HomeMy WebLinkAboutSDP199900051 Approval - County 1999-05-06 ,
Albemarle County Development Departments SDP-1999-051
SPIN Submission and Comments The Boars Head Inn Major
Amendment
Fire/Rescue Major Site Plan Amendment revision 2
reviewer received reviewed decision
Bruce Crow 4/12/99 5/6/99 approved with conditions
Indicate the location of fire hydrants. Fire hydrants must be within 400 ft, by prepared travelway of the
building and within 100'of the fire department connection (Albemarle County Zoning Ordinance 32.7 6)
r/ Indicate the location of the fire department sprinkler connection. Fire department sprinkler connections
shall be accessible and visible from the travelway at all times. (Albemarle County Fire Prevention Code,
Section 6-200, F-518.3)
v/ Reviewing the landscaping plan would indicate that 24" Cherry Laurel will be planted in the area of were
the fire department connection will be located
Fire Lanes will be required Fire lane designated by signs and pavement markings as required by the Fire
Offical shall be placed in the area of the fire department connection location (Albemarle County Fire
Prevention Code, Section 9-7)
Review 5/6/99. Plan approved provided comments are addressed on final plan, Comment 2 &3 have
been addressed with comments 1 &4 still outstanding
5/17/99 01:30 PM Page 1 of 1