Loading...
HomeMy WebLinkAboutSDP202100044 Action Letter 2021-06-28COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902-4596 Phone (434) 296-5832 Fax (434) 972-4126 June 28, 2021 Scott Collins 200 Garrett Street, Suite K Charlottesville VA 22902 RE: SDP 2021-44 Victorian Heights Initial Site Plan Mr. Collins: The Agent for the Board of Supervisors hereby grants administrative approval to the above referenced site plan. This approval shall be valid for a period of five (5) years from the date of this letter, provided that the developer submits a final site plan for all or a portion of the site within one (1) year after the date of this letter as provided in section 32.4.3.1 of Chapter 18 of the Code of the County of Albemarle, and thereafter diligently pursues approval of the final site plan. In accordance with Chapter 18 Section 32.4.2.8 Early or Mass Grading may be permitted after the following approvals are received: 1. Engineering approval of a VSMP plan meeting the requirements of Chapter 17 of the Code of the County of Albemarle. 2. Approval of all easements for facilities for stormwater management and drainage control. 3. Submittal of a tree conservation checklist with areas for tree preservation identified. The final site plan will not be considered to have been officially submitted until the following items are received: 1. A final site plan that satisfies all of the requirements of section 32.6 of Chapter 18 of the Code. 2. A fee of $1,500. 3. Revise the location of buildings 4 or satisfy the requirements of Chapter 18, Section 4.11.3. This buildings does not meet the minimum side setback requirement for non-infill projects as contained in Chapter 18, Section 4.19; "any dwelling unit that exceeds 35 feet in height shall be set back five feet plus one foot for each foot the dwelling unit exceeds 35 feet in height', The required setback is 30 feet. The setback appears to be 24 feet, however no dimension is provided on the plan. 4. Revise the location/dimensions of building 3 and 4 or obtain a special exception. These buildings do not meet the minimum building separation requirement for non-infill projects as contained in Chapter 18, Section 4.19; "any building that exceeds 35 feet in height shall be separated from any other building by ten feet plus one foot for each foot the building exceeds 35 feet in height'. The required building separation is 35 feet. The separation appears to be 30 feet, however no dimension is provided on the plan. 5. Revise the note for building separation between Lot 9 and Building 6. The note indicates the separation requirements is 10 feet. The required separation is 15 feet due to the height of building 6. 6. Building 2 must meet all setback, stepback and separation requirements or approval of special exceptions. No height is provided for this building on the initial plan. 7. Approval of special exceptions for stepback reduction for buildings 3 and 4. If no special exception is approved the buildings shall be modified to meet stepback requirements. 8. The area of Steep Slopes (managed) do not appear to correspond to the Zoning Map. The final site plan shall verify the location of the overlay district. 9. WPO plan satisfying VSMP requirements must be approved before final site plan can be approved. 10. Proposed slopes steeper than 3:1 must specify plantings that can withstand steep slopes. 11. Signed and sealed engineering plans for the retaining walls will be required before final site plan approval. 12. Indicate all proposed easements such as SWM facility and drainage. A Plat will be necessary to record proposed easements. 13. Trees shall not be over drainage pipes or SWM facilities. 14. All vehicle access aisles that are not adjacent to parking spaces shall not exceed a grade of ten percent. 15. Provide profiles for the travelways and the sight distance lines. 16. Clearly show where roll face and CG-6 will be used. Cross section on sheet 5 shows roll face on both sides of the 28 ft private travelway, however sheet 3 labels CG-6 on one side. 17. Ensure all radii and entrance types are labeled. 18. Sidewalk along Woodburn must be a minimum of 5ft wide. 19. Profiles and calculations will be necessary for the storm pipes and inlets. 20. To accommodate emergency/fire vehicle access, emergency vehicle access road(s)/route(s) are required. Fire apparatus access roads shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the buildings as measured by an approved route around the exterior of the buildings or facility. At final site plan phase, will calculate this distance to ensure this is met 21. There is a section of road/travelway that appears to decrease from 26 ft to 22 ft width for the travelway on the west side of the plans. Based on the heights of the buildings proposed, the travelway must be at least 26 feet width. 22. Based on the travelway width and the presented ROW width, no parkings signs will be required to establish the fire apparatus travel way so it remains unobstructed 23. There is a dead end on the east side of the plans that appears to be longer than 150 feet. Clarify this distance and if 150 ft or longer, provide an appropriate turn around 24. Provide a note on the plans of the calculated ISO fire flow for the buildings 25. Based on the fire flow calculation in comment above, provide appropriate number of hydrants separated by the required distance based on the fire flow required and show there locations on the plans (The larger the fire flow, the more hydrants that are needed and the closer they need to be to each other. At the lowest fire flow, they are required to be no more than 500 feet apart with no building more than 250 ft from a hydrant. AS the flow increases, the distances apart and from the buildings decreases) 26. Provide a note of flow test for hydrants 27. Submit a PDF and hard copies of the utility plan to ACSA for review. 28. RWSA approval will be required. See attached comments from RWSA for more detail. 29. Approval of the offsite sewer extension will be required prior to utility plan approval. 30. Offsite sewer easements will be required. 31. Utility plan approval will be required prior to final plat approval. 32. This site will require two (2) road names as noted in the screenshot below. Road A will need a name and Road B will need a name. 33. Provide right/left turn analysis for Woodburn Lane. 34. Provide additional detail and typical section for the parallel parking and the widening of Woodburn Lane. 35. Sidewalk must wrap around the left side of the proposed entrance on Berkmar Drive and cross the private travelway to tie into sidewalk. 36. Provide sight distance profiles for both public street entrances. 37. The required intersection sight distance on Woodburn Road is 390 feet. 38. Change labeling of dedication of right of way from VDOT to County of Albemarle. 39. Refer to VDOT's Road Design Manual, appendix F-pg., F-120, for commercial entrance designs along highways with curb and gutter. 40. Show geometry on proposed entrances, 25ft., min. width, and 301., radii. 41. Show on proposed taper a 12 foot offset from edge of pavement to end of radii for entrance onto Berkmar Drive. 42. Provide more detail on grading sheet. (See VDOT comments) 43. Provide drainage profiles on proposed drainage structures. 44. Final site plan mush show conformance with VDOT Road Design Manual Appendices B(1) and F, as well as any other applicable standards, regulations or other requirements. Please submit 8 copies of the final plans to the Community Development Department. The assigned Lead Reviewer will then distribute the plans to all reviewing agencies (for ACSA, please submit 3 copies of construction plans directly to them, as stated in their comments). Once you receive the first set of comments on the final site plan, please work with each reviewer individually to satisfy their requirements. The Department of Community Development shall not accept submittal of the final site plan for signature until tentative approvals for the attached conditions from the following agencies/reviewers have been obtained: SRC Members: Albemarle County Engineering Services (Engineer)- 2 copies [Emily Cox; ecox@albemarle.org] Albemarle County Planning Services (Planner)- 3 copies [Bill Fritz; bfritz@albemarle.org] 3 Albemarle County Planning Services (Architectural Review Board)- 1 copy [Margaret Maliszewski; mma I iszewski@al bema rle.org] Albemarle County Department of Fire Rescue- 1 copies [Howard Lagomarisino; hlagomarisino @albemarle.org] Albemarle County Service Authority- See comments for number of copies [Richard Nelson; rnelson @servicea uthority.org] Virginia Department of Transportation- 1 copy [Adam Moore; Adam. Moore@vdot.virginia.gov] If you have any questions about these conditions or the submittal requirements please feel free to contact me at Extension 3242, bfritz@albemarle.org. Sincerely, /' I � //- -/- - - William D. Fritz, AICP Development Process Manager 4