To: Tim Miller (tmiller@meridianwbe.com)
From: Cameron Langille — Senior Planner II
Division: Planning Services
Date: May 1, 2020
First Revision: September 11, 2020
Second Revision: November 13, 2020
Thirs Revision: February 2, 2021
Subject: SDP202000029 — Woolen Mills Light Industrial Park— Major Site Plan Amendment
Albemarle County Planning Services (Planner) — Cameron Langille, blanig llegalbemarle.org —Required changes:
I . 132.4.2.1 (1)] The mailing notification fee of $215.00 has not been paid. The fee must be paid prior to approval
of the major site plan amendment. Rev. 1: Comment not addressed. $215.00 fee has not been paid. Rev. 2:
Comment addressed.
2. [32.5.21 Sheets C-101 and C-100 listed in the index were not included in the first submittal plan set. Please
provide these on the next submittal. Ensure that all information on existing conditions specified by Section 32.5.2
are included on the drawings. Rev. 1: Comment addressed.
3. [32.5.2 (a)] On Sheets C-203, C-205, C-206, and C-300, there is a callout referring to SDP1989-086. Please
explain what this is. Remove the note if necessary. Is this referring to SDP199900084? Rev. 1: Comment
addressed.
4. [32.5.2 (a)] Provide a list of all recorded plats and deeds that apply to the property on Sheet C-100, including
the new easement plat that will be recorded prior to approval of this major amendment. Rev. 1: Comment
addressed.
5. [32.5.2 (a)] Please state approved ZMA applications associated with this site in the Zoning note on Sheet C-
100. State that the Preserved Steep Slopes Overlay District was amended with ZMA201800017 as shown on its
application plan. Rev. 2: Comment addressed.
a. In the Steep Slopes notes on Sheet C-100, state that a 19, 645 sq. ft. area of the Preserved Steep Slopes
Overlay District was rezoned to Managed Steep Slopes with ZMA201800017. Rev. 1: Comment not
fully addressed. State the ZMA application number. ZMA201800017, in the Managed Slopes note 42.
Rev. 2: Comment addressed.
b. Add the approved Application Plan as an exhibit to the site plan drawings. Rev. 1: Comment addressed.
6. [32.5.2 (b)] The "Purpose of this Amendment" and Sheet Index on Sheet C-100 mention that this is proposing
changes to SDP201600076. However, the most recently approved plan for this site was SDP201800065. Clarify
which sheets from SDP20160007 and SDP201800065 are being revised with this plan. Rev. 1: Comment
addressed.
7. [32.5.2 (a)] Please show and label all minimum and maximum building and parking setback lines on
Sheets C-200 through C-205. The setbacks should be shown in accordance with Section 4.20 of the
Zoning Ordinance. Rev. 1: Comment not fully addressed, please label the 10' front minimum building
setback along Broadway Street on Sheets C-200 through C-205. Rev. 2: Comment addressed.
8. [32.5.1 (c)] On Sheet C-400, there are numerous easement labels that are overlapping and make the callouts
illegible. Please revise. Rev. 1: Comment addressed.
9. [32.5.2 (b) ] Please state the maximum lot coverage area for industrial uses proposed.
a. The Floor Area Ratio note on Sheet C-101 states that 125,205 sq. ft. of total floor area is proposed.
However, the total floor area proposed is 145,041 sq. ft. when building heights are factored in. Please
verify what the total floor area is and amend the plans as necessary. Rev. 1: Comment not fully
addressed. Staff is aware that building heights may change once users/tenants are identified. However,
the site plan figures should be consistent across drawings. Based on building heights shown, the total
gross square footage proposed at this time is 144,603 sq. ft. The floor area ratio calculation on Sheet C-
100 should state " 144.603 gross square footage/612.629 sq. ft. = 0.23 FAR." Please revise. Rev. 2:
Comment addressed.
10. [4.12.4 (a)] Please provide a parking calculation table on Sheet C-100. Revise the parking provided note so that
it also states "if additional parking is needed to comply with Section 4.12, approval of a site plan amendment
will be required to install additional parking." Rev. 1: Comment addressed.
a. State the total number of parking spaces, handicap spaces, and van accessible handicap spaces proposed
on the plan. Rev. 1: On Sheet C-200, please revise the label for parking spaces in front of Building 7.
There are 23 spaces provided, but the label states 21. Rev. 2: Comment addressed.
11. [32.6.2 (i) and 32.7.3 (b)] No ADA accessible handicap ramps are shown at the sidewalks adjacent to the ADA
striping next to handicap parking spaces in front of buildings 3, 12, and 14. Please revise the drawings so
handicap ramps are provided. Rev. 1: Comment addressed.
12. [32.5.2 (d)] Please show the locations of all Managed and Preserved steep slopes on Sheets C-200, C-201, C-
204, C-205, C-206, C-207, and C-300. Rev. 1: Comment addressed.
a. Add a legend to each drawing where these features are visible and label each feature. Rev. 1: Comment
addressed.
13. [32.5.2 (n)] It appears no sidewalks are proposed in front of Building 6. Sidewalks should be provided so that a
full sidewalk connection is located along the western edge of the travel way. Rev. 1: Comment addressed.
14. 32.5.2 (n)] Please provide sidewalks along the travel ways along Fords Road and the new access aisles that lead
into TMP 77-40M. A fully connected sidewalk network should be provided throughout the site. Rev. 1:
Comment addressed.
15. [32.5.2 (r)] Provide a Legend on each drawing showing all symbols and abbreviations visible. Rev 1: Comment
addressed.
16. [32.5.2 (b)] Per section 18-4.12.13, this site requires loading spaces. Please address the following:
a. Add a required loading space calculation to Sheet C-100. State the exact calculation from the Ordinance:
"Loading spaces required: one space for the first 10,000 square feet of industrial floor area plus one
space for each additional 20,000 square feet of industrial floor area." Rev. 1: Comment addressed.
17. [4.12.18 (d)] Please show how the loading spaces will be delineated (i.e. signage, striping, etc.) on the plans.
Rev. 1: Loading dock detail is detail 6 on Sheet C-306. On Sheets C-200 and C-201, please add a label at all
loading spaces that states the detail number and page number. Rev. 2: Comment addressed.
18. [32.5.2 (b)] In accordance with Section 18-4.12.13 (e), please show the dimensions for the dumpster pad and
associated improvements on all applicable drawings. Rev. 1: Comment addressed.
a. [4.12.13 (e) and 4.12.15 (e)] It appears that the dumpster pads shown at the dumpsters adjacent to
buildings 13 and 7 extend into the vehicular drive aisles. The 8' pad should be located so that it does not
impeded drive aisles. Please revise. Rev. 1: Comment addressed.
19. [4.12.19 and 32.7.9.7 (a)(3)] Please provide a plan and profile view detail with dimensions and materials of the
dumpster pad and enclosures to verify compliance with the screening requirements contained in the Zoning
Ordinance. Please note that fences or other constructed screening measures must be a minimum of six feet (6')
in height, as specified in 32.7.9.7 (e). Rev. 1: On Sheets C-200 and C-201, add a label stating the sheet and detail
number for the dumpster pad construction detail (detail 2 Sheet C-306. Rev. 2: Comment addressed.
20. [32.7.3 (b)] Please show the locations of all proposed mechanical equipment and utility hardware. Please provide
information so that the agent can verify they will be screened from public view. Rev. 1: Comment addressed.
21. [32.5.2 (k)] Please label all existing and proposed sewer and drainage easements by type and include a
size/width measurement.
a. An easement plat application must be submitted, reviewed, approved and recorded prior to major
amendment approval for all proposed easements. Rev. 1: Comment stands, easement plat not yet
submitted for review. Rev. 2: Comment stands. SUB202000174 has been submitted and is under
review. Once SUB202000174 is approved and recorded, update the site plan so that the recorded
instrument number is stated. Rev. 3: Comment stands. Once SUB202000174 is approved and
recorded, please update the site plan accordingly.
b. Once the easement plat is recorded, the major amendment must be revised to show the recorded
instrument number for the easement plat (deed book and page number). The newly created
easements will need to be labeled with a dimensional width, easement type, and state whether it is
public or private. Rev. 1: Comment stands, easement plat not yet submitted for review. Rev. 2:
Comment stands. SUB202000174 has been submitted and is under review. Once SUB202000174
is approved and recorded, update the site plan so that the recorded instrument number is stated.
Rev. 3: Comment stands. Once SUB202000174 is approved and recorded, please update the
site plan accordingly.
22. [32.5.2 (n)] On Sheet C-303, a detail is provided for a wood fence. Where is this wood fence used on the site?
It did not appear to be visible on any drawings. Rev. 1: Comment addressed.
23. [32.5.2 (e)] Please provide more details about the existing landscape features as described in Section 18-
32.7.9.4(c).
a. The Albemarle County Conservation Plan Checklist and Chapter 3.38 of the Virginia Erosion and
Sediment Control handbook is not completed or signed on Sheet C-305. The Conservation Plan
Checklist will need to be completed and signed by the owners to approval. Rev. 1: Comment not fully
addressed. The checklist is not completely filled out, and all sections must be check/filled out and signed
by the owner prior to approval of the site plan. Please revise. Rev. 2: Per applicant comment response,
letter owner will sign the checklist on Sheet C-306 once the major amendment is submitted for
final County signature and approval.
b. [32.7.9.4 (b)(1) and 32.7.9.4 (c)] Identify all existing trees, groups of trees with a 6" caliper or greater
in Existing Canopy Area B on the landscape plan. State the common name for the trees in callout. Rev.
1: Applicant comment response letter states 'Not required" for this comment. Per the previously
approved site plans, there are trees measuring between 8"-12" caliper in the canopy area that will be
preserved along Franklin/Broadway Streets, and existing trees measuring between 6"-12" in the canopy
area along Ford Road. Labels should be added stating the tree type and caliper in diameter at breast
height for existing vegetation that will be preserved. Rev. 2: Comment addressed.
24. [32.7.9.6 (a)] Some proposed planting areas do not include trees or shrubs. Each planting area must have some
sort of trees or shrubs provided in order to count toward meeting the minimum area required. Please revise
Sheets C-206 and C-207 as necessary. Rev. 1: Comment addressed.
25. [32.7.8 and 4.17] The major amendment does not include a lighting plan in accordance with the requirements
of Section 4.17 of the Zoning Ordinance. Please include a lighting plan on the next submittal and address the
following:
a. [4.17.4] The luminaire schedule and luminaire locations tables on Sheet C-403 state that 36 and 38 total
luminaires are proposed, respectively. Please verify the actual number of outdoor luminaires exceeding
3,000 lumens that are proposed and update the Lighting Plan as necessary. Rev. 1: Comment
addressed.
b. [4.17.4 (a)] Please provide documentation from the manufacturer such as manufacturer cut -sheets that
all proposed outdoor luminaries exceeding 3,000 lumens are full -cutoff fixtures. Rev. 1: Comment
addressed.
c. Please add a note to the lighting plan which states "Each outdoor luminaire equipped with a lamp that
emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to
reflect light away from adjoining residential districts and adjacent roads. The spillover of lighting from
luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed
one-half footcandle." Rev. 1: Comment addressed.
26. [32.6.2 (d) and Chapter 14] Please submit an easement plat and application to the County that shows all new
easements proposed by the site plan. This includes all new drainage, stormwater, public access easements, etc.
The easement plat must be reviewed, approved, and recorded prior to approval of the final site plan. Detail 2 on
Sheet C-400 will need to be updated so that it states the recorded instrument number once the plat and associated
deeds are recorded. Rev. 1: Comment stands, easement plat not yet submitted for review. Once the easement
plat is approved and recorded, update the site plan as necessary. This includes revising note #2 under "Purpose
of this Amendment" on Sheet C-100 so that it states that new easements were recorded in DB pages
Update easement labels on Sheets C-400 through C-402 so that all easements are "existing" and include the
recorded instrument in the easement labels. Rev. 2: Comment stands. SUB202000174 has been submitted and is
under review. Once approved and recorded, update the major amendment as necessary. Rev. 3: Comment
stands. Once SUB202000174 is approved and recorded, please update the site plan accordingly.
27. [General Comment] Prior to final site plan approval, a WPO plan must be submitted, reviewed, and approved
by the Engineering Division. Please see Engineering comments below for additional information. Rev. 1:
Comment stands. See Engineering comments. Rev. 2: Comment stands. see Engineering Division comments.
Rev. 3: Comment stands, please see Engineering Division comments.
28. [General Comment] This site lies in the Monticello Viewshed. Please contact Liz Russell at
lrussell@monticello.org to discuss design strategies that comply with the Voluntary Guidelines for Development
within Monticello's Viewshed. Rev. 1: Applicant acknowledges this comment.
29. [General Comment] The new vehicular travel way leading into the site extends into TMP 77-40M. Please see
the attached letter from that property owner. Rev. 1: Site layout has been revised and portions of this comment
are no longer applicable, see new comment #30 below.
a. There is an existing ingress/egress and temporary construction easement platted in DB 4797, pages 416-
427 which was recorded on August 1, 2016. Per the deed recorded in the instrument, all construction
work within the limits of disturbance as shown on the plat shall be completed within 4 years from
recordation. This means that unless an agreement is made between both property owners, that easement
is only valid until August 1, 2020. Rev. 1: Site layout has been revised and portions of this comment
are no longer applicable, see new comment #30 below.
b. The major amendment may not be approved by August 1, 2020. The applicant needs to work with the
owner of TMP 77-40M to come up with a solution to this issue, such as recording a new easement and
agreement regarding improvements on TMP 77-40M. The County cannot and will not assist in private
negotiations regarding this issue, as it is a private matter. Please provide documentation that a revised
agreement is being worked on between the property owners. Rev. 1: Site layout has been revised and
portions of this comment are no longer applicable, see new comment #30 below.
c. A new easement allowing grading and construction and access through TMP 77-40M will need to be
included on the easement plat mentioned in comment #24 above. Rev. 1: Site layout has been revised
and portions of this comment are no longer applicable, see new comment #30 below.
New Comments First Revision & Second Revisions:
30. [General Comment] The site layout has been revised so that no "front road" travel way access is proposed
between TMP 77-40B and 77-40M. No further comments are necessary regarding the front road interconnection
shown on the first version of this major site plan amendment. However, there are still outstanding issues related
to the "side road" interconnection, see below:
a. Albemarle County staff were forwarded a letter from the Sixteenth Judicial Court, dated July 17, 2020,
concerning a preliminary injunction that has been imposed regarding the access easements recorded in
DB 4797, pages 416-427. Please address the following:
i. The letter states that the Court "GRANTS plaintiffs motion for temporary injunction enjoining
the defendant from developing the side road until further order of the Court." The plaintiffs are
the owners of TMP 77-40M. The revised site plan dated July 16, 2020 shows a side road being
provided through TMP 77-40M that will connect to the Ford's Road private travel way within
77-40B. Although the major amendment shows a steel gate at the end of the side road, the
County cannot approve the major amendment with any side roads until further documentation
and confirmation is provided that this legal matter has been resolved. Has further Court action
taken place allowing the owners of TMP 77-40B to construct the side road as proposed? Rev.
2: The site plan has been revised so that a 3' wide landscaping strip is provided between the end
of the pavement and the side road. There are currently five (5) shrubs in the strip, which will
partially preclude the side road from being used to access the entirety of the site. However,
please show additional shrubs in the gaps. There appears to be space to add three (3) additional
shrubs within the strip without conflicting with the HDPE pipe. Rev. 3: Comment addressed.
ii. The County is not a party to this dispute since this is a private easement between the owners of
TMP 77-40 M and 77-40B. However, it appears that there is a factual error or misunderstanding
between the plaintiffs and defendants in this matter that is reflected in the Court's letter. Under
"Likelihood of Success on the Merits" section of the letter, the Court states "The current plan
which has been approved by Albemarle County shows that it is possible to access the entirety of
the industrial park according to the testimony of Kevin O'Brien, He was the signatory for
Elemental EcoTech Inc. on the Deed of Easement. He agrees the approved plan allaws for the
side road to access the entirety of the property because the roads physically interconnect."
Please be aware that none of the previously approved site plans for TMP 77-40B showed a side
access road that allowed access to the entirety of the site. The only plan approved by Albemarle
County that even showed the side access road was the original final site plan (SDP201600076).
The side road only provided vehicular access to a single building (identified as Building 12 on
that plan), and no further access was extended to other portions of the development. Please be
aware of this fact in future legal proceedings regarding the easement. Rev. 2: This portion of
the comment was for information purposes only.
31. [General Comment] Please see the attached recommendation from the County's Historic Preservation reviewer.
Virginia Department of Historic Resources (VDHR) records indicate that archaeological resources have been
discovered on the southern portion of this property and there is potential that the site could contain significant
additional archaeological deposits, and potentially human remains. It is recommended that an archaeological
survey be completed prior to any ground disturbance south of Moore's Creek Lane to protect any buried
resources and the information they contain relative to our local history. Note that this is a County
recommendation, not a requirement. If this project requires any federal permits, however, VDHR review will be
required. Rev. 2: Comment was advisory.
32. See attached VDOT comments. The labels for Broadway Street currently list it as a private street ROW.
However, it appears that a portion of Broadway Street is in the public system as Route 1115, according to VDOT
comments. Planning staff conducted further research into this matter, and found a plat recorded in DB 4893,
pages 401-405 that identifies a portion of Broadway Street as a 56' wide public access easement/public ROW,
per instrument recorded in DB 675, page 326. Please address the following:
a. Revise Broadway Street labels so that it states that it is a public street and state recorded instrument
number. Rev. 3: Comment addressed.
Please contact Cameron Langille at the Department of Community Development at blanig Ile@albemarle.org or 296-
5832 ext. 3432 for further information.
Comments From Other Reviewers:
Albemarle County Engineering Services (Engineer) —David James, diames&albemarle.org— Requested changes, see
attached.
Albemarle County Service Authority — Richard Nelson, melson@serviceauthority.org — See attached
recommendation.
Rivanna Water & Sewer Authority (RWSA) — Dyon Vega, dvega@rivanna.org — Review not yet complete, comments
or approvals will be forwarded to the applicant upon receipt.
Virginia Department of Transportation— Max Greene, max. rg eene@vdot.vir ig nia.gov —Review not yet complete,
comments or approvals will be forwarded to the applicant upon receipt.
PROJECT: SDP202000029 Woolen Mills Industrial Park -Major Site Plan Amendment -Rev. 3
Engineering comments (David lames):
1. Submit a new WPO plan amendment (Approval required prior to this site plan amendment
approval). Disturbed area, impervious cover, drainage patterns, etc. have changed.
(Rev.1) Not currently addressed.
(Rev.2/3) WPO has not been approved yet.
2. Cover:
F:..I.J verify site a....egFa..1...within the 1a« VeaF C...F....:.Je date 5121
b. Provide ADT projected traffic information.
(Rev.1) Addressed.
3. Sheet 2 & 3 missing - Provide Existing Conditions sheets.
4. Areas of off -site disturbance need to be shown in an easement. A letter of permission from an
off -site property owner is sufficient as an easement in this case, but only for the purposes of
plan review. Bonds will need to be signed by the owners of all properties on which construction
takes place, or legal easements will be needed.
(Rev.1/2/3) Acknowledged. Easement plats to be reviewed, recorded prior to plan approval.
5. 5neet u, ,.
a. Show travelway arrow movements. (Rev.1) Addressed. -Sheet 1,
b. Provide 24' travelway width along Ford's Road where next to perpendicular parking &
where feasible. -10' parking space, previous amendment shows 10' S/21 (Rev.1)
Addressed.
c. Show access easement. (Rev.1) Acknowledged. See #4 above.
d. Show 25' (min) entrance radius. (Rev.1) Addressed.
e. Provide 3' buffer strip behind back of curb along Ford's Rd. (Rev.1) Addressed.
f. Add CG-12 at these locations: (Rev.1) Addressed.
g. Update note 2 so that it reads 30" instead of 36". (Rev.1) Addressed.
6. Provide guardrail at these locations: (Rev.1) Addressed.
7. Sheet 6/7: Label all proposed contour elevations for clarity. (Rev.1) Addressed.
a. (Rev.1) Connector convey flow from trench drain.
(Rev.2) Addressed.
8. Callout & provide profile of structures: (Rev.1) N/A.
9. Sheet 10: Label slopes greater than 3:1. (Rev.1) Not fully addressed.
a. (Rev.1) Label callout to detail sheet.
(Rev.2) Addressed.
10. Sheet 12:
a. Show the limits of disturbance. (Rev.1) Acknowledged - made the comment so I can
assess any runoff from site not captured.
b. Show the DA line & acreage for buildings 1, 10 &14. (Rev.1) Addressed.
c. Provide overland relief for Str. 3 in case of clogging. (Rev.1) Acknowledged.
d. (Rev.1) Show drainage area for building 11; SWM pond sub -area. (Rev.2) Addressed.
e. (Rev.1)Show drainage areas for trench drains. (Rev.2) Addressed.
f. (Rev.2) It's not clear which DI will pickup the drainage from buildings 2, 3, 4, 11, 13.
(Rev.3) Addressed.
11. Sheet
a. Laoei pipe runs Tor the profiles. (Rev.1) Acknowledged, Example:
(Rev.2) Not addressed. Not able to find Stm str. 28 thru 30; Str. 15, drainpipe to 15,
drainpipe to 18 information missing.
(Rev.3) Acknowledged.
b. Provide IS-1 for any structure with a 4' or greater drop. (Rev.1) Acknowledged.
c. Provide SL-1 in any structure taller than 12'. (Rev.1) Addressed.
d. Show ES-1 or EW-1 on all pipe outlets. (Rev.1) Addressed.
e. Show HGL in the profiles. (Rev.1) Addressed.
f. Velocity is excessive in pipe Str. 8-8A (>20fps). (Rev.1) Addressed.
g. Provide anchors per VDOT standard (pipes over 16% slope). (Rev.1) Addressed.
h. (Rev.1) Provide IS-1 at STM 5, 6, 11, 16, 18; IS-1 in structures where intersecting flows
occur. (Rev.2) Addressed.
i. (Rev - - mislabeled, Pipe 118, 124 not labeled, Inv. missing to Str.
15 (Rev.3) Addressed.
j. (Rev.3) The rim elev. for Str-34 should be above the finished grade.
k. (Rev.3) Indicate two 42" pipes for SWM-2 or show profile for each.
12. Parking places to be separated trom entrances and streets (to prevent queuing onto streets) a
min. 18' from back of entrance radius [VDOT, Apx. F, throat length & corner clearance].
(Rev.1) Not applicable anymore; entrance change.
13. Sheet 16:
a. Provide stationing for Ford's Road beyond 21+50 to the intersection with parking. -
May need to intersect Broadway - TBD. (Rev.1) Addressed.
b. Provide sight distance triangles and show sight distance easements at all travelway
intersections. (Rev.1) Show sight distance lines at upper entrance Broadway St.
(Rev.2) Addressed.
c. Show design speed. (Rev.1) Addressed.
d. Provide VDOT's Flexible Pavement Design worksheet for the pavement design.
(Rev.1) Acknowledged.
e. Provide Autoturn exhibit for all vehicle travelways. (Rev.1) Addressed.
f. Turning radius does not appear to meet minimum specs. (Rev.1) Addressed.
14. (Rev.1) Sheet 18: Provide channel design (2yr & 10 yr), show cross -sections and lining type
used to meet velocity requirements. Provide profiles of the longer channels on sheet 13.
(Rev.2) Addressed.
15. (Rev.1) Certified structural designs needs to be submitted for retaining walls prior to plan
approval. This includes walls in/adjacent to roads / parking area & where walls greater than 4'
height & where utilities are proposed to cross. (Rev.2) Acknowleged.
16. (Rev.2) Ensure 100% capture at entrance so runoff does not flow goes out into travel lane.
(Rev.3) Acknowledged.
17. (Rev.2) Ensure there's adequate space behind SWM retaining wall. Show tie -backs installation
won't cross property line; otherwise, a temporary construction easement will need to be
recorded.
(Rev.3) N/A Addressed.
18. (Rev.3) Show/Label proposed SWM facility easements on the site/grading plan.
Easement should be shown outside of Public R/W. For underground detention
system show that easement width equals 10'{landing)+(pipe diameter)+2'+2(H-5').
[ACDSM, p.15]
Cameron Langille
From: Richard Nelson <rnelson@serviceauthority.org>
Sent: Tuesday, January 26, 2021 4:44 PM
To: Cameron Langille
Subject: RE: Transmittal of SDP202000029 Woolen Mills Light Industrial Park Major Amendment
- 4th Review
CAUTION: This message originated outside the County of Albemarle email system. DO NOT CLICK on links or open
attachments unless you are sure the content is safe.
Cameron,
The applicant should submit 3 copies to ACSA for administrative approval. Last I heard, comments have been addressed,
but need to a set in our office to approve.
Thanks,
Richard Nelson
Civil Engineer
Albemarle County Service Authority
168 Spotnap Road
Charlottesville, Virginia 22911
(434) 977-4511
From: Cameron Langille <blangille@albemarle.org>
Sent: Monday, January 4, 20215:29 PM
To: David James <djames2@albemarle.org>; Richard Nelson <rnelson@serviceauthority.org>; Max Greene
<max.greene@vdot.virginia.gov>; vfort@rivanna.org; Dyon Vega <DVega@rivanna.org>
Cc: Brenda Loving <Brenda.Loving@vdot.virginia.gov>; Adam Moore <Adam.Moore @vdot.virginia.gov>
Subject: Transmittal of 5DP202000029 Woolen Mills Light Industrial Park Major Amendment - 4th Review
Good evening,
This major amendment has been submitted for its 41h review. Attached is a PDF of the applicant comment response
letter.
You can access the revised plan through County View, the file was too large to send via email. The revised site plan file is
dated 01/04/2021 in County View. You can access the file using this link:
https:Hlfweb.a I bemarle.org/webl i n k/sea rch.aspx?d bid=3&sea rchcom ma nd=%7b%5 bCDD-
P la nni ng%5d:%5 bAppl icatio n N um ber%5d=%22SDP202000029%22%7d
Please send me any comments or approvals by Tuesday, January 26, 2021. Please let me know if you have any questions.
Thanks,
Cameron
Cameron Langille
(pronounced "LAN-JILL")
Senior Planner 11
Albemarle County
blangille@albemarle.org
434-296-5832 x3432
401 McIntire Road, Charlottesville, VA 22902