HomeMy WebLinkAboutSDP202100098 Review Comments Final Site Plan and Comps. 2022-02-24�� pF AL8
County of Albemarle
Community Development Department - Department
Memorandum
To: Scott Collins, P.E., scott@collins-eneineering.com
Date: February 24, 2022
Re: SDP202100098 Brookhill Block 16 Final Site Plan - Review Comments
Cameron Langille
Principal Planner, Planning
blangille@albemarle.org
Telephone: (434) 296-5832 ext. 3432
The County of Albemarle Planning Division will grant or recommend approval of the plan referenced above once the
following comments have been addressed: [Each comment is preceded by the applicable reference, which is to the
Subdivision/Zoning Ordinances unless otherwise specified.]
Comments from Initial Site Plan (SDP202000070) Action Letter:
1. [ZMA201500007] The Code of Development (COD) requires a minimum of 50,000 sq. ft. of non-residential uses in
Block 1. Block 1 is the only block of Brookhill where non-residential uses are permitted. Per footnote #2 under Table 5
on page 15 of the COD, ancillary uses do not count toward the non-residential sq. ft. in each block. Therefore, only
2,650 sq. ft. of non-residential uses are proposed in Block 1. The note on Sheet 1 states that Block 1A + Block 1B
acreage = 12.673 acres. This means that all of the acreage allowed for Block 1 is being used with these plans, which
appears to make the future building labeled on this plan as not possible. Please clarify the true acreage of Block 113 in
order to verify that adequate area is available for future non-residential uses to meet the 50,000 sq.ft. minimum
required. First submittal: Comment addressed.
2. [32.5.2 (c)] Clarify the phasing note on Sheet 1. Where are the phase boundaries of the three sub -phases of Block 1?
Currently, only Phase 1 A and 1B are drawn. The layout drawings only label the proposed property boundary, which
appears to include areas where future buildings are shown. Are those buildings going to be constructed in a separate
sub -phase of Block 1? See Engineering comments for further information. First submittal: Comment addressed.
3. [32.5.2 (b)] Please revise and clarify the building footprint note on Sheet 1. According to Section 2.3.2.1 of the COD,
the maximum footprint allowed in Block 1 is 20,000 sq. ft. for non-residential uses and no maximum footprint for
residential uses. The note should differentiate between the maximum allowed non-residential and residential
footprints. First submittal: Comment addressed.
4. [32.5.2 (b)] Comment is for information only - per LOD201700025, the proposed ice rink is a by -right use in Block 1 as
an "ancillary use' and is not subject to the maximum building footprint limitation in the COD. The ice rink square
footage also does not count against the minimum/maximum non-residential use sq. ft. limits specified for Block 1 by
the COD. First submittal: Comment no longer applicable to Phase 1B final site plan. Ice rink is no longer proposed
within the limits of Phase 1B.
5. [ZMA201500007] Per Section 2.2.1 (page 9) of the COD, primary entrances for buildings in Block 1 must be located
on the front or side of the buildings. Please address the following:
a. Label primary entrances on all buildings. First submittal: Comment addressed.
b. Add sidewalks connecting the primary entrances to existing and/or proposed sidewalks along Archer Avenue
and Stella Lane as necessary. First submittal: Comment addressed.
6. [General comment] Please address the following on Sheet 3:
a. State the approval dates for SUB201700117 (11/16/2018). First submittal: Comment addressed.
WWW.ALBEMARLE.ORG
401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579
b. State the approval date for the preliminary plats for Blocks 16 and 17 (SUB202000141, 9/9/2020). First
submittal: Comment addressed.
c. State the approval date for the preliminary plat for Block 18 (SUB202000160,10/23/2020). First submittal:
Comment addressed.
d. If any other site plans, road plans, or plats are approved for other blocks prior to approval of the Block 1B final
site plan, update this sheet as necessary. First submittal: Comment stands pending further review and
approvals of this plan and plats/plans in other blocks of Brookhill. Prior to final site plan approval of
SD13202100098. Sheet 3 may need to be further revised.
[32.5.2 (b)] Per page 9 of the COD, 1 bicycle rack is required for every 5,000 sq. ft. of retail space. Please revise the
require bicycle parking calculation on sheet 1 so that it calculates the required parking based on the 2,650 sq. ft. of
retail space proposed in Block 1.
a. Move the bicycle rack closer to the residential/retail buildings. First submittal: Comment addressed.
b. Please label/title the construction detail provided for the bike rack on Sheet 10. First submittal: Comment
addressed.
8. [32.5.2 (a)] Label all minimum and maximum setback lines on the layout drawings. First submittal: Comment addressed.
9. [32.5.2(e)] Identify the types and sizes of the existing landscape features as described in section 32.7.9.4(c). First
submittal: Comment addressed.
10. [32.5.2(e)] On all plan view sheets provide labels identifying whether the existing wooded areas are composed of
evergreen, deciduous or a mix of types of trees. First submittal: Comment addressed.
11. [32.5.2 (1)] The private road extension of Stella Lane that is the main street within Block 1 must contain all features
shown on the cross-section identified as Figure 10: Connector Road and Main Street Road Cross Section (page 25) of
the COD.
a. The cross section provided on Sheet 10 is not consistent with the COD cross-section. No on -street parking is
provided. First submittal: The COD shows parking on both sides of the Main Street Road Cross Section (Figure
30 on page 25 of the COD). Currently, on -street parking is only provided on the north side of Stella Lane.
Staff acknowledges applicant's response regarding VDOT spacing requirements for in -bound traffic from the
roundabout at the Archer Avenue/Stella Lane entrance adjacent to Phase 113. Please be aware that future
extension of Stella Lane into Phase 1 will require parking on both side of the street. Curb cuts and entrances
should be planned accordingly so adequate spacing is available and on -street parking can be installed without
conflicting with VDOT requirements.
b. Draw and dimension the proposed bike lanes Along Stella Lane across all applicable drawings. See VDOT
comments for further information. First submittal: Comment addressed.
c. Provide on -street parking on the south side of Stella Lane. Currently, none are shown. First submittal: See staff
comment in comment #lla above.
12. [32.5.2 (1)] Prior to final site plan approval, a road plan application must be submitted, reviewed, and approved for the
extension of Stella Lane. First submittal, comment stands. See VDOT and Engineering comments for further
information.
13. [32.5.2 (1)] Please provide the recorded instrument numbers for existing Stella Lane, Archer Avenue, and Salamander
Street ROWS in the road labels across all applicable drawings. State the widths of the existing ROWS in the labels.
First submittal: Comment not fully addressed. See attached VDOT comment #3. ROW for roundabout at intersection
of Archer Avenue/Stella Lane is not shown correctly.
14. [32.5.20)] Provide the deed book and page references for all existing water, sewer, wastewater or storm drainage
systems easements that are located on the property. First submittal: Comment addressed. All existing easements as
WWW.ALBEMARLE.ORG
401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579
of 2/21/2022 are shown. See comment #15a below for further requirements that must be addressed prior to
approval of SDP202100098.
15. [32.5.2 (k)] Please show all proposed water, sewer, drainage, and stormwater easements on the final site plan and state
the easement type and width. First submittal: Comment stands.
a. Prior to final site plan approval, an Easement Plat Application must be submitted, reviewed and recorded. Once
recorded, the final site plan will need to be updated so that all new easement labels indicate the recorded
instrument number of the plat (deed book and page). First submittal: Comment stands.
16. [32.5.2(1)] Provide the location and width of any existing or proposed utilities and utility easements including
telephone, cable, electric and gas. Indicate the deed book and page reference for all exiting utility easements located
on the property. First submittal: Comment addressed.
17. [General Comment] Note 1 on Sheet 1 may need to be revised if any new easements will be private. First submittal:
Comment addressed.
18. [32.5.2(m)] Ingress and egress. Show the distance to the centerline of the nearest existing street intersection from the
propped ingress and egress. First submittal: Comment addressed.
19. [32.5.2 (n)] Where will the proposed 2,650 sq. ft. of retail space be located? Please state this in a note on the Cover
Sheet, and call out/draw the retail area within the building footprint on the layout drawings. First submittal: Comment
addressed.
20. [32.5.2 (n)] Please provide dimensions for all buildings, sidewalks, walkways, walls, etc. First submittal: There are areas
marked as ADA accessible routes across the parking lots that do not appear to be actual sidewalks. Please clarify
whether pedestrian striping is proposed along the ADA accessible routes. If not, additional pedestrian walkways
should be provided within the parking lot area to allow safe pedestrian travel from the apartment buildings to
handicap parking spaces, the dumpster area, etc. Please see attached Inspections Division comments for further
information regarding ADA requirements for parking, travelways, and accessible routes.
21. [32.5.2 (n)] Per Section 3.3. of the COD (page 33), the streetscape for the main street must feature furniture, such as
benches and trash receptacles. Currently, none are shown. Benches and trash receptacles should be provided along
the Stella Lane adjacent to the sidewalk on the final site plan. First submittal: Comment addressed.
22. [32.5.2 (n)] Per the Application Plan of ZMA201500007, there are some areas of land at the north side of Block 1B,
between the greenway and the proposed buildings, that needs to be open space (green color outside of the greenway
which is brown). On the final site plan, please address the following:
a. Show and label the open space areas on the layout drawings; First submittal: See comment #33 under Final
Site Plan Comments below.
b. Update the open space note on Sheet 1 to state acreage/sq.ft. of open space provided; First submittal: See
comment #33 under Final Site Plan Comments below.
c. Update the open space column in the Block Area Summary on Sheet 3. First submittal: See comment #33 under
Final Site Plan Comments below.
23. [32.5.2 (n)] Please provide a construction detail for the proposed enclosure around the trash compactor. The detail
needs to be plan and profile view and indicate the types and dimensions of all construction materials used for the
enclosure. First submittal: Comment not addressed. A plan and profile detail must be provided on the final site plan
for the dumpster enclosure.
24. [32.5.2 (n) and 4.12.19] Please show dimensions for the dumpster pad. Please be aware that dumpster pads must be
concrete, and the pad must extend a minimum of 8' beyond the front of the dumpster. First submittal: Comment
addressed.
WWW.ALBEMARLE.ORG
401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579
25. [32.5.2 (o)] The greenway is labeled as "existing" on multiple drawings. However, an easement has not yet been
recorded over the greenway. Prior to final site plan approval, the easement will need to be recorded, and the site plan
should show the accurate greenway easement dimensions/locations and reference the recorded instrument number.
First submittal: Comment stands. The greenway parcel has been subdivided, but no easement has yet been dedicated
as required by the COD/proffers. Per proffer #2a, a public easement over the greenway needs to be dedicated at
some point after the issuance of the 500"' permit for a dwelling unit within the project. Staff is willing to discuss the
greenway dedication further with the applicant if need be. Please indicate if the developer has an idea of when the
intend to dedicate the ereenwav easement. Additionally, please see comment #33 below for further information.
26. [32.5.2 (r)] Provide a legend on all applicable drawings where symbols and abbreviations are used. Identify the
different symbology used for all surface materials such as sidewalks, travel ways, open space, etc. First submittal
comment addressed.
27. [32.6] The final site plan must comply with all applicable requirements of Section 32.6 prior to approval. First
submittal: See comments under Final Site Plan Comments section below.
28. [32.5.2(p), 32.7.2.1] The proposed entrances shall be designed and constructed as required by the standards of the
Virginia Department of Transportation. VDOT approval of the proposed entrances to the site shall be required prior to
final site plan approval. First submittal: Comment stands, see attached VDOT comments.
29. [32.5.2(n)] Any proposed outdoor lighting must be shown on the site plan. A photometric plan and lighting cut sheets
must be provided with the final site plan. Proposed lighting must comply with requirements of Sections 32.7.8 &
Section 4.17 of the Zoning Ordinance. In addition to meeting all lighting requirements a standard lighting note will be
required. First submittal: See comment #32 below.
30. [32.7.9] Please provide a landscaping plan that complies with all requirements of Section 32.7.9 on the final site plan.
This includes the following:
a. [32.7.9.4 (c)] Existing landscape features as described in this Code section. First submittal: Comment addressed.
b. [32.7.9.5] Street trees 50 feet on center along Stella Lane. First submittal: Comment addressed.
c. [32.7.9.61 Minimum 5% of overall parking area landscaping, including one tree per every 10 parking spaces
proposed. Please provide a calculation on the landscaping plan identifying the percentage and sq. ft. of required
and proposed parking area landscaping. First submittal: Comment not fully addressed. The calculation on Sheet
17 states that 4,288 sa.ft. of landscaping is provided within the parking area. However. 7,000 sa.ft. is required.
Please identify additional landscaping within the parking area that will be used to meet the 7,000 sq.ft
minimum, and update the landscaping provided sq.ft figure as necessary.
d. [32.7.9.8] Minimum 15% total landscaping canopy for the site area. Site area is calculated as described in
Section 32.7.9.8 (c). Please provide a calculation on the landscaping plan identifying the percentage and sq. ft.
of required and proposed canopy area. First submittal: Comment addressed.
e. All proposed landscaping must be species identified on the Albemarle County Approved Plants List. First
submittal: Comment addressed.
f. Canopy areas for specific tree and shrub species can be obtained from the Plant Canopy Calculations table.
First submittal: Comment addressed.
Final Site Plan Comments:
31. [32.7.8] Provide a lighting plan that addresses the following:
a. [4.17] Show the location of all outdoor lighting fixtures and luminaries proposed. First submittal: See comment
#31b and #31c below.
b. [4.17] Provide a luminaire schedule identifying each type of outdoor luminaire proposed. Include the
manufacturer name, model number, lamp type (e.g. LED, incandescent, etc.), wattage/lumens emitted, and
pole/mounting height. Include a column in the schedule that identifies the symbology used for each fixture on
the lighting plan. State the number of each outdoor luminaire provided by type. First submittal: Luminaire
WWW.ALBEMARLE.ORG
401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579
schedule states that zero (0) SLA3 and SLA4 luminaires are proposed but these types are shown on the
drawing. Additionally, a luminaire type. WLA3, is noted in the Site Lighting Fixture table, but this luminaire
type is not provided in the Luminaire Schedule. Please update the quantity column of the schedule to reflect
the plans.
c. [4.17] Provide a table with photometric data for each luminaire type. Show photometric measurements within
the site and along all property boundaries. Please be aware that Albemarle County requires photometric plans
to use a Light Loss Factor (LLF) of 1.0 to calculate footcandle measurements on site plans. Please be aware
that the spillover of lighting from luminaires onto public roads and property in residential or rural areas
zoning districts shall not exceed one-half foot candle. First submittal: Comment not addressed. Sheet 19 is
the lighting plan, but no footcandle measurements are visible for Phase 113. Please revise.
d. [4.17.4 (a)] Provide manufacturer cut sheets for all outdoor luminaires that will emit 3,000 lumens or greater.
Be sure that the cut -sheets identify that these luminaires will be equipped with full -cutoff fixtures. First
submittal: Comment not fully addressed, only two cut -sheets are provided but five different luminaire types
appear to be proposed. Please revise.
32. [ZMA201500007] Please revise the drawings so that the WPO stream buffer and greenway boundaries are depicted
accurately. Per Section 2.4.1 of the COD (page 18), the greenway encompasses all land within the 100-foot stream
buffer and 100-year floodplain. The 100-foot stream buffer measurement applies to both sides of a perennial stream.
Currently, the plans do not appear to be consistent with this requirement. See Engineering Division comments for
further information.
a. If necessary, update the greenway sq.ft. notes on Sheet 1 and Sheet 3 to reflect the total area required and
proposed. within the greenway
33. [ZMA201500007] The buildings shown in Phase 1B are all identified as four (4) stories. However, no stepbacks are
shown on the layout drawings and it is unclear if or where stepbacks will be provided. Per Section 2.3.1 of the COD,
buildings greater than 3 stories in the town center (block 1) must step back a minimum of 15 feet after the 3' story, or
provide a minimum 15-foot front or side setback adjacent to a street. If not stepbacks are proposed, then show the 15'
setback line on the layout drawings so staff can verify that each building is setback at least 15' from the ROW of Archer
Avenue and Stella Lane in Phase 1B.
34. 118-30.7.4 (B)(1)(h)] The site plan identifies areas of Preserved Steep Slopes that the applicant states are less than 25%.
Please provide topographic information demonstrating this so that the County Engineer can review and verify that this
is true and the Preserved Slopes can be disturbed. See Engineering Division comment #7 for further information.
35. [32.7.3] Please show the required 2' overhang area for all proposed parking spaces that measure 9' x 16.' See
Engineering Division comments for further information.
36. [37.9.5] Sheets 17 and 18 identify street trees that have already been installed along Archer Avenue as approved with
the road plans, SUB201700117. However, there are no existing trees shown along the eastern side of Archer Avenue
abutting buildings 2 and 3. The road plans showed trees being installed along that segment or Archer Avenue. Please
clarify - have those trees been installed? If so, please show them and gray them out just like the other trees further
south along Archer.
37. [32.7.9.9 (a)] On the landscaping plans, add a note stating "All landscaping shall be installed by the first planting season
following the issuance of the first certificate of occupancy within the development, or a phase thereof."
38. [32.7.9.9 (c)] On the landscaping plans, add a note stating "All landscaping and screening shall be maintained in a healthy
condition by the current owner or a property owners' association, and replaced when necessary. Replacement material
shall comply with the approved landscape plan."
WWW.ALBEMARLE.ORG
401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579
Please contact Cameron Langille in the Planning Division by using blangille@albemarle.org or 434-296-5832 ext.3432 for
further information.
Comments from Other Reviewers.
Albemarle County Engineering Division - Emily Cox, ecox2@albemarle.org - Requested changes, see attached.
Albemarle County Architectural Review Board (ARB) - Margaret Maliszewski, mmaliszewski@albemarle.org - Requested
changes, see attached.
Albemarle County E911 Services - Elise Kiewra, ekiewra@albemarle.ore - Requested changes, see attached.
Albemarle County Building Inspections - Betty Slough, bslou¢h@albemarle.ora - Requested changes, see attached.
Albemarle County Department of Fire & Rescue - Howard Lagomarsino, hla¢omarsino(o)albemarle.ore - Requested
changes, see attached.
Albemarle County Service Authority (ACSA) - Richard Nelson, rnelson@serviceauthority.org - Review not yet complete,
comments or approvals will be forwarded to the applicant upon receipt.
Virginia Department of Transportation (VDOT) - Max Greene, max.¢reene@vdot.vireinia.¢ov - Requested changes, see
attached.
Rivanna Water & Sewer Authority (RWSA) - devreview@rivanna.or-No objection, see attached.
WWW.ALBEMARLE.ORG
401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579
County of Albemarle
- COMMUNITY DEVELOPMENT DEPARTMENT
�18cit�P
Memorandum
To: Cameron Langille
From: Emily Cox
Date: 02/14/2022
Subject: Brookhill Block 1B Final Site Plan (SDP202100098)
401 McIntire Road, North Wing
Charlottesville, VA 22902-4579
Telephone: 434-296-5832
WWW.ALBEMARLE.ORG
The Brookhill Block 1B final Site Plan has been reviewed by Engineering. The following
comments will need to be addressed before approval:
1. WPO plan must be submitted and approved before final site plan can be
approved.
2. Grading as shown for the "existing SWM facility" is not existing and does not
match the approved WPO201700037 -amendment 2 plan. Please note that all
grading must meet County Code 18.4.3.3.
3. Road plan must be submitted, approved, and built or bonded before final site plan
can be approved.
4. Signed and sealed retaining walls plans will be necessary before final site plan
approval.
5. Please measure and show the stream buffer and greenway. Ensure they meet
Brookhill Code of Development and County Code requirements. Code of
development:
the community The Greenway encompasses the land within the 100 foot stream buffer along
the perennial streams and wetlands and all land located within the floodplam. This Greenway
County code: The stream buffer shall be no less than 100 feet wide on each side
of any perennial stream and contiguous nontidal wetlands, measured
horizontally from the edge of the contiguous nontidal wetlands, or the top of
the stream bank if no wetlands exist
6. Canopy trees must be at least 5ft from storm pipes.
7. Please provide the exhibit for the changing of preserved slopes in accordance
with County Code 30.7.4.b.1.h.
8. Stella Lane continuation should be a public street.
9. Grading off site will require easement or permission from landowner.
10. Ensure all proposed drainage easement widths meet the requirements in the
Design Standards Manual, page 15:
https://www.albemarle.org/Home/ShowDocument?id=270
11. [Sheet 13] Some of the spreads for inlets in sump appear large. Please show the
WSE on the plans to ensure the spread is not in the travelway.
12. Are there proposed blockades/bollards for the travelways that are for future
extension on the eastern side of the project? If so, please show on the plan and
provide detail.
13. Please label the 2ft. overhang where parking spaces are 9'x16'.
Engineering Review Comments
Page 2 of 2
14. Travelway and parking to the east of apartment building 2 do not appear to meet
County Code requirements. See section 18-4.12.16.
15. [Sheet 15] Dumpster pad detail should have rebar specified.
Review Comments for SDP202100098 Final Site Development Plan
Project Name: BROOKHILL BLOCK I - FINAL - DIGITAL
Date Completed: Tuesday, February 22, 2022 Depanment/Division(Agency: Review Status:
Reviewer: Margaret Maliszewski -2 CDD ARB 0 Requested Changes
An ARB application for a Final Site Development Plan is required. Submit architectural designs for review. Revise the lighting
plan as follows:
1. Revise the photometric plan to show point -by -point footcandle readings.
2. Revise the color temperature of the light fixtures to 3000K maximum-
1 The notes next to the legend conflict with the lighting schedule and cut sheets.
a. Coordinate the lighting plan regarding fixture finish color. Ensure consistency with the completed development.
b. Coordinate the lighting plan regarding pole height. Fixtures must not exceed 20 in height, including bases.
Page: 1 1County of Albemarle Printed On: 02l24l2022
�� pF AL8
County of Albemarle
GEOGRAPHIC DATA SERVICES OFFICE
COMMUNITY DEVELOPMENT DEPARTMENT
PLAN REVIEW COMMENTS - E911
APPLICATION#: SDP202100098
TMP: 04600-00-00-019136
DATE: 1/24/22
The following road names are acceptable:
]ADA LN
Elise Kiewra
ekiewraC?albemarle.org
tel: 434-296-5832 ext. 3030
fax: 434-972-4126
Please also submit a road name for the travelway in red in the screenshot below.
W W W.ALBEMARLE.ORG
401 McIntire Road, Suite 228 1 Charlottesville, VA 22902-4596
Review Comments for SDP202100098 Final Site Development Plan
Project Name: BROOKHILL BLOCK I - FINAL - DIGITAL
Date Completed: Monday, January 24, 2022 Department/DivisiordAgency: Review Status:
Reviewer: Betty Slough CDD Inspections Requested Changes
unange tsuraing Coae notes 1 142 to the tonowmg:
Accessible parking spaces, access isles, and accessible route shall be installed in accordance with ICC ANSI A117.1-09 and
the 2018 Virginia Construction Code.
All water, sewer and fire lines require NEW inspection and testing procedures. The ACSA performs any testing and
inspections of the public sewer and water main(s).
The Albemarle County Building Inspections Department(ACBID) does a visual inspection and witnesses the testing of the
building drain, water service pipe and the sprinkler lead-in connection.
The developer/contractor is responsible to retain a Special Inspector as outlined in the updated Albemarle County Policy for
Site Utilities to perform the visual inspection and testing of all utilities
not covered by the ACSA orACBID. This includes building sewers, water and fire line branches between the main and the
meter(sybuilding(s).
The Special Inspector's report must be submitted and approved by the Albemarle County Engineering Department prior to a
Certificate of Occupancy being issued.
Page: 11County of Albemarle Printed On: 02l21l2022
Review Comments for SDP202100098 Final Site Development Plan
Project Name: BROOKHILL BLOCK 1B - FINAL - DIGITAL
Date Completed: Monday, January 31, 2022 Department/Division/Agency: Review Status:
Reviewer: Howard Lagomarsino -E Fire Rescue Requested Changes
t) Please provide projection oT me available tire now Tor nyarants as a note on the plans.
2) There are points on the roads in the plan where parking would reduce the travelway below the required minimums. Please
indicate the installation of no parking signs for those areas.
3) During construction, the following fire prevention steps are required, so please note them on the plan:
a) Smoking shall be prohibited in areas where smoking makes conditions such as to make smoking a hazard and these
areas shall be designated with no smoking signs per Virginia Statewide Fire Prevention Code.
b) Areas where smoking can occur, shall have appropriate receptacles for discarded smoking materials per Virginia
Statewide Fire Prevention Code.
c) Per the Virginia Statewide Fire Prevention Code, vehicular access for firefighting shall be provided at all construction
and demolition sites, provide access to within 100 ft. of temporary or permanent fire department connections, and have no
overhead wiring or other overhead obstructions lower than 13 ft. 6 inches; this access may be via permanent or temporary
road, but shall be capable of supporting fire apparatus in all weather conditions.
d) Contractor shall ensure the street numbers are always plainly visible from the frontage street during construction per the
Virginia Statewide Fire Code
e) An approved water supply for firefighting operations shall be in place and available as soon as combustible materials
arrive on site.
f) Waste and combustible debris shall be removed from the building at the end of each day and disposed of in accordance
with the Virginia Statewide Fire Code
g) Fire extinguishers shall be provided, with not less than one approved fire extinguisher at each stairwell, on all floor levels
where combustible materials have accumulated, in every storage and construction shed and in areas of special, hazards, such
as where flammable and combustible liquids are stored or used, in accordance with the Virginia Statewide Fire Code
h) Operations involving the use of cutting and welding shall comply with the Virginia Statewide Fire Prevention Code and
shall require a permit from the Albemarle County Fire Marshal's Office
Page: 1 1County of Albemarle Printed On: 02/21 /2022
(Z)
COMMONWEALTH of VIRGINIA
DEPARTMENT OF TRANSPORTATION
Stephen C. Brich, P.E. 1401 East Broad Street
Commissioner Richmond, Virginia 23219
County of Albemarle
Department of Community
401 McIntire Road
Charlottesville, VA 22902
Attn: Cameron Langille
January 25, 2021
Development
Re: SUB-2021-00098 — Brookhill, Block 113 — Final Site Plan
Review# 1
Dear Mr. Langille:
(804) 786-2701
Fax: (804) 786-2940
The Department of Transportation, Charlottesville Residency Transportation and
Land Use Section has reviewed the Brookhill, Block I — Final Site Plan, dated
October 15, 2021 as submitted by Collins Engineering and find the following:
i. Show "No Parking" signage on all roads except in areas with designated
parking. Begin/end signs should be shown to delineate areas.
2. Please show the mail boxes & cluster box units per RDM Appendix B(1)-56
3. Please show the proposed right of way for the roundabout on the plans per
the existing conditions on sheet #4 and plat recorded in DB 5107 pg. 148.
R/W is currently shown across the roundabout.
4. The proposed right of way must extent to one foot beyond the back of
sidewalk.
5. CG-12 detail is no longer on sheet 15 and reference should be to the Road &
Bridge Standards
hqps://www.virginiadot.orwbusiness/locdes/Standards CompleteSections.asp
6. Approved road plans meeting SSAR, and in compliance with the VDOT
Road Design Manual are required prior to plat approval.
7. Please provide a comment response letter with each submission after the
initial.
VirginiaDOT.org
WE KEEP VIRGINIA MOVING
8. Note that the final plan must show conformance with the VDOT Road
Design Manual Appendices B(1) and F, as well as any other applicable
standards, regulations or other requirements.
A VDOT Land Use Permit will be required prior to any work within the right-of-
way. The owner/developer must contact the VDOT Charlottesville Residency Land
Use Section at (434) 422-9399 for information pertaining to this process.
If you have further questions, please contact Max Greene at 434-422-9894.
Sincerely,
Doug McAvoy Jr., P.E.
Area Land Use Engineer
VDOT - Charlottesville Residency
Review Comments for SDP202100098 Final Site Development Plan
Project Name: BROOKHILL BLOCK 1B - FINAL - DIGITAL
Date Completed: Monday, January 24, 2022 Department/Division/Agency: Review Status:
Reviewer: Unassigned ] RWSA No Objection
Page: 1 1County of Albemarle Printed On: 02l21l2022