Memorandum
To: Scott Schiller
From: Christopher Perez,Senior Planner
Division: Planning
Date: REVISED September 9,2020
Subject: SDP202000046 Moores Creek Wastewater Treatment Plant(Lighting Plan)-Minor Amendment
The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have
been satisfactorily addressed(The following comments are those that have been identified at this time.Additional comments or
conditions may be added or eliminated based on further review.):[Each comment is preceded by the applicable reference,which is to the
Subdivision/Zoning Ordinances unless otherwise specified.]
1. [32.5.1(c),32.7.8,4.7]Lighting.Increase the width and boldness of all property lines so they are easily distinguishable from other
lines on the plan.Rev 1.Comment addressed.
2. [32.5.2(n)] Outdoor Lighting.On the plan provide cut sheets for all proposed light fixtures.Ensure they are clearly labeled.Rev 1.
Comment addressed.
3. [32.5.2(a),32.7.8,4.7]Lighting.On the cover sheet clearly label which parcels are included in the lighting plan.It is not clear which
tax map parcels are part of the site plan amendment.Rev 1.Comment addressed.
4. [32.7.8,4.7]Lighting.Utilize a Light Loss Factor(LLF)of 1 for the revised lighting plan.List the LLF utilized on the plan.Rev 1.
Comment addressed.
5. [32.7.8,4.7]Lighting.Identify and label the existing and the proposed light poles and light fixtures.Rev 1.Comment addressed.
6. [32.5.2]On the cover sheet provide the following "SDP202000046 Moores Creek Wastewater Treatment Plant(Lighting Plan)-
Minor Amendment" Rev 1.Comment addressed.
7. [32.4.3.6,32.4.3.2]The site plan shall not be approved until all other reviewers have approved the plan.Their comments are
referenced below and attached.Rev 1.Comment still relevant.
8. [32.7.8,4.7]Lighting.The photometric plan is not legible.The spillover numbers cannot be read.Resubmit this plan with legible
spillover numbers.I think when the electronic file was flattened the details were lost,thereby making it not legible.
9. [32.7.8,4.7]Lighting.The cutsheets are not all legible.I think when the electronic file was flattened the details were lost,thereby
making it not legible.Resubmit this plan with legible cutsheets.Additionally,staff was unable to locate cutsheets for the following
fixtures:VFX-L,PWM,PXHW WDU.Ensure cutsheets for these are provided and clearly labeled.
ARB—Khris Taggart
1.Revise the plan to include manufacturer's cut sheets for all light fixtures.Staff was unable to
locate cutsheets for the following fixtures:VFX-L,PWM,PXHW WDU.Ensure cutsheets or photographs,if cutsheets are unavailable,
are provided for these fixtures.
2.A number of the illumination values(maximum values,spillover values,etc.)provided on the photometric plan are not legible.
Resubmit this plan with all illumination values legible.
3.Provide information on the lamps that indicates the wattage on fixtures where the cutsheet information is unavailable.
Zoning—Lisa Green
1.Make sure that there is a 100%complete inventory.Our major concern is getting a cut sheet for each fixture and lamp to make sure
they are full cutoff.Also,what we asked for is a list of fixtures and poles that were existing and an approximate date of the installation or
replacement of the new lighting for each fixture.
1
. o
Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the
County Attorney's office.The Code may found on the County Attomey's website which may be found under"Departments and
Services"at Albemarle.org.In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a
revised final site plan to address all of the requirements within six(6)months after the date of this letter the application shall be deemed
to have been voluntarily withdrawn by the developer.If you have any questions about the comments please feel free to contact me.
Please contact Christopher Perez in the Planning Division by using cperezPalbemarle.org or 434-296-5832 ext.3443 for further
information.
2
Review Comme. ;S for SDP202000046 Pinar Amendment
Project Name MOORES CREEK WASTEWATER TREATMENT PLANT-MINOR-DIGITAL
Date Completed:Liursday, September 03, 2020 DepartmentlDivision/Agency: Review Status:
Reviewer Khristopher Taggart U CDD ARB j Requested Changes
9/3t20:
1. Revise the plan to include manufacturer's cut sheets for all light fixtures_ Staff was unable to
locate cutsheets for the following fixtures: VFX-L, PWfvl, PXHW WDU. Ensure cutsheets or photographs, if cutsheets are
unavailable, are provided for these fixtures.
2_A number of the illumination values (maximum values, spillover values, etc.) provided on the photometric plan are not legible.
Resubmit this plan with all illumination values legible.
3. Provide information on the lamps that indicates the wattage on fixtures where the cutsheet information is unavailable.