see 18-4.12.15.p.)
24. Label proposed terrain contours.
25. Show existing sanitary sewer.
26. Show proposed gas line service.
27. Show proposed /existing waterlines.
28. Show roof leader line connections to SWM.
29. Provide LD-204, LD-229, and storm line profiles.
30. Ensure positive drainage away from patio, and port cochere.
31. Ensure underground SWM system can be installed or replaced without encroaching on nearest retaining
wall. See easement diagram, ACDSM, pg. 15.
32. Show and label railings for retaining walls, N and S sides of hotel, including highest elev. of 3-tier walls.
33. Show proposed grading required for retaining walls; for example: walls near Rt. 250 do not tie to existing
grade. Tie proposed grading for retaining walls to existing grade.
34. Provide design to capture weep hole drainage at base of tiered walls.
35. Label radius of dashed -circle at lower parking elevation, an area for fire -rescue apparatus turnaround.
36. Engineering anticipates ACF&R request for on -site fire hydrant, given 230' and 270' distance to Ex. FHs,
east and west of site. Engineering defers to ACF&R.
37. Ensure UG SWM Facility cover is adequate for fire -rescue apparatus (-66 ton apparatus).
38. C2 existing contours indicate a natural stormwater conveyance exists along N property boundary. Design
shows -30-ft. wall near this (off -site /US Rt. 250) natural storm (conveyance) channel. Accommodate Ex.
drainage easement /gully /culvert, bk.-pg. 3045-558 (see, below_). Walls may not encroach Ex. easement/s.
7MP 4784PO4-40-013A4
DRAINAGE EASEMENT
V DRAINAGE EASEMENT D B. 407. .� D.B. 1132, PG. 118
r----- PG. 86JPLAT)OUL1 -T-�
SEE
SEE DETAIL/I! ---------_N69�.iC-ems --r'�� r�1; Lt �DETAIL#2
! "A" S83"5T42" W 4521T F-"
L=----_j BOUNDARYLINE"A Ir _ _ IN -- -J
OVERLAP AREA
HURT INVESTMENT COMPANY
A 988
D.B. . M. 128
39. Provide spot elevations to ensure positive drainage and no nuisance ponding in parking areas.
40. Obtain /record and show temporary construction and/or permanent grading easements required to construct
retaining walls (RW) on S side of hotel. Note: segmental block RW design would require one or both, and
would also require a Maintenance Easement on TMP 78-73B 1 (installation /repair /replacement of geogrid).
Engineering Review Comments
Page 3 of 4
41. Provide sealed geotechnical retaining wall design to Engineering prior to FSP approval.
42. Wall ht. >3-ft. requires a building permit; ht. >4-ft. requires sealed geotechnical retaining wall (RW,) design.
43. Show grading and paved storm runoff channel along top of retaining wall on N side of hotel (paved since
fill section); provide grading and paved runoff channels along top of retaining walls on S side of hotel
(paved given steepness /length of slopes above walls). Also, item 55, below.
44. Show waterline connection to proposed 15' fountain.
45. Provide one or more grate -style drains for 15' fountain, for incidental water that may create hazard.
46. Ensure proposed grading on managed steep slopes at west end of site conforms with any applicable
construction standard listed at 18-30.7.5 (benched grading may be required).
47. Provide armored design for channel created by proposed /existing grade, west end of site. Also, item 43.
C5
48. Engineering recommends additional landscape screening on N side of hotel, above the retaining wall to
discourage trespass. A fall from 30' height presents risk of injury or death.
49. Note: Additional landscape plantings should discourage trespass, but not compromise wall design.
50. Note (WPO plan -related): For slopes steeper than 3:1, propose vegetative cover hardier than grass that does
not require mowing, and that requires minimal (if any) maintenance.
51. Provide plant schedule.
52. Ensure plant types proposed near base of 3-tier wall along S boundary near US Rt. 250 do not compromise
integrity of wall; recommend consider whether proposed plant types will thrive in this narrow space.
53. Ensure Min. 2' clearance between FC and'h mature tree trunk DIA for 15 parking spaces, S side of site.
C6:
54. Provide typical details, including VDOT IS-1, SL-I.
55. Provide paved storm runoff (RW) channel detail.
56. Provide water /sanitary sewer details.
57. Provide roof leader line detail.
58. Provide VDOT GR-1 detail.
59. Provide stairway detail/s.
60. Provide standard handrail detail (VDOT HR-1) for retaining wall on N side of hotel; decorative railing is
insufficient, given wall height.
61. Revise pavement and dumpster pad details, eliminate `T symbol.
• • • .. raaaDPacorAc�re
000000000a00000a 9 WOI q1A en�sTohE
CO/�iAC1rD SLRGAADE
NK CBIMO
1 TYPICAL. SIDEWALK SECTION
SRot is sm.
7' Of 51YM1 SVKWAW
060
G�C�ndn�e�C�GnG� A'i VDOT 021A8ASf510FF
- C PA D511R(.RADE
10%F3flD VERFIFD
sQTYPICAL PAVEMENT SECTION FOR PARKING LOT
ci Not To 5-de
LClIM
.fAY5
7- 6
Ai A,
A A7COO 57RCNMLE
=FIWCRCW.DRM
BARS ATt70C
`
A" CWAC
ACTED SuEC+ADE
"Mcow"
3 Dum sler Wad Deta1
TOIEmDy�
T. des.
62. Min CBR =10.0 is typical. Please clarify design intent of Min. CBR =6.0. Request for clarification, only.
Engineering Review Comments
Page 4 of 4
Please feel free to call if any questions. Thank you
J. Anderson 434.296-5832 -0069
SDP20190007J VVG11U W( FIVLLA 1Jr 161U
Review Comments for SDP201900073 11nitial Site Plan
Project Name: OVERLOOK HOTEL - INITIAL - DIGITAL
Date Completed: Tuesday, December 03, 2019 DepartmentlaivisionlAgency: Review Status:
Reviewer: Brian Becker ODD E911 No Objection
No objection
Page: County of Albemarle Printed On: Fo'UO3T2020
Review Comments for SDP201900073 Initial Site Plan
Project Name: OVERLOOK HOTEL - INITIAL - DIGITAL
Date Completed: Tuesday, December 03. 2019 DepartmentfDivisionfAgency: Review Status:
Reviewer: Michael Dellinger
CDD Inspections Requested Changes
5 accessible parking spaces are required for an R-1 use_ Accessible parking spaces shall be located on the shortest
accessible route of travel from adjacent parking to an accessible building entrance_ In parking facilities that do not serve a
particular building, accessible parking spaces shall be located on the shortest route to an accessible pedestrian entrance to the
parking facility- Where buildings have multiple accessible entrances with adjacent parking, accessible parking spaces shall be
dispersed and located near the accessible entrances_ 60% of all required entrances are required to be accessible. coordinate
with architect and provide spaces accordingly_
Add the following to the general notes page:
All roof drains shall discharge in a manner not to cause a public nuisance and not over sidewalks_
Add detail of accessible parking spaces, van spaces, and signage to plans_
Page: County of Albemarle Printed On: Fo'110312020
Review Comments for SDP201900073 11nitial Site Plan
Project Name: OVERLOOK HOTEL - INITIAL - DIGITAL
Date Completed: Tuesday, January 07, 2020 Department1DivisionfAgency: Review Status:
Reviewer: Shawn Maddox_ _ Fire Rescue Requested Changes
1_ An emergency apparatus turn around must be provided since the travel way exceeds 150'_ �
_ AFDC must be shown on the plans and located within 100' of a hydrant that will not impede a public travel way during
its use-
3- A knox box will be required-
4- Provide the ISO needed fire flovr for the site and the currently available fire flow_
Page: County of Albemarle Printed On: Fo 7081 2020
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 229024596
Phone (434) 296-5832 Fax (434) 9724126
January 7, 2020
Justin Shimp
Shimp Engineering, PC
912 E High Street
Charlottesville, VA 22902
RE: ARB-2019-148: Overlook Hotel (TMP 07800-00-00-073A7)
Dear Mr. Shimp,
At its meeting on Monday, January 6, 2020, the Albemarle County Architectural Review Board
unanimously voted to forward the following recommendations on the above -noted Initial Site
Development Plan to the agent for the Site Review Committee:
• Regarding the Initial Site Plan:
The ARB does not recommend approval of the initial site plan at this time. Prior to Initial Plan
approval the following items must be resolved to the satisfaction of the ARB:
1. Resolve the development issues arising from the tree conservation and landscaping
easements on the subject property.
• Regarding recommendations on the plan as it relates to the guidelines: None.
• Regarding conditions to be satisfied prior to issuance of a grading permit:
1. Maintain grading outside the driplines of trees to remain. Show tree protection
fencing on, and coordinated throughout, the grading, landscaping, and erosion and
sediment control plans.
• Regarding the final site plan submittal:
A Certificate of Appropriateness is required prior to final site plan approval. The following
items and all items on the ARB Final Site Plan Check list must be addressed:
1. Show the location of mechanical equipment (building and ground mounted) on the
site and architectural plans and show how it will be screened from the EC.
2. Provide a complete plant schedule with the next submittal.
3. Show how landscaping, retaining walls and signage will be coordinated at the street
frontage and how an appropriate appearance for the EC will be achieved.
Perspective renderings are recommended.
4. Provide large perimeter parking lot trees, 2%" caliper at planting, at 40' on center.
5. Add 6 interior parking iot trees on the landscaping plan; or provide 4 additional
perimeter trees with 2 additional interior trees.
6. Add the plant health note to the plan.
7. Show the existing trees, tree conservation easement, and landscaping easements
on the existing conditions plan.
8. Resolve the development issues arising from the easements on the subject properly.
9. Revise the plan to provide landscaping to compensate for removed landscaping
required to mitigate visual impacts of the bank site.
10. Show existing trees on the existing conditions plan. Show trees to remain on the site
plan.
11. Identify the retaining wall heights on the south side of the hotel on the grading plan.
Provide complete information on the wall on the north side of the parcel.
12. Indicate retaining wall material(s) and color(s) on the plan. A physical sample may be
necessary for review.
13. Enhance the planting of the terraced retaining walls.
14. Provide site sections and perspective drawings to clarify appearance and visibility of
the hotel and retaining walls.
15. Show existing trees on the existing conditions plan.
16. Show areas designated for preservation, if any, on the site plan. Maintain grading
outside the dripiines of trees to remain. Show tree protection fencing on, and
coordinated throughout, the grading, landscaping, and erosion and sediment control
plans.
If you chose to continue to pursue the initial site plan at this time, please.submit revised drawings
addressing the first bulleted item above. Alternatively, you may submit a new application for a
different proposal at your earliest convenience. Application fortis, checklists and schedules are
available on-line at www.albemarle.org/ARB. Please be certain that your ARB submittal addresses
the above -noted issues..
If you have any questions concerning any of the above, please feel free to contact me.
ncerely,
"J
Khris Taggart
Planner
ktaggart@albemade.org
cc: DJCM Investments LLC
1389 Richmond Rd
Charlottesville, VA 22911
File
Christopher Perez
From: Richard Nelson <rnelson@serviceauthority.org>
Sent: Monday, January 6, 2020 10:24 AM
To: Christopher Perez
Subject: SDP201900073 Overlook Hotel - Initial Site Plan
CAUTION: This message originated outside the County of Albemarle email system. DO NOT CLICK on links or open
attachments unless you are sure the content is safe.
Chris,
Below are comments that need to be addressed prior to Initial Site Plan approval:
Show connections to existing utilities.
The following are general comments:
The applicant can reach out to me for draft connection fees.
Offsite easements for water utilities may be required, depending on the proposed connection location.
Thanks,
Richard Nelson
Civil Engineer
Albemarle County Service Authority
168 Spotnap Road
Charlottesville, Virginia 22911
(434) 977-4511
Review Comments for SDP201900073 11nitial Site Plan
Project Name: OVERLOD HOTEL - INITIAL - DIGITAL
Date Completed: Tuesday, December 17, 201 DepartmentlDivisionlAgency: Review Status:
Reviewer: Rebecca Ragsdale CDD Zoning Denied
Based on review of ZMA200200008, the application plan must be amended through a rezoning to allow this use_ The application
plan shows this area only as a tree conservation area and with no other uses shown_ This rezoning amended the plan to no
longer include hotel in the land use summary -
Page: County of Albemarle Printed On: Fo 7O-T2020
Stephen C. Brich , P.B.
Commissioner
COMMONWEALTH of VIRGINIA
DEPARTMENT OF TRANSPORTATION
1601 Orange Road
Culpeper. Virginia 2270r
January 09, 2020
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902
Attn: Christopher Perez
Re: Overlook Hotel — Initial Site Plan
SDP-2019-00073
Review # I
Dear Mr. Perez:
The Department of Transportation, Charlottesville Residency Transportation and Land Use
Section, has reviewed the above referenced plan as submitted by Shimp Engineering, dated 25
November 2019, and offers the following comments:
1. Include ADT, design/posted speed, for Route 250 on plans.
2. Please provide entrance geometry, for proposed entrance. Entrance, as proposed, does not
meet Access Management spacing standards. Shared commercial entrance and inter -
parcel access standards do not appear to be met. If to remain as proposed, will require
Access Management exception.
3. Please show more detailed information west and east of the proposed entrance.
4. Please show mill and overlay on plans in accordance with WP-2. Please add WP-2 detail
to plans. Also show mill and overlay to the adjacent travel lane.
5. Please provide MOT plan in accordance with the revised 2019 Virginia Work Area
Protection Manual.
6. Please extend continuous right turn lane along frontage.
7. Please provide sight distance lines and profiles for proposed entrance onto Route 250.
8. Please provide drainage calculations and show the respective design storm for a principal
arterial road (Route 250.)
9. Show existing drainage structures, particularly in the vicinity of the proposed entrance.
10. Please label CG-12s for the proposed sidewalk.
11. Note that final site plan must show conformance with the VDOT Road Design Manual
Appendices B(1) and F, as well as any other applicable standards, regulations or other
requirements.
Please provide two copies of the revised plan along with a comment response letter. If further
information is desired, please contact Willis Bedsaul at 434-422-9866.
VirginiaDOT.org
WE KEEP VIRGINIA MOVING
January 09, 202020
Chris Perez
Page 2
A VDOT Land Use Permit will be required prior to any work within the right-of-way. The
owner/developer must contact the Charlottesville Residency Transportation and Land Use
Section at (434) 422-9399 for information pertaining to this process.
Sincerely,
wait, rl/)
Adam J. Moore, P.E.
Area Land Use Engineer
Charlottesville Residency
VirginiaDOT.org