Loading...
HomeMy WebLinkAboutWPO202000004 Review Comments WPO VSMP 2020-08-03�A COUNTY OF ALBEMARLE Department of Community Development „P 401 McIntire Road, Room 227 Charlottesville, Virginia 22902-4596 Phone (434) 296-5832 Fax (434) 972-4126 VSMP Permit plan review Project title: Brookhill Blocks 9-11 Project file number: 3AIP0201800086(illrnow WPO20200004(rev 1 and on) Plan preparer: Collins Engineering — Scott Collins [scott@collins-engineering.com] Owner or rep.: Riverbend Development — Alan Taylor [alan@riverbenddev.com] Rev. 1 received: 21 Jan 2020 Rev. 2 received: 26 May 2020 Rev. 3 received: 01 July 2020 Rev. 1 comments: 28 Feb 2020 Rev. 2 comments: 12 June 2020 Rev. 3 comments: 03 Aug 2020 Reviewers: Emily Cox County Code section 17-410 and Virginia Code §62.1-44.15:34 requires the VSMP authority to act on any VSMP permit by issuing a project approval or denial. This project is denied. The rationale is given in the comments below. The application may be resubmitted for approval if all of the items below are satisfactorily addressed. The VSMP application content requirements can be found in County Code section 17-401. A. Stormwater Pollution Prevention Plan (SWPPP) The SWPPP content requirements can be found in County Code section 17-405. A SWPPP must contain (1) a PPP, (2) an ESCP, (3) a SWMP, and (4) any TMDL measures necessary. 1. SWPPP was not provided with this submission. Provide two copies of a SWPPP. If overall Brookhill SWPPP is to be used, provide updated registration statement and an overall sheet showing disturbed area covered by the registration statement. Rev. 1: 2 SWPPPs were provided, however coverage map was not provided. Is this intended to have its own DEQ permit? Or will the current riverbend development permit be revised to include this area? Please clarify. Rev. 2: Is the total acreage now 78.32? The area highlighted on the legend only shows an additional 4.88 acres with this plan, however the highlighted map shows 18.85 acres. Please clarify. Rev. 3: Comment not addressed. Per meeting on July 91, 2020, applicant is sending new registration statement and coverage map which will cover this project and WPO20170037 — amendment 2 which is anticipated to be approved at a similar timeframe. If not, a registration and map just for this plan must be submitted. 2. Rev. 2: Since this is going on the existing DEQ permit, the registration statement total area should match the total area, not only the area with this plan. The current permit is for 54.39 acres. Should the total now be 73.24 acres? Please clarify. Rev. 3: Same as comment above. B. Pollution Prevention Plan (PPP) The PPP content requirements can be found in County Code section 17-404. 1. PPP was not provided with this submission. Provide two copies of a PPP and ensure it contains everything as outlined in County Code section 17-404. If E&S plan is intended to be used for PPP, ensure it shows all requirements and provide a note stating it is also PPP. Rev. 1: Comment Engineering Review Comments Page 2 of 6 addressed. C. Stormwater Management Plan (SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is disapproved, and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17-403. 1. Professional seal must be signed and dated on the calculations package. Rev. 1: Comment addressed. 2. The Overall Brookhill Stormwater Quality Compliance Table must be updated and provided with this application. Rev. 1: Comment addressed. 3. [Sheet 2] Label the buffer as proposed greenway per the approved ZMA. There is no existing buffer. Also, update note 2. Ensure greenway is labeled consistently throughout plans. Rev. 1: Comment not addressed. 100' WPO stream buffer is still labeled on several sheets (5, 6, etc). Rev. 2: Comment addressed. 4. Please provide the following document on the plans: htta://www.albemarle.org/upload/images/forms center/departments/Community Development/fo rms/En ing eering_and_WPO_Forms/WPO_VSMP_Construction_ Record_ Drawings Policy 23M ay2014.pdf Rev. 1: Comment addressed. 5. Please note that since this plan does not include the proposed road connection to Ashwood Boulevard, an additional WPO Plan will be necessary for that road design before the associated road plan can be approved. Rev. 1: Comment addressed. 6. Ensure this TMP is covered by the existing SWM maintenance agreement. Otherwise, a SWM maintenance agreement will be necessary before plan approval. Rev. 1: Comment not addressed. Rev. 2: Comment not addressed. Applicant acknowledged and will get SWM agreement before plan approval. Rev. 3: Comment addressed. 7. Is the proposed SWM preservation easement area the forest and open space easement? Or is it the greenway that is to be dedicated to the county? If it is forest and open space, it should be labeled as SWM forest & open space and the following note should be on the plan and plat: "The SWM Forest and Open Space Easement is subject to the guidance set forth by DEQ in the Virginia Stormwater Management Program. The areas will remain undisturbed in a natural, vegetated state, except for activities as approved by the local program authority, such as forest management, control of invasive species, replanting and revegetating, passive recreation (e.g., trails), and limited bush hogging to maintain desired vegetative community (but no more than four times a year)." Rev. 1: Plat will need to be recorded showing this easement area (11.34 AC). The plat should have the same note. When will this plat be submitted? Rev. 2: The legend on Sheet 4 says SWM preservation area. Is this the SWM forest & open space? If so, please label it as that. If not, please clarify the areas and hatches. Rev. 3: Comment addressed. 8. Please show SWM facility easement around stormwater facility and access road. Rev. 1: Please label as SWM facility & access easement. Rev. 2: Comment addressed. 9. [Sheet 15] Show plan #, not just note stating, different set of plans. Rev. 1: Comment addressed. 10. [Sheet 16] Is outfall pipe from the pond 12" or 15"? It is shown as 15" in E&S, but 12" in SWM. Rev. 1: Comment no longer applicable. 11. [Sheet 15] Show design and drainage area for "proposed diversion associated with this set of plans..."Rev. 1: Comment no longer applicable. 12. [Sheet 15] Clarify the note stating that "two proposed adequate pipe outfalls... sub area less than 1%........ Show drainage areas for each and compare to the overall area. Also label/distinguish each concentrated outfall. This is slightly shown/labeled in the calculations packet for the outlet protection, however, it is very unclear on the plans. Rev. 1: Comment addressed. 13. [Sheet 15] Please distinguish drainage areas and outfalls with labels, such as 1, 2 3 or A, B, C. It I very confusing to read and follow. Rev. 1: Comment addressed. Engineering Review Comments Page 3 of 6 14. [calculations packet] There is only one drainage area shown (DA A), when this area is actually made up of several drainage areas? Rev. 1: Comment addressed. 15. [calculations packet] What is the Qdev for the SWM outfall? Calculations show it must be less than 0.14, but do not say what it is. Also, the flood protection states the same thing (post less than pre, but does not give any numbers) Rev. 1: Comment addressed. 16. [calculations packet] Please label remaining outlets (1-5) on the plans. Also, if these are just sheet flow, they are not "concentrated flow" and do not have to be analyzed. How is flood protection being addressed with these outlets, 1-5? The package only outlines channel protection. Rev. 1: Comment addressed. 17. [runoff reduction] Please clearly show the 35.34 acres and associated areas that are being used in the calculations. Rev. 1: Comment addressed. 18. [Sheet 161 Retaining wall design must be provided since it is part of the SWM facility grading. Rev. 1: Comment still applies. There are retaining walls surrounding the wet pond. Rev. 2: Comment not addressed. Applicant says plans are pending. Rev. 3: Comment addressed. 19. [Sheet 16] Provide safety bench and aeration for the level II wet pond per: https://www. swbmp.vwrrc.vt.edu/wp-content/uploads/2017/ 11 BMP-Spec-No-14_WET- PONDS vl-9 05112015.12dfRev. 1: Comment addressed. 20. [Sheet 16] Provide contour labels. Rev. 1: Comment addressed. 21. [Sheet 16] Provide outlet protection for the inflow to the pond. Rev. 1: Comment addressed. 22. Since there are no pipe/storm drain calculations, provide pipe design information for SWM facility outfall (size, capacity, flow, velocity). Rev. 1: Comment addressed. 23. Rev. 1: [Sheet 4, and others] SWM preservation area should be labeled as, "SWM forest & open space easement'. Rev. 2: See comment 7 above. It is shown correctly on other sheets, however, Sheet 4 still shows "preservation area" Rev. 3: Comment addressed. 24. Rev. 1: Nutrient credits must be purchased before land disturbance permit can be issued. Rev. 2: Comment not addressed. Rev. 3: Comment not addressed. 2.1 Ib/yr must be purchased. 25. Rev 2: [Sheet 17] Based on the water quality summary, WPO 201700037 Amendment 2 must be approved before this plan can be approved. Rev. 3: Comment not addressed. 26. Rev. 3: See attached ordinance that was recently adopted. This applies to all plans that are not currently approved. Ensure walls and grading meet these requirements. 27. Rev. 3: [Sheet 221 Please provide the excel spreadsheet for the VRRM. Also, please ensure pond B from WPO201700037 amendment 2 is included. 28. Rev. 3: Has disturbance to preserved slopes been changed? Per road plan SUB202000082, an exhibit was provided showing slopes less than 25%. This exhibit should be provided with this plan, referenced with a date/title/approval date of exhibit. Preserved slopes can be disturbed as shown on approved ZMA201500007. Ensure disturbance outside of what is shown on the ZMA is part of the slopes exhibit and is clearly shown on this plan. The exhibit should also have a professional seal and signature. 29. Rev. 3: Please provide an updated calculations packet. Even if no changes, should submit with each full submittal package and match the date of the plans. D. Erosion and Sediment Control Plan (ESCP) Virginia Code §62.1-44.15:55 requires the VESCP authority to approve or disapprove an ESCP. This plan is disapproved, and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. 1. [Sheet 3]: Ensure detail and notes for construction entrance match the design standards manual, page 8. Engineering Review Comments Page 4 of 6 http://www.albemarle.org/upload/images/forms center/departments/community development/for ms/design standards _manual/Albemarle _ County Design Standards_ Manual_2015-04- 25 draft.odf Rev. 1: Comment addressed. 2. Please clearly show limits of disturbance vs property line vs buffer lines vs drainage divide lines vs silt fence and tree protection lines. It is unclear in some locations. There is a note stating they are offset for graphic reasons, however, silt fence should be INSIDE the limits of clearing and grading because it requires disturbance for installation. Rev. 1: The limits of disturbance and the tree protection are too close to the preserved slopes. They should be offset (ideally 5 ft) in order to allow installation without disturbance to the slopes. Rev. 2: Comment addressed. 3. Per section 2.4.1 Greenway and 2.4.2 Buffers of the code of development, both the greenway and buffers shall not be located in any lots. Lots 1-12. 32-46 and 76-95 appear to have lot lines within buffers. Please revise. Rev. 1: Per 2.4.2 Buffers, in the code of development, buffers shall not be located within any private lot. Part of the Route 29 buffer is shown on lots (on sheet 11). Rev. 2: Comment addressed. 4. [Sheet 2] Please update Block 4B and road plan notes. Do not list under review, simply list the file #. Also note, the road plan is an SUB, not SDP. Rev. 1: Comment partially addressed. Road plan is SUB201700117, not SDP. Rev. 2: Comment addressed. 5. [Sheet 2] Show DB & PG for all existing, recorded easements. This includes easements associated with Block 4B, etc. Rev. 1: Easement text was there but is not legible. It is too small. Rev. 2: Block 4B easements are recorded and should have a DB&PG. Rev. 3: Comment addressed. 6. [Sheet 3] Dimensions for diversion channel crossing are not legible. Please increase the font size. Also, please distinguish between type A, B or V crossing. Rev. 1: Comment addressed. 7. [Sheet 3] The project description in the narrative states that 19.77 acres will be disturbed, while Sheet 5 states that 24.4 acres will be disturbed. Please clarify. Rev. 1: Sheet 3 narrative says 19.01 AC, sheet 17 says 18.85 AC and the registration statement says 19.77 AC. What is the total disturbed area? It appears to be 18.85 AC based on calculations. Please ensure everything matches. Rev. 2: Comment addressed. 8. [Sheet 4] Provide a north arrow. Rev. 1: Comment addressed. 9. [Sheet 4] Please label limits of construction. It appears that there is disturbance to preserved slopes and greenway, which is not allowed per the approved ZMA. Also, please show the buffer along 29 since this is an overall sheet. Rev. 1: Per 2.4.2 Buffers, in the code of development, buffers shall not be located within any private lot. Part of the Route 29 buffer is shown on lots (on sheet 11). Also, see comment 92 above regarding the location of E&S measures and their location adjacent to preserved slopes. Rev. 2: Comment addressed. 10. Provide drainage area to all silt fence showing that it meets the requirements of 0.25 ac per 100 ft of silt fence. Rev. 1: Comment addressed. 11. [Sheet 5] The diversion dike to sediment trap # 1 will not function. There is a low point in the southwestern comer of the drainage area (as drawn). Water will not flow to sediment trap # 1 as drawn. Please add additional control at the low point and revise drainage area and diversion dike to sediment trap #1. Rev. 1: Comment addressed. 12. Grading is shown in the buffer (greenway) and preserved slopes. This is only allowed as shown in the approved ZMA. Rev. 1: See comment 42 above regarding the location of E&S measures and their location adjacent to preserved slopes. Rev. 2: Comment addressed. 13. Are the project limits the same as the limits of construction? Please clarify. Rev. 1: Comment addressed. 14. Please clarify all hatches on the plan. A legend would be very helpful. Also a legend with drainage divide line, soil type line, etc would be helpful. Rev. 1: Comment addressed. 15. [Sheet 5] Note regarding 70' buffer at the top of the sheet is not sufficient. A sheet must show that there is no disturbance to the buffer. Rev. 1: Comment addressed. 16. [Sheet 7] There is work shown outside of the project limits line? Rev. 1: Comment addressed. Engineering Review Comments Page 5 of 6 17. [Sheet 7] Is the sediment trapping device for the construction entrance an existing trap? If not, show the proposed grading. Also, SF is currently shown going through this trap? Rev. 1: Comment addressed. 18. [Sheet 7] Provide design information for proposed culvert (drainage area, flow, velocity, size, etc). Also, show design information for proposed rip -rap outfall. Currently silt fence is also shown going through the rip -rap. Rev. 1: Comment addressed. Please note that this will need VDOT approval with the road plans. Please do not construct until you have VDOT approval. Rev. 2: Comment addressed. 19. [Sheet 7] 1:1 slopes are not allowed, even if temporary. Rev. 1: Comment addressed. 20. [Sheet 7] The outfall to sediment basin #1 is not completely shown. Provide matchline or adjust viewport. Rev. 1: Comment addressed. 21. [Sheet 7] Provide permit or note that permit is not required for work in the stream with the proposed culvert. Rev. 1: Comment addressed. 22. [Sheet 10] Please clarify or revise ST #4 vs ST #3. Rev. 1: Comment addressed, however, now there are two ST # 5 (the existing ST and then a new one in phase III?) Rev. 2: Comment addressed. 23. [Sheet 11] Proposed concrete washout is in the middle of proposed road? Rev. 1: Comment addressed. 24. [Sheet 13] Show tops and bottoms of proposed retaining wall. Rev. 1: Comment addressed. Please note that 6ft is the maximum allowed height. Some spots are exactly 6ft. This will be a zoning violation if they are over 6ft. Also, retaining walls that cross lot lines must be in easements and must obtain maintenance agreements. Rev. 2: Comment noted. Will be addressed on subdivision plat. 25. [Sheet 14] Drainage areas for traps and basins do not appear to match what is shown on the plan view sheets. Please clarify. Rev. 1: Comment addressed. 26. [Sheet 14] Weir length for ST #1 is calculated as 17 ft., but is shown as 6 ft. on the plans. Also, the storage area does not have a 2:1 length to width area. Please revise. Rev. 1: Comment addressed. 27. [Sheet 14] Outlet protection design table should show the flow and/or velocities that design of outlet protection is based on. Or add a note stating calculations are in the attached supplemental calculation booklet. Rev. 1: Comment addressed. 28. [Sheet 14] ST #2: The maximum embankment height should be 5' from the toe of the stone outlet. This appears to be 6ft. Please revise. Rev. 1: comment addressed. 29. [Sheet 16] Ensure trash rack includes anti -vortex device. Rev. 1: Comment addressed. 30. Rev. 1: [Sheet 5 & 141 SB 92 emergency spillway is over fill. Per the VESCH, page III-86, emergency spillway shall not be constructed over fill material. Rev. 2: Comment addressed. 31. Rev. 1: [Sheet 31 Please clarify and provide detailed sequence of construction. For example, all perimeter controls for Phase I cannot be installed until the culvert is installed and the stream can be crossed? Also, please note in step 412, ST # 5 is referenced to be installed. If ST #5 is existing, please revise, or change St #'s. Rev. 2: Comment addressed. 32. Rev. 1: The cover sheet says phasing: these blocks may be developed as 1 or 3 phases. Ensure those phases (and how they will be executed/built)are clearly outlined in the E&S plan. Rev. 2: Comment addressed. 33. Rev. 1: [Sheets 4, 5, 181 How will the Route 29 buffer be replanted adjacent to the SWM facility? There are 2:1 slopes within the 30ft portion that is allowed to be disturbed, however, it must also be able to be planted with shrubs and trees. Rev. 2: Comment addressed. 34. Rev. 1: [Sheet 71 There is silt fence shown across where construction traffic needs to travel? Rev. 2: Rev. 2: Comment addressed. 35. Rev. 2: [Sheet 111 Note near ST 46 still appears to reference ST 45. Please clarify. Rev. 3: Comment addressed. Engineering Review Comments Page 6 of 6 36. Rev. 3: Please add a note to the sequence requiring that preserved slopes be marked in the field before grading in that area begins. The VSMP permit application and all plans may be resubmitted for approval when all comments have been satisfactorily addressed. For re -submittals please provide 2 copies of the complete permit package with a completed application form. Engineering plan review staff are available from 2-4 PM on Thursdays, should you require a meeting to discuss this review. Process; After approval, plans will need to be bonded. The bonding process is begun by submitting a bond estimate request form and fee to the Department of Community Development. One of the plan reviewers will prepare estimates and check parcel and easement information based on the approved plans. The County's Management Analyst will prepare bond agreement forms, which will need to be completed by the owner and submitted along with cash, certificates or sureties for the amounts specified. The agreements will need to be approved and signed by the County Attorney and County Engineer. This may take 2-4 weeks to obtain all the correct signatures and forms. After bonding and agreements are complete, county staff will need to enter project information in a DEQ database for state application processing. DEQ will review the application information based on local VSMP authority approval. At this time, the DEQ portion of the application fees will need to be paid directly to the state. For fastest processing, this is done electronically with the emails provided on the application. DEQ should notify applicants with instructions on how to pay fees. When DEQ approves the application, they will issue a permit coverage letter. This should be copied to the county. After DEQ coverage is issued, via the coverage letter, the County can hold a pre -construction conference. Applicants will need to complete the request for a pre -construction conference form, and pay the remainder of the application fee. The form identifies the contractor and responsible land disturber, and the fee remaining to be paid. This will be checked by county staff, and upon approval, a pre -construction conference will be scheduled with the County inspector. At the pre -construction conference, should everything proceed satisfactorily, ajoint VSMP and grading permit will be issued by the County so that work may begin. County forms can be found on the county website forms center under engineering; bft://www.albemarle.org/deptforms.asp?departrnent--edengmTo ORDINANCE NO. 20-18(1) AN ORDINANCE TO AMEND CHAPTER 18, ZONING, ARTICLE Il, BASIC REGULATIONS, AND ARTICLE III, DISTRICT REGULATIONS, OF THE CODE OF THE COUNTY OF ALBEMARLE, VIRGINIA BE IT ORDAINED by the Board of Supervisors of the County of Albemarle, Virginia, that Chapter 18, Zoning, Article ll, Basic Regulations, and Article III, District Regulations, are hereby amended and reordained as follows: By Adding: Sec. 4.3.3 Grading standards By Amending: Sec. 30.7.5 Design standards CHAPTER 18. ZONING ARTICLE It. BASIC REGULATIONS 4.3.3 Grading Standards The following design standards apply to any land disturbing activity requiring a Virginia Erosion and Sediment Control Program (VESCP) application plan, or a Virginia Stormwater Management Program (VSMP) application plan, or both. A. Retaining walls. Retaining walls shall meet or exceed the following minimum standards: 1. Height. The maximum height for a single retaining wall, measured from grade to grade, shall be ten feet, except as provided in subsection (A)(3). When the overall retained height would exceed ten feet, the retaining wall shall be broken into multiple stepped walls. 2. Multiple stepped walls; separation. A minimum horizontal distance of three feet shall be maintained between each individual wall in a stepped wall system, and shall be landscaped with screening shrubs planted on ten foot centers. 3. Incorporation of wall into design of a building. Retaining walls may be incorporated into the design of a building so that they become part of the building. Retaining walls incorporated into the design of a building shall not be subject to height limitations of subsection (A)(1). B. Cuts and fills. Any cut or fill shall meet or exceed the following minimum standards: 1. Rounding off. Any cut or fill shall be rounded off to eliminate sharp angles at the top, bottom and side of regraded slopes. 2. Location of toe of the fill slope. The toe of any fill slope shall not be located within ten feet horizontally of the top of an existing or proposed cut slope. 3. Tops and bottoms. Tops and bottoms of cut and fill slopes shall be located either: (i) a distance from existing and proposed property lines at least equal to the lesser of three feet plus one -fifth (1/5) of the height of the cut or fill, or ten feet; (ii) any lesser distance than provided in subsection (13)(3)(i) the zoning administrator determines would not adversely impact the abutting parcel based on information provided by the owner of the abutting parcel; or (iii) on the abutting parcel if the owner obtains an easement authorizing the slope on the abutting owner's parcel. 4. Steepness. Cut and fill slopes shall not be steeper than a 2:1 (50 percent) slope. If the slope is to be mowed, the slope shall be no steeper than a 3:1 (33 percent) slope. C. Reverse slope benches or a surface water diversion. Reverse slope benches or a surface water diversion or both shall meet or exceed the following minimum standards: When required. Reverse slope benches or a surface water diversion or both shall be provided whenever: (i) the vertical interval (height) of any 2:1 (50 percent) slope exceeds 20 feet; (ii) the vertical interval (height) of any 3:1 (33 percent) slope exceeds 30 feet; or (iii) the vertical interval (height) of any 4:1 (25 percent) slope exceeds 40 feet. 2. Width and location of benches. Reverse slope benches shall be at least six feet wide and located to divide the slope face as equally as possible and shall convey the water to a stable outlet. Benches shall be designed with a reverse slope of 6:1 (approximately 17 percent) or flatter to the toe of the upper slope and have a minimum of one foot. The bench gradient to the outlet shall be between two percent and three percent, unless accompanied by appropriate design and computations. 3. Flow length within a bench. The flow length within a reverse slope bench shall not exceed 800 feet unless accompanied by appropriate design and computations demonstrating that the flow length is designed to be adequate to ensure the stability of the slope and prevent or minimize erosion. 4. Surface water diversions. Surface water shall be diverted from the face of all cut or fill slopes or both, using diversions, ditches, and swales, or conveyed downslope by using a designed structure. The face of the slope shall not be subject to any concentrated flows of surface water such as from natural drainage ways, graded swales, downspouts, or similar conveyances. (§ 30.7.5; Ord. 14-18(2), 3-5-14; § 4.3.3; Ord. 20-18(1), 7-15-20) State law reference — Va. Code §§ 15.2-2280(1), (2), 15.2-2286(A)(4). ARTICLE III. DISTRICT REGULATIONS Sec. 30.7.5 - Design standards. The following design standards apply to land disturbing activity to establish a use permitted by right or by special use permit in the steep slopes overlay district. A. Retaining walls. Retaining walls shall meet or exceed the following minimum standards: 1. Wall height. The maximum height for a single retaining wall, measured from grade to grade, shall be six feet, except as provided in subsection (A)(3). When the overall retained height would exceed six feet, the retaining wall shall be broken into multiple stepped walls. 2. Multiple stepped walls; separation. A minimum horizontal distance of three feet shall be maintained between each individual wall in a stepped wall system, and shall be landscaped with screening shrubs planted on ten foot centers. 3. Incorporation of wall into design of a building. Retaining walls may be incorporated into the design of a building so that they become part of the building. Retaining walls incorporated into the design of a building shall not be subject to height limitations of subsection (A)(1). B. Cuts and fills. Any cut or fill shall meet or exceed the following minimum standards: Rounding off. Any cut or fill shall be rounded off to eliminate sharp angles at the top, bottom and side of regraded slopes. 2. Location of toe of the fill slope. The toe of any fill slope shall not be located within ten feet horizontally of the top of an existing or proposed cut slope. 3. Tops and bottoms. Tops and bottoms of cut and fill slopes shall be located either: (i) a distance from existing and proposed property lines at least equal to the lesser of three feet plus one -fifth of the height of the cut or fill, or ten feet; (ii) any lesser distance than provided in subsection (b)(3)(i) the zoning administrator determines would not adversely impact the abutting parcel based on information provided by the owner of the abutting parcel; or (iii) on the abutting parcel if the owner obtains an easement authorizing the slope on the abutting owner's parcel. 4. Steepness. Cut and fill slopes shall not be steeper than a 2:1 (50 percent) slope. If the slope is to be mowed, the slope shall be no steeper than a 3:1 (33 percent) slope. C. Reverse slope benches or a surface water diversion. Reverse slope benches or a surface water diversion or both shall meet or exceed the following minimum standards: 1. When required. Reverse slope benches or a surface water diversion or both shall be provided whenever: (i) the vertical interval (height) of any 2:1 (50 percent) slope exceeds 20 feet; (ii) the vertical interval (height) of any 3:1 (33 percent) slope exceeds 30 feet; or (iii) the vertical interval (height) of any 4:1 (25 percent) slope exceeds 40 feet. Width and location of benches. Reverse slope benches shall be at least six feet wide and located to divide the slope face as equally as possible and shall convey the water to a stable outlet. Benches shall be designed with a reverse slope of 6:, (approximately 17 percent) or flatter to the toe of the upper slope and have a minimum of one foot. The bench gradient to the outlet shall be between two percent and three percent, unless accompanied by appropriate design and computations. Flow length within a bench. The flow length within a reverse slope bench shall not exceed 800 feet unless accompanied by appropriate design and computations 3 demonstrating that the flow length is designed to be adequate to ensure the stability of the slope and prevent or minimize erosion. 4. Surface water diversions. Surface water shall be diverted from the face of all cut or fill slopes or both, using diversions, ditches, and swales, or conveyed downslope by using a designed structure. The face of the slope shall not be subject to any concentrated flows of surface water such as from natural drainage ways, graded swales, downspouts, or similar conveyances. (§ 30.7.5; Ord. 14-18(2), 3-5-14; Ord. 20-18(1), 7-15-20) State Law reference— Va. Code §§ 15.2-2280 (1), (2), 15.2-2286 (A)(4). I, Claudette K. Borgersen, do hereby certify that the foregoing writing is a true, correct copy of an Ordinance duly adopted by the Board of Supervisors of Albemarle County, Virginia, by a vote of six to zero, as recorded below, at a regular meeting held on July /15, 2020. nfy'S � Clerk, Board of County u &FIsors�� Mr. Gallaway Ms. LaPisto-Kirtley Ms. Mallek Ms. McKee) Ms. Palmer Ms. Price Ave Y Y Y Y Y Y