HomeMy WebLinkAboutSP201900006 Correspondence 2019-12-16 •SHIMP :ENGINEERING, RC.. Design Focused Engineering .December 16, 2019 Frank Pohl County Of Albemarle Department of Community Development 401 McIntire Road,North Wing. Charlottesville,Virginia 22902 RE: ZMA2018-01$ River's Edge Pump Station Preliminary-Design Dear Mr. Pohl, As part of the plan requirements,we have completed a basic preliminary design for the sewer pump stations. Flow Calculations: A design population of 100 2-person units has an average:design flow of 100 gpd/person=200 gpd/unit. (SCAT regs -:9YAC25-790-460-F). The design peak capacity of the system.shall be 2.5 times this avg. design flow. (SCAT regs:: 9VAC25-790-310-D) Avg Design Flow= 100.units x 200 gpd/units:=20,000 gpd Peak Design Flow=2.5 x Avg Design Flow= 50,000-gpd (34.7 gpm) Minimum design pump rate must exceed 35 gpm to allow for the Peak Design,Flow, Basic Pump Station Design: The pump station shall bean inline underground wet well with submersible pumps that will pump effluent through a force main at select times when the sewage level reaches set.elevations in the wet well. The pump station will consist of a remote monitoring system that will be.managed by a contracted professional third party, a backup generator in case of loss of power, and an.onsite alarm in case of failure. Preliminary Wet Well Sizing:' The wet well will be a 60"precast lined watertight manhole. For a wet well with 10'sdepth well and a .design lead pump switch"on" elevation at 4' above the invert,the Well storage would teach 540 gal. of effluent before the lead pump engaged. In this scenario,the pump would operate roughly 37 times per day (using the avg. design flow estimate of 20;000 gpd for the 100 units from above). With this basic design,the lead pump would engage on average every 39 minutes.This cycle period minimizes potential nuisance from the pump station by ensuring the sewage:does not sit long enough to go anaerobic and also ensures potential adverse noise impacts on future residents are mitigated:through cycle frequency management. 912 E..1 ighl:St.Charlottesville,VA 229021 434'.227.5140ii shutip-engirieerioq:Coin Additional Design Considerations: The following considerations are based on previous design experience with pump stations, and the final design shall account for these considerations. 1. Since the pump station will be handling raw sewage,pumps and force main must be capable of passing 2" solids. Thus, the minimum force main size should be 3". A minimum scour velocity of 2 fps must be achieved within the force main. 2. To remove cumbersome.maintenance requirements, submersible grinder pumps shall be used. 3. Two robust pumps shall be chosen to provide redundancy. Multiple switches shall be implemented which will trigger first one,then both pumps when sewer levels reach critical elevations within the wet.well. 4. CCS Tracer wire shall be installed along the force main to allow for maintenance to immediately identify the location from above ground. 5. To prevent unpleasant odors, which are mainly caused by sewage going anaerobic, a small air pump and diffuser shall be installed for the wet well. 6. Fencing and vegetative screening shall be provided to make the pump less conspicuous for residents. If you have any questions please do not hesitate to contact me at your convenience. I can be reached at: justin@shimp-engineering.com or by phone at 434-227-5140. Regards, Keane Rucker - keane@shimp-engineering: (434)299-9843 Copy:justin.@shimp-engineering.com