HomeMy WebLinkAboutSDP201900081 Review Comments Minor Amendment 2020-05-29r� 'AL � IRGS?at� County of Albemarle Department of Community Development Memorandum To: Eric Woolley, Woolley Engineering; (ewoollev@woollen-eng.com) From: Andrew Reitelbach, Senior Planner Division: Planning Date: May 29, 2020 Subject: SDP2019-00081 Tandem Friends School Pavilion — Minor Amendment; 2nd Submittal The Planner for the Planning Division of the Albemarle County Department of Community Development will recommend approval of the plan referred to above when the following items have been satisfactorily addressed. (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.) [Each comment is preceded by the applicable reference to the Albemarle County Code.] 1. [13.2.2.5] The proposed use requires an amendment to the existing special use permit (SP2015-00021) for this project. The site plan minor amendment cannot be approved without an amended special use permit that has been approved by the County's Board of Supervisors. It is acknowledged that there is an application (SP2019-00007) currently in progress to amend the special use permit, with an anticipated date for a public hearing before the Board on April 15, 2020. Comment addressed. The Board of Supervisors approved SP2019-00007 on April 15, 2020, amending the previously -approved special use permit to allow the proposed use of a pavilion. 2. [32.5.2(a)] Provide the county and state names of the location of this project in the title of the project on the cover sheet. Comment addressed. 3. [32.5.2(a)] Provide the application number of this project (SDP2019-00081) in the title on the cover sheet of the site plan. Comment addressed. Also, revise the final site plan number that this plan is amending. This plan is amending SDP1998-00081. (SDP2016-00073 is no longer valid because it was an initial site plan, and no final site plan was ever submitted for that project within one year of the initial site plan's approval, as required by the ordinance.) Comment addressed. 4. [32.5.2(a)] Revise the signature panel on the cover sheet to remove the Zoning division and to add VDOT and ARB. Comment addressed. [32.5.2(a)] Include all applicable zoning overlay districts to the zoning note (note #5) on the cover sheet. The zoning overlay districts for this property include Entrance Corridor, Airport Impact Area, and Steep Slopes — Managed. Comment addressed. 6. [32.5.2(a)] If the Board of Supervisors chooses to approve the amended special use permit for this project (SP2019-00007), then a copy of the special use permit, including all conditions, will need to be included in the site plan. (These copies are generally included on sheet 2.) Comment not addressed. Sheet 2 currently depicts the action letter from the Planning Commission public hearing. Replace this action letter with the approved resolution, including the approved conditions, from the Board of Supervisors public hearing that occurred on April 15, 2020. 7. [32.5.2(b)] Revise notes 7 and 8 on the cover sheet so that they match. Note #7 indicates that the footprint of the proposed new building is 3,266 sq. ft., while note #8 indicates that the footprint is 3,267 sq. ft. Comment addressed. 8. [32.5.2(b)] Provide the maximum amount of impervious cover that is being added to this site with this project. Comment addressed. 9. [32.5.2(a)] In the site development plan narrative on sheet 2, #9 (SDP2016-00073) should be removed from the list, as that site plan is no longer valid. A final site plan was never submitted for the middle school expansion project, rendering that initial site plan invalid one year after its date of approval. Comment addressed. 10. [32.5.2(n)] On sheet C3.0, it appears that additional portions of the existing tree cover near the eastern property line should be shown as demolished, as the stormwater management plans depict SWM facilities being installed in that area. Comment addressed. 11. [32.5.2(d)] The areas of managed steep slopes also need to be shown on sheets C3, C4, and C5 so that staff may accurately understand the locations of those slopes in relation to the proposed improvements, in order to determine whether any steep slopes are being disturbed with these improvements. The addition of gravel to expand the existing gravel drive may disturb some steep slopes. Comment addressed. 12. [32.5.2(n)] Identify the height of the proposed new wall surrounding the sidewalk on the northwest side of the pavilion. A railing may be required along the wall. Comment addressed. 13. [32.5.2(n)] A railing needs to be provided on either side of the wood stepped porch. Comment addressed. 14. [32.5.2(n)] Clarify what the label "add alternate #1" means for the wood stepped porch. Comment addressed. 15. [32.5.2(n); 4.17] A lighting plan was not included in this submission of the site plan. If any outdoor lighting is proposed for this project, then a lighting plan that meets the requirements of 18-4.17 must be submitted to be reviewed along with the site plan. Clarify whether any outdoor lighting is proposed in associated with this pavilion building. Comment addressed. 16. [General Comment] An easement plat (SUB2020-00091) has been submitted to the County for review for this project. This easement plat must be approved and recorded prior to approval of the site plan minor amendment. 17. [32.5.7.9] Sheet 1-1.0 has a note near the bottom of the page that states, "Proposed trees and shrubs (See sheet C6.0)." There is no sheet C6.0 included in this site plan. Revise the note to indicate the correct sheet that contains this information. Please contact Andy Reitelbach at the Department of Community Development at areitelbach@albemarle.org or 434-296-5832 ext. 3261 for further information. Comments from Other Reviewing Departments and Agencies Albemarle County Engineering Services — David James, dlames2@albemarle.org— Requested Changes; meeting with applicant recommended; please see the attached memo. Albemarle County Building Inspections — Michael Dellinger, mdellinger@albemarle.org — No objection other than recommendations below: Verify allowed distances to plumbing features, etc. are not exceeded. For future reference, sprinklers may be required with the addition of the future addition, see code requirement below: Group A-2. An automatic sprinkler system shall be provided for Group A-2 occupancies where one of the following conditions exists: 1.The fire area exceeds 5,000 square feet (464.5 m2); 2.The fire area has an occupant load of 100 or more in night clubs or 300 or more in other Group A-2 occupancies; or 3.The fire area is located on a floor other than a level of exit discharge serving such occupancies. Albemarle County Service Authority (ACSA) — Richard Nelson, rnelson@serviceauthority.org — No objections at this time. PROJECT: SDP201900081 - TANDEM FRIENDS SCHOOL —MIA — 5/22/20 Engineering comments (David James): 1. The VSMP plan is currently under review and approval is necessary prior to site amendment approval. Comment still valid. 2. Sign & date seals. Addressed. 3. Remove the SWM & ESC plan sheets from the site plan amendment (Sheets 8, 12-14). Addressed. 4. Cover: Provide date of field verification of existing site conditions: Topography should be visually field verified by within the last year. Addressed. S. Show drainage profile info and separation distances. Show the separation distance between existing sewer and storm pipe 2-1. 6. The proposed travelway/driveway extension is subject to county engineer approval. [DSM, pg. 16] See comment 8. 7. Continue grading for proposed extension. -Cross-slope should follow minimum standards for travelways. See comment 8. 8. If the intent is to use this as an emergency vehicle access, then the entrance and travelway will have to meet minimum design standards. a. I measured the entrance grade or cross -slope to be about 11%. This exceeds the minimum grade allowable of 4% for 40ft. b. The entrance radius should be 25ft min. c. You're providing a 9ft wide gravel travelway for the first 170ft length of access. The minimum travelway width should be 12ft on a one-way aisle, but for an emergency vehicle it would need to be 20ft. d. The next 220-ft length of access is a propriety grass pavement system that is 20ft wide. The cross -slope appears to be generally high up to 20%. I'm not sure about the cross -slope requirement for the grass paver system, but the maximum allowable grade is 10%. Please refer to Sec. 18-4.12.17 — Minimum design requirements and improvements for vehicle access aisles