HomeMy WebLinkAboutSDP201900069 Correspondence 2020-07-06 (3)L I N E + G R A D E C I V I L E N G I N E E R I N G June 15, 2020 TO: Albemarle County Community Development 401 McIntire Road Charlottesville, VA 22902 ATTN: Paty Saternye Senior Planner RE: SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Dear Paty, On behalf of Tom Thorpe, we offer the following responses and plan revisions to comments dated May 26, 2020. Our Responses are in bold italic text below each comment. Paty Saternye — Senior Planner Comment Subject + Location 2. [LOR #2 & #4] The proposed minor site plan amendment appears to not match the LORs that have been previously approved. Address the following: a. [LOR #4] The site plan does not show all of the improvements approved in LOR #4. Address the following: ii. The trellis shown on the LOR #4 drawings is not shown on the site plan. From the original request letter for the LOR it appears there was not the intention to build the trellis at that time. If it is not to be built, then it does not need to be shown included in the site plan. If it may be built in the future more comments may be required. Rev. 1: Comment not yet fully addressed. Although the comment response letter states that the trellis was not built and there is currently no intention of adding the trellis the note on the coversheet states "As well as a trellis to be built in the future". Please clarify this discrepancy and do one of the following. a) IF the trellis is not to be built in the future then the following applies. It appears that the concrete wall, and some form of a fence, have been constructed in the terrace area based upon LOR #4. Therefore, for L I N E + GRADE CIVIL ENGINEERING 113 4`h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 2 the portion of LOR #4 that has been built the labels (like shown on sheet X1.7 but revised for what was built) in the existing conditions sheet and a detail (like shown on sheet X1.8 but revised for what was built) needs to be included in the details sheet of the current site plan (SDP2019-69). The attached previously approved LOR is not a substitute for adding this information into the proposed site plan. b) IF the trellis will, or may, be built in the future then follow the comment above for the existing conditions sheet. Then also, in the proposed layout sheet, show the future trellis being added. A note should be added in that sheet that states "To be added in the future by others". In the details provide one detail for what was already built and then provide the proposed revision (should be the same as sheet X1.8). Ensure that that the second detail is labeled as "Future Trellis Addition". Please note that the labels and information shown in both of the LOR #4 sheets (X1.7 & X1.8) should be included in this site plan. Attaching the previously approved LOR is not a substitute for adding this detail into the proposed site plan. Comment noted. See revised plans. We have use the LOR #4 documents to re-create the CAD linework of this area. We hope this addresses your comment. [Comment] A list of requested changes is needed for a Minor Amendment. The "Scope of Work" note on the coversheet partially addresses this requirement. Address the following: a. Under "Minor Amendment changes to SDP2000-77:" List all previously approved LOR separately in a bulleted list. A brief description of the changes approved with each LOR is important. L IERev. 1: Comment not yet fully addressed. Address the following: ii. Revise the description of LOR #2 to state the approved GRADE concrete pad width. A way to do this, without causing future confusion, would be to state, "Addition of 14.5' x 40' 100 concrete pad adjacent to 6.5' existing sidewalk." STREET NE, sAE. CHARLOTTESVILLE, VA 2290902 LINE-GRADE.COM Comment noted. See revised plans. SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 3 iii. Add the four LORs to the "Project History' on sheet C0.1. Comment noted. See revised plans. We assume you meant, "Project Summary" on sheet CO. 1. In the bulleted list mentioned above, individually list the two changes already specified under "Scope of Work:". Rev. 1: Comment not yet fully addressed. Address the following: i. Revise the note to add back in the mention of the addition of "asphalt paving". That change is still proposed on the site plan. Comment noted. See revised plans. Revise the note to change "edition" to "addition". Comment noted. See revised plans. Include in that bulleted list all other changes, not approved in the 4 previous LORs, that where not approved with SDP2000-77 (see attached PDF of approved site plan). Any and all changes not already approved must be listed here. They include (but may not be limited to): ii. The removal of street trees and their replacement with shrubs along Avon Street Extended. Including a very brief description on why that change was made and allowed would be helpful. iii. Specify that the landscaping has been revised. Trees and shrubs have been removed around the site. New trees and shrubs will be added with this site plan amendment in order to compensate for those previous changes from the approved site plan. See comments on landscaping below. iv. The addition of a dumpster enclosure and pad. Although the hatching on sheet C2.0 appears to be showing the dumpster pad as being approved with a LOR it does not appear to be included in four LORs. v. Changes to the parking layout, striping, removal or addition L I N E + of stop blocks. GRADE vi. Changes to the parking calculations and requirements. Rev. 1: Comment revised. Remove this section on the cover sheet. Staff will include a note in the permanent file on the 1134 L STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 first bulleted item, with the details of the past history. All the LINE-GRADE.COM other items have been sufficiently incorporated in the site plan with notes and clouds and therefore no longer need to be specifically listed here. SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 4 Comment noted. See revised plans. 4. [Comment] There are items shown on the site plan that were not approved with the original site plan or with LORs 1 through 4. Address the following: a. Provide any documentation on the approval for the dumpster enclosure and pad to the reviewer. Also, show it and list it in this site plan amendment as a change being proposed with the amendment. Rev. 1: Comment not yet fully addressed. The note has been added to the cover sheet. Also include a dumpster enclosure detail within the site plan showing the height, material, gates etc. Comment noted. See revised plans. We have re-created the existing dumpster enclosure per observations from a site visit. c. Many of the parking spaces, especially along Avon Street Extended, do not appear to meet the dimensions specified on the approved site plan (SDP2000-77) or the current ordinance. Ensure the spaces are as approved or meet current requirements. Although the lines shown on the proposed amendment may be as they are currently painted (as built) those paint lines will need to be revised, to meet this site plan amendment once it is approved. Address the following: i. i. Revise the parking space width and depth to meet the previously approved size or the current zoning ordinance. SDP2000-77 shows both 9'x18' spaces and 9'x16' spaces (when there is at least 2' of open space (without shrubs or trees) in front of the space). There are many spaces that do not appear to be either 9' wide or 16' deep. Rev. 1: Comment not yet fully addressed. Address the following: a) Shift the 9 parking spaces along the edge of Avon Court to be closer to Avon Street Extended. The parking space on the right does not appear to meet the minimum width requirements but there is additional area on the left side that can be utilized. Comment noted. See revised plans. b) Clarify if the two handicapped (HC) spaces near the entrance to Avon Court are being changed to be three regular spaces. The two proposed paint lines on either side of the hatched access aisle make it unclear if these will remain as HC spaces or regular L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 5 spaces. If they are to stay as HC spaces the ADA space size requirements govern their size. If they will be regular spaces the HC parking markings should be removed. These are to become traditional spaces. See revised plans. c) Either remove the single parking space near the northern edge of the property, next to the ash tree and in the vicinity of the dumpster, or remove it from the Proposed Plan layout. It does not appear to meet the minimum parking space size requirement. Please note that it does not appear that there is sufficient width of the travel way to extend the space to the required depth. That travel way must be 24' wide since the parking spaces on the other side of it are only 9' wide. Comment noted. See revised plans. d) There are 22 parking spaces within TMP 77-9A shown on this site plan. They also do not appear to match the parking space layout shown on SDP2008- 30. Add a label in this area that states, "This area of parking is not being reviewed with this site plan and is part of SDP2008-30." Comment noted. See revised plans. Revise the parking calculations as follows: iv. The parking required for the industrial portion of the building does not include the required spaces for the customers/public. There is supposed to be 1 space for every 500 SF of area open to the public, but there is also a minimum of 2 customer spaces. Include this as part of the calculation for the industrial parking requirements and ensure the customer parking requirement is met. Rev. 1: Comment not yet fully addressed. The calculation for L I N E + GRADE the industrial parking requirement appears to be correct, but the information required to determine if it is correct has not STREET NE, 00 CHARLOTARLTESVILLE, VAA2222902 been included in the calculation on the site plan. Add a note LINE-GRADE.COM below the calculation stating that no portion of the building is open to the public. SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 6 Comment noted. See revised plans. Note has been added to footnote 1 below the calculations. g. See Inspections comment on the number of handicapped spaces provided in the plan. Rev. 1: Comment not yet fully addressed. Inspections has an additional comment (5/22/2020) based upon the addition of the temporary building. See their attached comment. The temporary Building is being removed from the plan. The Owner has made other arrangements. The landscaping plan has changed from the approved site plan. Address the following: i. Provide a landscape schedule that specifies at least the information specified on the approves site plan (SDP2000-77: Tree species, quantity, caliper and symbol). Rev. 1: Comment not addressed. Address the following: a) The landscape plan appears to not be based upon SDP2000-77 but on an earlier site plan (1991) that was attached to the site plan submission. This has only a small impact on the landscaping within the parcel, but one tree (MSA near dumpster) and one shrub (yew near entrance) are different. Revise the landscaping and landscaping labels to be based on SDP2000-77. See elsewhere in these comments on impact outside of the parcel. Comment noted. See revised plans. b) Applicant has chosen to put information in labels instead of a schedule. Since this is based upon a previously approved plan prior to current requirements this will be allowed. However, all of the information shown in the previously approved plan must be provided. The caliper of the tree at the time of planting is not provided and is required. Revise the labels for all trees that are to include the caliper of the tree at the time of planting or provide a schedule that includes this information along with the tree type and quantity. Please note that 1 1/2" caliper trees were the specified minimum on the approved site plan. This information must be provided to not only match the previously approved site plan but also to provide the necessary L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 7 information for any required tree replacements needed in the future. Comment noted. A planting schedule has been developed. See revised plans. iii. Ensure that all existing or proposed tree or shrub has a label, for the tree type, that is referenced in the landscape schedule. Rev. 1: Comment not yet fully addressed. A tree schedule has not been provided, and not all of the information provided in the tree schedule on the approved site plan has been included in the labeling for each existing and proposed trees. See comment "ii." Above on how to address this comment. Comment noted. A planting schedule has been developed. See revised plans. v. The tree canopy provided is specified on the site plan. However, it specifies "existing tree coverage preserved". However, no trees are shown as preserved on the site plan. If this is referring to the existing tree cover, going down the hill to Moore's Creek, address the comment above and then: c) 2. Include in that label if they are "deciduous", "evergreen" or a "deciduous/evergreen" mix. Rev. 1: Comment not yet addressed. This comment is in reference to large preserved tree area on the north side of the parcel and not the individual trees within the developed portion of the site. Address this comment by labeling the "Existing Tree Canopy to be Preserved" as either "deciduous", "evergreen" or "deciduous/evergreen mix". Comment noted. See revised plans. vii. In the approved plan there were three additional trees (pines) along the Avon Court road frontage. If they are not to be replanted, then plant two more Large Shade Trees along Avon Court to meet the current street tree requirement. These should be parallel to the road, line up with the existing tree that is about 30' from the travel lane (which may be a willow oak) and within the parcel. L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 8 Rev. 1: Comment not yet fully addressed. Revise the location of the proposed willow oak furthest southeast along Avon Court to not impact the existing business sign. The trunk appears to be less than 5' from the monument sign and will be blocking the view of the sign. Comment noted. Willow oak moved so as not to impede the view from Avon Extended. See revised plans. viii. In the approved plan there were 3 Japanese Yews and three Red or Austrian Pines along the Avon Court parcel boundary. These evergreens were meeting a requirement for mitigation the view of the parking lot. If they are not to be replanted, then at a minimum shrub should be planted between Avon Court and the parking lot at 5' on center and at a height of 12' at time of planting. Rev. 1: Comment not yet fully addressed. Although the 4 Japanese Yews shown on the approved site plan are shown as being replaced (see below) they do accomplish the visual mitigation that would have been provide by evergreen trees between Avon Court and the parking. Fully address this comment as specified above. Comment noted. See revised plans. Ensure that all existing landscaping on the parcel, and in the VDOT right of way, is shown and labeled. It is possible that some of the existing landscaping may be able to meet some of the requirement mentioned above. Rev. 1: Comment not yet fully addressed. Address the following: a) Show the existing shrubs along Avon Street Extended in the "existing conditions and demolition plan" sheet. Comment noted. See revised plans. b) If none of the 4 yews at the entrance from Avon Court are currently existing, then they should not be shown in the existing conditions sheet. Comment noted. The 4 Japanese Yews are not shown on the existing conditions sheet. L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 9 Please contact us if this comment is not fully addressed. WE're not sure we understood the nature of this comment. c) The proposed plan sheet should either show no landscaping (existing or proposed since there is a separate landscaping sheet) or show all existing and proposed landscaping. Currently it is showing just existing landscaping even though it is a "proposed plan" sheet. Comment noted. See revised plans. d) The Proposed Layout sheet should not show trees that were "removed per VDOT". They are neither existing nor proposed and therefore should not be shown in the plan at all. Comment noted. See revised plans. e) Removed any reference to trees "removed per VDOT" in the site plan. As specified in a phone call on 5/18 county staff will include a note in the permanent file about those previously allowed changes. Comment noted. See revised plans. f) As specified in the comment elsewhere (and in a phone call on 5/18), in reference to the "Site changes not associated with SDP2000-77" note, special treatment of these items not previously approved is no longer being requested. Revise the labels for these two shrub areas (along Avon Street Extended and the yews near the entrance) to match those of other existing and/or proposed landscaping. What is ultimately provided will be compared against the previously approved plan, but reference to that previous approval in the labels is no longer requested. Comment noted. See revised plans. L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 10 Please contact us if this comment is not fully addressed. WE're not sure we understood the nature of this comment. There is an area shown on the approved site plan, going down to Moore's Creek, that is no longer being shown on this site plan amendment. Address the following: iii. Show and label the Dam Inundation Area line and specify if it is state or federal. Rev. 1: Comment not yet fully addressed. Revise the labels to specify if they are the state or the federal Dam Inundation Area boundaries. Comment noted. See revised plans. iv. Show the full extents of the Steep Slopes overlay district. Address the following: b) 2. Provide labels or a legend for the hatched areas of the steep slopes to specify if they are managed or preserved. It appears that the hatches on the site plan already show two different hatches for managed and preserved steep slopes but there is no key or legend clarifying what the two different hatches represent. Rev. 1: Comment not yet fully addressed. There is a small area of "managed" steep slopes on the property in the vicinity of the terraced patio. Show this area, hatch it, and label it. There appears to be some hatching in the appropriate area, but it is not labeled, and the hatch symbol selected for "managed" steep slopes is not obvious. Even if the area is no longer graded as it once was, when designated as "managed steep slopes", this is an overlay district and the district applies even after the grading has been modified. Comment noted. See revised plans. k. Rev. 1 [NEW COMMENT]: Show the location of all loading spaces in the site plan. Address the following: i. Show the spaces including hatching and labels. ii. Include a calculation on the site plan specifying the required and existing (or proposed) loading spaces L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 11 Comment noted. See revised plans. 6. [32.5.2(a) & 32.6.2(a)] Address the following in reference to general information on the site plan: a. a. Revise the zoning information to also specify that this parcel is in the: i. Airport Impact Area ii. Dam Inundation Area iii. Flood Hazard Area (and include FEMA note) iv. Steep Slopes: Managed and Steep Slopes: Preserved overlay district. Rev. 1: Comment not yet fully addressed. Although specific comment above was addressed, the overall zoning of "Light Industrial" was not correctly stated. It is "LI" (the letter "I") not "L- 1". Revise this information in the zoning portion of the cover sheet. Comment noted. See revised plans. b. Revise the setbacks to fully and accurately specify the setback requirements. v. Side and rear setbacks for parking are the same, so could be stated together. However, the description of the setback needs to be expanded. "None Required" is not complete. There is a 30' setback for buildings if the adjoining lot is zoned residential, rural areas, or Monticello Historic District. Although the adjoining lots to not currently fall into that category this information should be included. Rev. 1: Comment not yet fully addressed. Although staff can allow the reduction in detail level requested by the applicant, the information provided on C0.1 is not correct. Revise the "(Adjacent to R1)" to instead read either "(Adjacent to LI and B-2)" Comment noted. See revised plans. d. For the adjoining parcels adjoining within the City of Charlottesville provide the names of the owners, zoning district, tax map and parcel number and present use. Rev. 1: Comment not yet fully addressed. The information added to sheet C0.1 was for Albemarle County parcels, which had already been provided on sheet C1.0, and not the City of Charlottesville. Address the comment for the adjacent parcels within the City of Charlottesville. There are two adjoining parcels within the City on the other side of Moore's Creek. Please provide this information on the L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 12 existing conditions Sheet C1.0, as was done for the County parcels. They have the parcel numbers of 590371000 & 590370000 and are zoned B-2. Comment noted. See revised plans. 7. [Comment] See the attached comments from the other reviewers. The site plan will not be approved without the approval of the other reviewers. Rev. 1: Comment addressed. Comments for Inspections were addressed, but the addition of the temporary building has required additional comments. See the attached comment from inspections. Temporary Building has been removed from the scope of work. 8. Rev. 1: [New Comment — 5.8] Temporary Industrialized Building. The "Proposed Temporary Modular Building" was not included in the 1st submission of this minor site plan amendment. Therefore, if it continues to be included in this minor amendment all requirements for 18-5.8 must be met and additional revisions to the site plan are required. Address the following: a. It has been suggested by zoning that the temporary industrialized building might be handled as a "Letter of Revision" (LOR) after the minor site plan amendment has been approved. In that case the LOR, the zoning clearance, and the building permit could be processed together. By proposing the temporary building in the 2nd submission of this minor amendment additional information is required that was not requested in the 1st round of comments. 5.8(b) Provide a written statement from the owner to the zoning administrator explaining the purpose of the temporary industrialized building, the activities to be conducted therein, and the duration that the temporary industrialized building will be located on site. This letter should be submitted separately and also incorporated into the site plan. c. 5.8(d) Conditions to address the impacts arising from the temporary industrialized building must be incorporated into the site plan for review and approval to meet 5.8. Address the following: i. Include the in the label for the temporary industrialized building the period of time that the building will be allowed to be on site. Ensure it is no more than specified in 5.8(f). Include in the site plan information about the required skirting (see 5.8(e)). This should be included as both part of L I N E + GRADE 113 41h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM SDP201900069 (Afton Scientific — Minor Site Plan Amendment) Comment Response Letter January 01, 20191 Page 13 the label for the building as well as a detail showing the skirting. Ensure it meets the requirements specified in 5.8(e). iii. Screening for the temporary building needs to be shown and reviewed. There is existing landscaping on the adjoining parcel TMP 77-9A which may meet some of that requirement. Please note that SDP2000-77 showed landscaping in this area but it appears changes have been made. Therefore, information on the last approved final site plan for TMP 77-9A (SDP1993-85), and its landscaping, must be researched will be forwarded to the applicant once it is scanned. iv. Both a building permit and a zoning clearance are required for a temporary industrialized building. That process takes place after the approval of the minor amendment. Temporary Building has been removed from the scope of work. Rev. 1: [New Comment] Staff appreciates having access to the previously approved minor amendment and LORs. However, they are not part of this site plan and attaching them to it does not limit the amount of information that is required to be within the proposed site plan itself. The attached documents will not be considered, or kept, as part of the approved site plan packet. Comment noted. We will still keep them included. Michael Dellinger — CDD Inspections 2020-03-25: Initial comment: "no objection" 2020-05-22: Comment Revised: Provide a description of what the temporary building will be used for. Additional comments may be required depending on the use. Temporary Building has been removed from the scope of work. L I N E GRADE 113 4`h STREET NE, STE. 100 CHARLOTTESVILLE, VA 22902 LINE-GRADE.COM