County of Albemarle
�l COMMUNITY DEVELOPMENT DEPARTMENT
GIRGIN��'
Memorandum
401 McIntire Road, North Wing Charlottesville,
VA 22902-4579
Telephone:434-296-5832
W W W.ALBEMARLE.ORG
To: Daniel Hyer (dhyer@line-grade.com)
From: Kevin McCollum — Senior Planner I
Division: Planning Services
Date: December 16, 2021
Subject: SDP202100083 Charlottesville Orthopaedic Minor Site Plan Review Comments
The Planner for the Planning Services Division of the Albemarle County Department Community Development will
recommend approval of the plan referred to above when the following items have been satisfactorily addressed. (The
following comments are those that have been identified at this time. Additional comments or conditions may be added or
eliminated based on further review.) [Each comment is preceded by the applicable reference to the Albemarle County
Code.]
Review Comments:
1. [32.5.2(a)] Please add the application number, SDP202100083, to the project title on Sheet C0.0.
2. [32.5.2(a)] Please amend the Planning History information on Sheet C0.0 to include a reference to minor site plan
amendment SDP198900047 and remove the reference to SDP199000093.
3. [32.5.2(a)] Please provide additional information to confirm the current owner. Albemarle County GIS lists the property
owner as 2275 Seminole Lane LLC at 2043 Thomson Rd Charlottesville, VA 22903.
4. [32.5.2(a)] Provide the total number of sheets under the sheet list table.
5. [32.5.2(a)] Add a date of revision to the submittal log.
6. [4.12.16(c)] It does not appear that the aisle widths are wide enough for the parking spaces fronting the property. The
aisle width for 9' x 18' parking spaces must be at least 24'. Revise accordingly.
7. [32.7.9.51 Please move the landscape legend slightly on Sheet C3.0 so that all landscaping labels are easily seen.
8. [32.7.9.61 Make sure all planting labels are correct. It appears there are some butterfly bushes missing a label and an
erroneous purple beautyberry label at the entrance to the site. In the upper right comer, there are additional butterfly
bushes and purple beautyberry shrubs missing labels.
9. [32.5.2 (s)] Please provide a project narrative on Sheet C0.0 that lists the proposed use and all site changes proposed
with this minor amendment.
a. No new easements are shown. Are any new easements proposed?
b. No new outdoor lighting is identified. Are any new outdoor lights proposed? This includes pole lights and
wall -mounted lights.
10. [32.7.8 and 4.171 Please identify the proposed locations and types of any new outdoor lighting that will be installed as
part of this project. The minor amendment should demonstrate compliance with all applicable site lighting requirements
of the Zoning Ordinance. This may include a lighting/photometric plan that identifies footcandle measurements within
the property and along the property lines.
a. Provide a schedule of proposed outdoor luminaires that identifies the luminaire type, wattage, lumens, pole
heights (if applicable), LLF (use 1.0 for calculations), etc.
b. [4.17.4 (b)(1)] The spillover of lighting from luminaires onto public roads and property in residential or
rural areas zoning districts shall not exceed one-half ('/z) foot candle. A spillover shall be measured
horizontally and vertically at the property line or edge of right-of-way or easement, whichever is closer to
the light source.
c. [4.17.4 (b)(2)] All outdoor lighting, regardless of the amount of lumens, shall be arranged or shielded to
reflect light away from adjoining residential districts and away from adjacent roads.
d. [4.17.4 (a)] All outdoor luminaires emitting 3,000 lumens or greater shall be equipped with a full -cutoff
fixture.
e. If no new outdoor lighting is proposed (this includes pole lights as well as wall -mounted lights on any
structures), then state this in the project narrative on Sheet C0.0.
11. [32.5.2 (k)(1), 32.6.2(g)] Any new easements required for water, sewer, drainage facilities, or any proposed utilities will
need to be reviewed, approved, and recorded prior to final site plan approval. Please submit an easement plat application
the County for review. The final site plan will need to be updated so that all easements are shown and labeled identifying
easement type, whether it's public or private, a width dimension, and the recorded instrument with deed book and page
number.
12. [32.5.2(a)] For any adjacent parcels visible on the drawings, please show the property lines and include a label stating
the owner name, TMP number, zoning districts, and present uses.
13. [32.7.9.7 (a)(3)] Please provide a construction detail in plan and profile view of the proposed dumpster enclosure.
The detail should identify materials to be used, color, dimensions, etc. Please be aware that walls used for screening
must be a minimum of 6' in height.
14. [General Comment] Please add the Site Review Committee (SRC) signature panel (attached) to the cover sheet.
15. [General Comment] Please show and label any existing easements and include their recorded instrument reference
(deed book and page number).
16. [32.7.9.41 Please show and label the existing trees and landscaping features on Sheet C3.0. Please provide additional
information on the existing vegetation on site. Is this a mix of deciduous, evergreen, or other plant material? Are
there trees and shrubs? Please provide caliper sizes of existing trees for trees/groups of trees with calipers greater than
6" diameter at breast height (DBH). Verify the locations, species, and sizes of all existing vegetation that will remain
and count toward the canopy.
17. [32.7.9.81 15,764 sq. ft. of existing canopy will remain and count toward the total site canopy required (as currently
stated on Sheet C4.1) the owner will need to sign the Conservation Plan Checklist and this will need to be added as an
exhibit to the Landscape Plan.
18. [General Comment] Ensure to show the extents of the rear property on Sheets C 1.0, C2.0, and C3.0.
Please contact Kevin McCollum at the Department of Community Development at kmccollum@albemarle.org or 296-5832
ext. 3141 for further information.
Comments from other reviewers:
Albemarle County Architectural Review Board —Margaret Maliszewski, mmaliszewski@albemarle.org —Requested
changes, see attached.
Albemarle County Building Inspections — Betty Slough, bslou hg &albemarle.org - Requested Changes, see below.
1. Add the following note to the general notes page:
All water, sewer and fire lines require NEW inspection and testing procedures. The ACSA performs any testing and
inspections of the public sewer and water main(s).
The Albemarle County Building Inspections Department (ACBID) does a visual inspection and witnesses the testing of
the building drain, water service pipe and the sprinkler lead-in connection.
The developer/contractor is responsible to retain a Special Inspector as outlined in the updated Albemarle County Policy
for Site Utilities to perform the visual inspection and testing of all utilities
not covered by the ACSA or ACBID. This includes building sewers, water and fire line branches between the main and
the meter(s)/building(s).
The Special Inspector's report must be submitted and approved by the Albemarle County Engineering Department prior
to a Certificate of Occupancy being issued.
Albemarle County Engineering Services —Matthew Wentland, mwentland@albemarle.org — No objection.
1. As the disturbance (outside of mill & overlay) is below 10,000sf, no VSMP plan is required. However, Engineering
recommends best practices be followed for erosion control during construction.
Albemarle County Fire Rescue— Howard Lagomarsino — hlaeomarsino@albemarle.org —Requested changes, see below.
1. Please provide a note on the plan indicating the ISO calculated needed fire flow for the building
2. Provide a note on the plan for the available fire flow at the hydrants(s) serving the structure
3. Hydrants are needed that provide the required fire flow and are spaced as required based on the needed fire flow
calculation
4. If a fire sprinkler system is installed, a hydrant needs to be located within 100 feet of the FDC for the system and
arranged so that when in use, it does not obstruct the travel way.
Albemarle County Service Authority — Richard Nelson, melsonkserviceauthority.org — Requested changes, see below.
1. Provide proposed fixture counts to confirm existing meter is adequately sized.
2. Show ACSA utilities on the landscape plan. Any trees should have a minimum 10-feet of separation from ACSA
utilities.
Virginia Department of Transportation (VDOT) — Douglas McAvoy, Jr., dou as.mcavoy@a,vdot.vir ig nia.gov — Review
pending. Comments will be forwarded to the Applicant upon receipt.
V
TO:
FROM:
RE:
DATE:
County of Albemarle
COMMUNITY DEVELOPMENT/PLANNING
MEMORANDUM
Kevin McCollum
MARGARET MALISZEWSKI
mmaIiszewski@albemarle.org
434-296-5832 ext. 3276
Margaret Maliszewski
SDP-2021-83 and ARB-2017-111: Charlottesville Orthopaedic Center
December 16, 2021
The ARB acted on the Charlottesville Orthopaedic Center on November 20, 2017 under ARB-2017-111. The
ARB's action was to approve the request, pending staff administrative approval of several conditions. Those
conditions are listed below. Revised site and architectural drawings addressing these conditions are required for
review.
1. Revise the elevation drawings to include a material/color schedule keyed to the elevations.
2. Provide paint samples for the two shades of grey that are proposed.
3. Reconsider the proposed colors to be more in keeping with the originally proposed color palette.
4. Clarify on the drawings where the charcoal grey metal is proposed to be located.
5. Provide the VLT and VLR of the proposed window glass. Add the standard window glass note to the
architectural drawings: Window glass in the Entrance Corridors should meet the following criteria:
Visible light transmittance (VLT) shall not drop below 40%. Visible light reflectance (VLR) shall not
exceed 30%..Specifications on the proposed window glass should be submitted with the application
forfinal review.
6. Revise the plan to show the location of mechanical equipment. Show that visibility of the equipment
will be eliminated.
7. Add the standard mechanical equipment note to both the site and architectural drawings: Visibility of
all mechanical equipment from the F,ntrance Corridor shall be eliminated.
8. Revise the plan to include a dumpster enclosure detail. Show that the enclosure is compatible with the
building design.
9. Revise the plans to clearly indicate all light poles to be demolished, relocated and/or retained. Show all
proposed lights. Provide a photometric plan. Show that all new and relocated fixtures meet ordinance
requirements. Shift lights and poles to allow for complete rows of shrubs along the parking rows.
Clarify and coordinate the notes regarding relocated light poles and relocated power poles.
10. Increase the planting size of the maples to 3'/z" caliper.
11. Show all utilities and their associated easements on the landscape plan. Resolve utility/landscape
conflicts without reducing the quantity of landscaping proposed.
12. Revise the spacing of the Kousa Dogwoods to 20' apart.
13. Add shrubs along the north and south parking rows.
14. Revise the plant schedule to show shrub planting size as 24" high.
15. Add the plant health note to the landscape plan: All site plantings oftrees and shrubs.shall be allowed
to reach, and be maintained at, mature height; the topping of trees is prohibited. Shrubs and trees
shall be pruned minimally and only to support the overall health of the plant.
WWW.ALBEMARLE.ORG
401 McIntire Road, Suite 228 1 Charlottesville, VA 22902-4596
16. Limit the number of proposed plants for any one species to a maximum of 25% of the total proposed
for that plant type.
17. Clarify the reason for the off -site shrubs. Provide evidence of an off -site planting easement.
18. Revise the site plan to show the sidewalk against the back of the curb to allow people to enter the
building more easily.
19. Consider alternative vegetation along the west elevation that better fits the available planting area.