HomeMy WebLinkAboutSDP202200026 Correspondence 2022-04-18 (2)SHIMP ENGINEERING, P.C.
Design Focused Engineering
April 13ih, 2022
Mr. Howard Lagomarsino
hlagomarsinokalbemarle.org
Department of Community Development
401 McIntire Road
Charlottesville, VA 22911
Regarding: SDP2021.60 Albemarle fire & Rescue —
Take 5 Pantops Comment Response
Dear Mr. Howard,
Thank you for your review of the Final Site Plan for Pantops. We have revised our plans per most recent comments
dated August 13'h, 2021. Please see below for a detailed response to each of your comments.
Proposed height listed at 28 ft, keep in mind if this project goes much taller than the proposed
height, an emergency/fire vehicle access road/route needs to provide an unobstructed travel way
width of 20 ft. if buildings/structures are under 30 feet tall and 26 ft. if buildings/structures are
over 30 feet tall
Comment noted Building height shall not exceed 30'
2. Emergency/fire vehicle access roads need to be clear of overhead obstructions at 13 ft 6 in. and
bi.'.—
Pantops corner way will serve as access, there are not overhead obstruction.
3. To accommodate fire apparatus, turn radii serving fire apparatus access must be a minimum of
25 ft.
Pantops corner way serve as fire access.
Road grade cannot exceed 10 %
Road grade does not exceed 10%
5. Provide a nc plans of the required ISO fire calculation for the buildings
To be provided: 1500 gpm
6. Indicate on the plan the latest ACSW flow test to ensure adequate fire flow per calculation in
comment # 5
See note on Sheet C4
7. Provide the locations of fire hydrants as determined by calculations in # 5, with spacing in
accordance with the required fire flow calculation (This starts at 500 feet and arranged so that no
building is more than 250 feet from a hvdrant, but the distances are further reduced as the
Attached Copy of ACSA flow test to response letter.
8. A Knox Box will be required. Please place a note indicating this on the plan. The location of this
can be coordinated with the Fire Marshal's Office.
A Knox Box has been provided - See sheet C3
9. Fire suppression, fire alerting systems and other building design features, such as exits, interior
finishes, building access etc., are the purview of the building official and required as directed by
that offirr
Not fire suppression is provided. Fire suppression is not required in building official review/
building permit.
10. if fire suppression systems or standpipes are installed the FDC must face the road, on
address/entrance side and there needs to be hydrant within 100 ft. of the FDC, arranged so that
when hv_ drant and FDC are in use for emergency operations, hose does not obstruct travel way.
Not fire suppression is provided.
If you have any questions or concerns about these revisions, please feel free to call me at (434) 299-9843 or
email Justin Shimp at iustinoshimp-engineerinq.com and we can discuss any questions that you may have in further
detail.
Best Regards,
Justin Shimp
Shimp Engineering, P.C.
Albamw6lC°°"�y �, Hydrant Flow
Service Auth�ri
Ser*q'"nq fl�� Test Report
lf;0 Spotrtap Road C ruResNlIe, VA P2911 (431) 9Hy 11
Location
Date and Time of Test
Minutes of Flow
Pipe Size (Inches)
PANTOPS CORNER WAY
3/28/2022 9:07:00 AM
F
Pressure Hydrant 13272
Static Pressure (psi) 107
Residual Pressure (psi) 71.9
Date of Report
3/28/2022
A&A
Pressure Zone URBAN RING
C Q20 Looped ❑ Q20 Multiple Inline Hydrants ❑ Q20 Single Flow ❑ Sprinkler Test Single Flow
Flow Hydrant #1
Em#Pitot
Pressure #1 (psi)
L 64
Yellow 1
.❑
Test Flow 1
1331
Flow Hydrant #2
10780
Pitot Pressure #2 (psi)
56.2
Yellow 2
Test Flow 2
1256
Flow Hydrant #3 E4278 Pitot Pressure #3 (psi) 55.7 Yellow 3 ❑ Test Flow 3 1043
Total Estimated Flow (gpm) 3630
AWWA Q20 Calculation (gpm) 5926
(No value in Q20 indicates insufficient pressure drop for Q20 OR a sole sprinkler test.)
r11lITITI}:
Hydrants opened all the way
For method of calculating pitot flow with a red Pollard diffuser: see eq. 13, Walski and Lutes article 1990 Journal Management and
Operations AW WA. For yellow Pollard diffusers, a best fit third order polynomial equation of the Pollard flow vs. pitot pressure gauge is
used.
Estimated Consumption (gal) 7260
For use for water audit
Signature of Tester:
11 /y 1, EGEND
325 � 00 320 ,yy'L �A d�. �� 328�3. CSA Hydrant
So ` " 1193 / 36U. J 332 nService, Ownership
�ryM\ � , .� ,� QO.-` Not In Service, ACSA Owned yb g06 3 7
;,1 Not In Service, Pnvate Ownershi
,� 32D � 3.,v� Flow Hydrant r m I � f 979 � 2
r6ry Op `8�0 k22.� 384 8p'90
38 " In Service, Private Ownership
° '�' f- _ 1 _ In Service, ACSA Owned
♦O� OVA ,�'Ya� - �, 13271� ACSA Water Service
7321
336 -_� i g9°i /— �-398 ACSA Fire Line
3q0
0 9 i CSA Water Main
SAD�,ti- �00 i �,�,y6 33� �348 362 _ 392 ��.., ershi
6Y31N. �10
�^�1 O`L° ,�0,6 j 865 �ro PJ AC at P
_ riv a OwneMhi
- 34;�,y .y`I.Q / �� 20 +5+1 M 1 \1290 +294 SA Water Main p
368 0 +294 l N\ tIIItY TIPe
` 1 1150 Test Hydrant azD. nl a Potable water
Q0 ��i N Raw Water
11sD
ti° 1172 +za9 1327 I> I City water Lines
103 Parcels
1300
°+01' 1127�1192
�� 414
6" 1127
i 410 - - 412 8n 420
rti NM
RICOND-RD-0250 a a
r 11127 z5o < g
1128 0� +05 '0 366 a
40012381
° t 400
��260 �-140 O% +� Flow Hydrant 1289 N 'oc,
1313
A 4 r �� � � 1142
308- TAO 120 f 2 -� I
304 300 fO 125 11--- 392-
312 00,\ .^'- '384--364�-368— 7
48
310 +40 r• 3
co 388
138 " 1 v p' ry
350 1078 i 36�
S60 U1 +53 �368 ` car ro ry
sn �� > 1 / 11281 0 AN9 °
Flow H drant - 370 372 C 42? �L
y 160 168 404 P
DISCLAIMER
Utilities, structures, lot lines, and all appurtenances indicated on this map are intended for general N I Q/�/� (�
layout and reference location only. This printout is not intended for any other use Man for preliminary Albemarle County
planning and gene2l location purposes. The utilities shown on this map am believed to he accurate, W E
however, recent utility improvements and/or system changes may have been updated since the yAy
fiveof ents, property
lines Any determorboundadonoftopgenephyor nformaoum, or ononly ndepictionofphysical Service Muth6rtt�/
improvements, property lines or boundaries is for general information only and shall not be used for the 6
design, modification, or construction of improvements M real property or for flood plain determination.
Contact ACSA directly for specific utility locations. 0 125 250 375 500