HomeMy WebLinkAboutSDP202000030 Correspondence 2020-03-23 (4)AlbemaldeCounty � Hydrant Flow Service Auth♦ri �'"'�"°'�'"'� `��'� Test Report 16S SpoYiep ROM Charlottesville. VA 22911 (Aadl 9"4511 Location Date and Time of Test Minutes of Flow Pipe Size (Inches) COLONNADE DR 3/5/2020 9:19:00 AM 3 10 Pressure Hydrant 10190 Static Pressure (psi) 64 Residual Pressure (psi) 55 1-1 Q20 Looped ❑ Q20 Multiple Inline Hydrants Flow Hydrant #1 10191 Pitot Pressure #1 (psi) Flow Hydrant #2 10192 Pitot Pressure #2 (psi) Flow Hydrant #3 Pitot Pressure #3 (psi) Date of Report 3/5/2020 fVI Q20 Single Flow ❑ Sprinkler Test Single Flow Total Estimated Flow (gpm) 1560 AWWA Q20 Calculation (gpm) (No value in 0.20 indicates insufficient pressure drop for Q20 OR a sole sprinkler test.) Comments Hydrants opened all the way 20 Yellow 1 ❑ Test Flow 1 625 31 Yellow 2 0 Test Flow 2 935 Yellow 3 Test Flow 3 0 For method of calculating pltot flow with a red Pollard diffuser: see eq. 13, Walski and Lutes article 1990 Journal Management and Operations AW WA. For yellow Pollard diffusers, a best 0t third order polynomial equation of the Pollard flow vs. pitot pressure gauge is used. Estimated Consumption (gal) 4680 For use for water audit Signature of Tester:^^ 2 k W,j ^ }; CO >} \ } \� �)$| «|2 \\0 ; / [ SD p | ( ( /