HomeMy WebLinkAboutSUB202000055 Correspondence 2020-09-25 (4)SHIMP ENGINEERING, P.C. Design Focused Engineering September 25, 2020 Emily Cox, PE County of Albemarle Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902 RE: Response Letter #1 for SUB202000055 Proffit Road Townhomes north — Engineering Dear Emily, Thank you for your review of the Road Plans for Proffit Road Townhomes North. This letter contains responses to County comments dated July 17, 2020. Our responses are as follows: 1. Road B must terminate at Road D to match the approved ZMA20180006. Also interconnectivity must be shown as illustrated on the same approved ZMA. ZMA20180006 is no longer applicable. Road B matches ZMA201900010 which was approved on September 16, 2020. Rev. 1: Velocity in storm pipe shall not exceed 15 ft/s. Per meeting with Justin Skimp, the county agreed to allow the velocity in this storm pipe to exceed 15ft/s. 3. Rev, 1: The trench drain should tie in with a manhole so there is a way to inspect or service the system. Acknowledged, we've added a structure for that connection which will allow the inspectors to access the outlet pipe. Please see Sheet C4. Rev. 1: [ Sheet C61 Trees should be ideally located at least 5 ft from a storm pipe. They cannot be centered on the pipe. Per a phone conversation with Justin Shimp, this comment was resolved so that the trees remain in their location. If you have any questions or concerns about these revisions, please feel free to contact me at keane(c-r�shimp-engineering.com or by phone at 434-227-5140. Regards, Keane Rucker, EIT Shimp Engineering, P.C. 912 E. High St. Charlottesville, VA 22902 1434.227.5140 1 shimp-engineering.com