VSMP Permit Plan Review
Hampton Inn VSMP
WP0201900047
Bohler Engineering VA n BohlerEng com [ jwri hg_t(&bohlereng.com ]
PT Hotel, LLC
2 Aug, 2019
11 Sep, 2019
3 Jan 2020
14 Aug 2019
16 Sep 2019
8 Jan 2020
27 Aug 2019
25 Sep 2019 /rev. 2-Oct 2019/Alb. County
21 Feb 2020
WW Associates, Inc. (initial /Rev. 1) / Rev. 1, 2 (J. Anderson)
County Code section 17-410 and Virginia Code §62.1-44.15:34 requires the VSMP authority to act on any
VSMP permit by issuing a project approval or denial. This project is denied. The rationale is given in the
comments below. The VSMP application content requirements can be found in County Code section 17-
401.
A. Stormwater Pollution Prevention Plan (SWPPP)
The SWPPP content requirements can be found in County Code section 17-405. A SWPPP must contain
(1) a PPP, (2) an ESOP, (3) a SWMP, and (4) any TMDL measures necessary.
1. Registration Statement:
a. Section IV E states that the discharge is to an MS4. This appear correct for program compliance
purposes since project is located within Alb. County MS4 boundary.
b. Section IV F requires the provision of a 6t' order HUC. Please provide the 12-digit code, or the 2-
letter, 2-digit number code. (Rev. 2) Addressed.
c. Section VI: the Certification must be signed and dated. (Rev. 2) Comment persists.
2. Provide the Notice of Permit Coverage, once issued. (Rev. 2) Comment persists.
B. Pollution Prevention Plan (PPP)
The PPP content requirements can be found in County Code section 17-404. This plan is disapproved.
1. Please provide an 11" x 17" plan sheet that shows the second construction entrance, with settling pit for
washdown. (Rev. 2) Partially addressed. As follow-up: Please show settling pit for washdown. Show
initial rain gauge, chemical /solvent storage, and concrete washout locations.
2. Show fueling in Table C of Section 6. (Rev. 2) Addressed. (Incl. at Table B.)
3. Provide the responsible person prior to Grading Permit issuance. (Rev. 2) Comment persists. Applicant
response: `Acknowledged.'
4. Revise Section F. to comply with 9VAC25-880-70, Part 11, section A.4.e. (Rev. 2) Addressed.
5. Revise Section G to comply with 9VAC25-880-70, Part II, section A.4.f. This requirement is focused on
training personnel, not the construction or inspection/duties of personnel. (Rev. 2) Addressed.
Engineering Review Comments
Page 2 of 5
6. Section 7 states that bacteria are a TMDL basis for the Rivanna River. State here the measures that will be
taken to ensure that fecal coliform bacteria do not leave the site. (Rev. 2) Addressed.
7. Section 8: Qualified Personnel must be identified prior to Grading Permit issuance. (VSMP /WPO Plan
must be approved prior to approval of the Final Site Plan /FSP.) (Rev. 2) Comment persists. Applicant
response: `Acknowledged.'
8. Section 9: The signed certification must be submitted prior to Grading Permit issuance. (Rev. 2) Comment
persists. Applicant response: `Acknowledged.'
9. Section 10: The Delegation of Authority should be provided prior to Grading Permit issuance. (Rev. 2)
Comment persists. Applicant response: `Acknowledged.'
10. Provide a legend for the hashmark symbols used in the port-a-john, dumpster, fuel pan and materials
stockpile areas. (Rev. 2) Addressed.
C. Stormwater Management Plan (SWMP)
VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This
plan is disapproved for reasons listed, below. The stormwater management plan content requirements can
be found in County Code section 17-403.
Nutrient must be purchased before final VSMP plan approval. Section 17-502 provides the requirements
for acquisition of offsite nutrient credits. Provide required documentation for purchased credits. Please
coordinate with Ana Kilmer (434.296-5832-x3246) prior to purchase, else purchase documents may
require revision. (Rev. 2) Comment persists. Applicant response: `Nutrient purchase documents have
been provided on Sheet C-901. Nutrient purchase will occur prior to plan approval, once all stormwater
management comments have been addressed and no further revisions are required.' Also: in addition to
providing documents on the plan, it is imperative to coordinate with Ms. Kilmer prior to nutrient credit
purchase.
2. Provide a maintenance and inspection schedule for the permanent stormwater control practices, detention
and isolator row. Also, items 6 and 13, below. (Rev. 2) Addressed.
3. Coordinate a stormwater control maintenance agreement with Ana Kilmer as soon as possible. Agreement
is required under 17-415, and is prerequisite to both Grading Permit and FSP approval. (Rev. 2) Comment
persists. Applicant response: `Acknowledged.'
4. Stormwater conveyance piping sizes not specified. Provide for review. (VDOT LD-204; LD-229) (Rev. 2)
Addressed.
5. Show pre- and post -development Tc calculations. (Rev. 2) Partially Addressed. As follow-up: Cannot
locate pre -development Tc calculation on sheet C-900. Please guide reviewer to this information.
6. The Isolator Row is a Practice 17 filtering device. Please correct the VRRM spreadsheet, line 14b. Also,
include with plans pg. 34-37 (portion of O&M Manual) of .PDF file at: https://www.swbmp.vwrrc.vt.edu/wp-
content/uploads/2017/10/Filter Application_ StormTech-Isolator-Row Item-l.pdf# age=34 ). (Rev. 2) Addressed.
New: (10/2/19)
7. Recommend project site area and limits of disturbance be listed on C0.0. (Rev. 2) Addressed.
8. Since storm runoff releases to a natural conveyance downslope of pipe outfall, compliance requires energy
balance, which is provided. Given this, channel protection analysis is complete at riprap section at outfall.
No need to evaluate at POI-1, or discuss POI-1. Likewise, recommend revise SWM Narrative to reflect
flood protection is met using 9VAC25-870-66.C.2.b, in which case, POI -A analysis is not required. (Rev.
2) Addressed.
9. C-900: Water Quality /BMP Analysis makes ref. to Isolator Row. Provide isolator row plan /profile details,
as well as installation details for this stormwater quality -related BMP. Plan -profile -details required for
adequate installation, and construction inspection. (Rev. 2) Addressed.
C-901
Engineering Review Comments
Page 3 of 5
10. Stormwater Detention System — Outlet Structure Detail: If this is (sheet C-202) Str. STM A-30 revise detail
caption to clarify this is the case (if outlet structure detail is STM A-20, please revise detail to clarify).
Also: (Rev. 2) Addressed.
a. Low flow orifice < 3" DIA is prone to blockage. Engineering requires 3" Min orifice diameter.
Revise weir plate design, detention system design, and routings, as needed. (Rev. 2) Withdrawn.
b. Provide weir plate data: material, gauge, connection to MH wall (pre -fabricated /field -built, etc.)
c. Ensure weir plate connection with MH /outlet structure is watertight. Provide notes
/specifications, as needed.
d. Provide low -flow orifice trash rack, and detail.
e. Label critical elevations of 45" StormTech ® MC-3500 detention system profile. For example:
underdrain, stone chamber beneath system, top of chamber, final grade, etc.
11. Operation of bypass is unclear. Provide plan /profile design information for bypass /bypass structures.
Clarify whether weir plate is located in STM A-20 or A-30. Clarify location and elevations of bypass
pipes. Show bypass pipes in profile. Provide schematic detail aligned /consistent with C-203 Sequence,
Phase I, Note 7, where bypass pipes are introduced. Explain how permanent bypass of a portion of post -
developed storm runoff works. Clarify post -developed bypass runoff via narrative and schematic detail.
(Rev. 2) Partially addressed. Please consider possibility underground detention may become obstructed
(consider site runoff routed to system, not State Farm Blvd. off -site runoff that bypasses the site).
Engineering recommends design allow bypass of on -site runoff of the underground detention system in
event system experiences obstruction or unanticipated issue.
12. Consolidate SWM details, as much as possible. For example, only plan -view schematic of StormTech
system is an outline of the system on C-202, which is insufficient. Include plan -view of detention system
on SWM plan sheet, rather than ESC plan sheet. Label overall L x W of detention system. (Rev. 2)
Addressed.
13. It is unclear after reviewing plan and technical information whether the entire extent of the MC-3500
system is an isolator row, or if only a portion is. Clarify using linework, notes, labels, etc., extent and
location of isolator row. Ensure plan provides sufficient detail to guide installation of inspection ports,
non -woven fabric, etc. (Rev. 2) Addressed.
14. Provide calculation using L x W of StormTech system to show VaRRM.xls required volume is provided:
5,842.49 FT3. (Rev. 2) Partially addressed. Asfollow-up: Details on C-903 (* footnote) appear to indicate
12" stone above a 9" stone foundation, or 2 1 " stone total is required to provide design treatment volume.
Please confirm minimum installed storage meets required (VaRRM .xls) treatment volume.
D. Erosion and Sediment Control Plan (ESCP) — Comments addressed with Rev. 2 shown in light grayscale text.
Virginia Code §62.1-44.15:55 requires the VESCP authority to approve or disapprove an ESCP. This plan
is disapproved for relatively minor reasons listed, below. The erosion control plan content requirements can
be found in County Code section 17-402.
1. Intentionally blank
2. Provide the name of the certified land disturber. Also See. B., above, PPP. Listed on plan sheet C-101.
3. A waiver is required for the proposed disturbance within the critical slope area. Please provide evidence
that a waiver has been obtained for this disturbance. (Rev. 2) Withdrawn; review error. Proposed grading
on managed slopes is a permitted use, and is complaint with 18-30.7.5.
New: (10/2/19)
C-201
4. Remove silt fence unless parallel with contours.
5. Provide alternative ESC measures for SF removed at item 4; DD, for example.
6. Label floor dimensions of sediment trap. Label ST weir dimensions. (Also, item 22, below).
Engineering Review Comments
Page 4 of 5
7. DA upslope of silt fence may not exceed 100', which appears to be the case at the N corner of LOD.
Revise SF design consistent with VESCH, 3rd Edit, 1992.
8. Revise CE label to read PCE. VA Uniform Coding System legend is fine, but project requires a paved
construction entrance. Revise Legend to include Mulch (MU). Revise sheet C-202, as well.
C-202:
9. Note: PE -sealed geotechnical retaining wall design is required for Site Plan approval. (Rev. 2) Comment
persists. Applicant response: `Acknowledged. PE -sealed geotechnical retaining wall designs will be
provided prior to Site Plan approval.'
10. Show /label SWM Facility Easement (detention /isolator row). Provide SWM Facility Access Easement
that extends to public RW (State Farm Blvd). (Rev. 2) Partially addressed. As follow-up: SWM Facility
easement linework is show. Please label linework. (SWM Facility Access Easement is labeled.)
11. Provide, show and label public drainage easement for permanent stormwater conveyance downstream of
detention system. (Rev. 2) Partially addressed. As follow-up: Easement linework is show. Please label
linework.
12. Submit easement plat application for items listed at 10 and 11, above. Ensure easement width for detention
system conforms with drainage easement diagram at ACDSM, p. 15; link to Design Manual: (Rev. 2)
Comment persists. Applicant response: `An easement plat will be provided prior to plan approval.'
http://www.albemarle.org/upload/images/fonns_center/departments/communily development/forms/design
standardsmanual/Albemarle_County_Design Standards _Manual _2015-04-25_draft.pdf
13. Note: Recorded deed of easement (deed /plat) is required prior to VSMP /WPO plan approval. (Rev. 2)
Comment persists. Applicant response: `Acknowledged. The recorded deed of easement will be provided
prior to plan approval.'
14. Dimension riprap (L x W x D) at storm pipe outfall near west corner of site.
15. Add labels that correlate this sheet with C-203, VII, Sequence, Phase I, Note 7., bypass pipes (proposed and
existing 2 1 " bypass).
C-203
16. Sequence of Construction, Phase I, Note 7: Label 2 1 " RCP pipe on C-202. (Rev. 2) Comment appears to
persist. Reviewer cannot locate label.
17. Include county Construction Record Drawing (As -built) policy on VSMP plan; link to policy:
http://www.albemarle.org/upload/images/forms center/departments/Community Development/forms/En_ing eering and
WPO Forms/WPO VSMP Construction Record Drawings Policy 23Ma, 2014.pdf
18. Provide /include manufacturer -specific installation and periodic inspection guidelines on the plan. Also,
comment at C.6., above.
19. Provide additional sequence /text description of transition from Phase I to Phase II, especially measures
required once sediment trap is removed, but before site is stabilized and detention system is on-line. (Rev.
2) Partially addressed. As follow-up: It appears Note 7 should precede Note 5, since it appears the 24"
permanent (bypass) pipe must be installed prior to the sediment trap. Also, please see Engineering review
comments on Hampton Inn FSP (SDP2020-00004), d. 14 Feb 2020.
20. Provide additional sequence that details how /when detention system is brought on-line, relative to site
stabilization. (Rev. 2) Partially addressed. Asfollow-up: Revise Note 9 to clarify that the StormTech
system (underground stormwater detention facility) may not be connected and should remain isolated from
upstream storm conveyance pipes until all contributing upslope areas are stabilized (stone /pavement, etc.).
Also, revise Note 8 to indicate that contractor may not remove sediment trap (or any active ESC measure)
without county ESC inspector approval.
C-204:
21. Include VDOT standard details, including: ST-1, IS-1, MH-1.
22. Show sediment trap floor dimensions on C-201 (Also, item 6, above).
Engineering Review Comments
Page 5 of 5
The VSMP permit application and all plans may be resubmitted for approval when all comments have been
satisfactorily addressed. For re -submittals please provide 2 copies of the complete permit package with a completed
application form.
Engineering plan review staff are available from 2-4 PM on Thursdays, should you require a meeting to discuss this
review.
Process:
After approval, plans will have to be bonded. The bonding process is begun by submitting a bond estimate request
form and fee to the Department of Community Development. One of the plan reviewers will prepare estimates and
check parcel and easement information based on the approved plans. The County's Management Analyst will
prepare bond agreement forms, which will have to be completed by the owner and submitted along with cash,
certificates or sureties for the amounts specified. The agreements will have to be approved and signed by the County
Attorney and County Engineer. This may take 2-4 weeks to obtain all the correct signatures and forms.
Stormwater Management Facilities Maintenance agreements will also have to be completed and recorded. The
County's Management Analyst or other staff will prepare the forms and check for ownership and signature
information. The completed forms will have to be submitted along with court recording fees.
After bonding and agreements are complete, county staff will enter project information in a DEQ database for state
application processing. DEQ will review the application information based on local VSMP authority approval. At
this time, the DEQ portion of the application fees will have to be paid directly to the state. For fastest processing,
this is done electronically with the emails provided on the application. DEQ should notify applicants with
instructions on how to pay fees. When DEQ approves the application, they will issue a permit coverage letter. This
should be copied to the county.
After DEQ coverage is issued, via the coverage letter, the County can hold a pre -construction conference.
Applicants must complete the request for a pre -construction conference form, and pay the remainder of the
application fee. The form identifies the contractor and responsible land disturber, and the fee remaining to be paid.
This will be checked by county staff, and upon approval, a pre -construction conference will be scheduled with the
County inspector. At the pre -construction conference, should everything proceed satisfactorily, a joint VSMP and