RE: SDP202000015 Moores Creek Wastewater Treatment Plant — Minor Amendment
Dear Mr. Perez:
In response to your letter of review dated June 11, 2020, Hazen and Sawyer offers the following
responses to the comments for the above referenced project.
Review Comments / Responses
Department/Division/Agency: Planning
Reviewer: Christopher Perez
8/ 17/20
[Site Plan Amendment Policy] Revised sheet Cl to act as a legend to all of the other previous minor
amendments that have been approved (SDP2010-82, SDP2012-40, SDP2013-33, SDP2015-45). On
sheet C 1 please label the individual areas of each of the previous 4 minor amendments. Rev 1.
Comment not fully addressed. While a legend has been provided on sheet C1 to list all the
previous approved site plans, that areas of these site plans has not been denoted/marked on the
plans. Revise.
Hatch patterns on Location Map that correlate to Legend. Hatched areas are also called out
with project name and SDP number on Location Map.
6. [32.7.9.6] Landscaping. The parking area is required two large or medium shade trees. Please revise
the landscape sheet to provide these plantings. Rev. 1. Relocate the medium shade tree nearest to
the handicap parkin¢ space to the planting island in place of the Dwarf English Box Wood or
plant it closer to the parking area even with the light poles.
Per email correspondence with Christopher Perez, medium shade tree is to remain in shown
location due to existing utility conflicts.
7. [32.7.4.1, 32.7.4.2] Prior to site plan approval the WPO application must be approved. Rev. 1
Comment still applicable.
Noted.
8. [32.4.3.6, 32.4.3.2] The site plan shall not be approved until all other reviewers have approved the
plan. Their comments are attached. Rev. 1 Comment still applicable.
Noted.
9. [32.7.8, 4.7] Lighting. The light poles appear to interfere with the parking spaces. Please clarify by
either removing the light heads from the drawing or by labeling them as lighting heads. If these
Hazen
8/17/20
squares are not lighting heads the lighting poles should be moved back further from the parking lot as
to not interfere with the parking spaces.
Squares represented lighting head and have been removed from drawings. Only light pole is
shown.
Department/Division/Agency: ACSA
Review: Richard Nelson
Add a note added that the contractor is to contact ACSA 3 days prior to work on the ACSA water
main for the new fire hydrant.
Noted added to C104 — Utility Plan.
Department/Division/Agency: CDD ARB
Review: Khristopher Taggart
1. Revise the landscape plan to relocate the medium shade tree southwest of the parking island shown
on the plan to either replace the Dwarf English Box wood currently in the planting island or plant it
closer to the parking area even with the light poles.
Per email correspondence with Christopher Perez, medium shade tree is to remain in shown
location due to existing utility conflicts.
Department/Division/Agency: CDD Engineering
Review: Matthew Wentland
1. The VSMP (WPO202000008) will need to be approved before amendment approval.
Noted, in process of purchasing nutrient credits.
Department/Division/Agency: CDD Inspections
Review: Michael Dellinger
No Comments
Department/Division/Agency: Fire Rescue
Review: Shawn Maddox, 434-326-2623
No Comments
We trust these responses together with the associated revised drawings are sufficient to allow a complete
review and approval of our SDP application. If you have any questions, please contact me at
bedwards@hazenandsawyer.com.
Sincerely,
Bret Edwards, P.E.
Hazen and Sawyer