Loading...
HomeMy WebLinkAboutSDP202100053 Study 2022-03-10JUbemadeCounty Date of Report ServiceAuth♦rity Hydrant Flow 3/10/2022 Test Report 168 6polnap RoaO Charlottesville. VA 22911 (434) 9774511 Location BISHOPGATE LN Pressure Zone CROZET SERVICE AREA Date and Time of Test 3/10/2022 10:47:00 AM Minutes of Flow 2 Pipe Size (Inches) 8 Pressure Hydrant 13388 Static Pressure (psi) 95 Residual Pressure (psi) 84.5 ❑ Q20 Looped ❑ Q20 Multiple Inline Hydrants Q20 Single Flow O Sprinkler Test Single Flow Flow Hydrant #1 13389 Pitot Pressure #1 (psi) 24.4 Yellow 1 ❑O Test Flow 1 822 Flow Hydrant #2 Pitot Pressure #2 (psi) Yellow 2 Test Flow 2 0 Flow Hydrant #3 Pitot Pressure #3 (psi) Yellow 3 Test Flow 3 0 Total Estimated Flow (gpm) 822 AWWA Q20 Calculation (gpm) 2376 (No value in Q20 indicates insufficient pressure drop for Q20 OR a sole sprinkler test.) Comments Hydrants opened all the way. For method of calculating pilot flow with a red Pollard diffuser: see eq. 13, Wa lski and Lutes article 199D Journal Management and Operations AW WA. For yellow Pollard diffusers, a best fit third order polynomial equation of the Pollard flow vs. pitot pressure gauge is used. Estimated Consumption (gal) 1644 For use for water audit �j Signature of Tester: �� %/'�