HomeMy WebLinkAboutSDP202000021 Other 2022-04-20ARCHITECT OF RECORD:
THOMAS E. MORGAN, JR.
ARCHITECT
22'-0" AFF
T.O. PARAPET
14'-0" AFF
T.O. MASONRY
9FF
B.O. AWNING
9'-4" AFF
T.O. WINDOW
3'-4" AFF
T.O. SILL
-0'-6" AFF
TUNNEL F.F.
ump
I I i I
I I r 0"AFF
i T.O. PARAPET
mmi 12'-0"
INTERIOR GARAGE DOOR
12'-8' AFF
B.O. AWNING
8M'-0.'AFF
.O. SCONCE
BRICK; TO MATCH EXTERIOR
SILL CAP; TO MATCH EXTERIOR
3'-4" AFF
T.O. SILL
STONE; TO MATCH EXTERIOR
0'-01,
F.F.E.
-0'-6" AFF
TUNNEL F.F.
■ LEGEND
EF-I: EIFS EXTERIOR FINISH, SAND PEBBLE FINISH AND SMOOTH TRIM BANDS
COLOR: MATCH SHERWIN WILLIAMS SW7001 MARSHMALLOW
aBR -I: THIN BRICK VENEER, WHITE
GENERAL SHALE BRADFORD HALL OR EQUAL
aSTN-1: HORIZON STONE, MANUFACTURED VENEER MASONRY
COLOR: SMOKY MOUNTAIN HANDCRAFTED
aSTN-I: HORIZON STONE WATER TABLE SHAPE LEDGESTONE
COLOR: SMOKY MOUNTAIN HANDCRAFTED
MTL-1: PREFINISHED ALUMINUM COPING
COLOR: BONE WHITE
MTL-2: PREFINISHED ALUMINUM FLAT CANOPIES
COLOR: BURNISHED SLATE
MTL-3: PREFINISHED ALUMINUM SHADE AWNINGS, PAC CLAD 7.2
PANELS ATTACHED TO ALUM FRAME, COLOR: BURNISHED SLATE
ALUM/GLASS: PREFINISHED ALUMINUM DOORS AND WINDOWS
COLOR: DARK BRONZE ANODIZED, GLASS COLOR GRAY
HOLLOW MTL PAINTED: METAL DOORS AND FRAMES
COLOR: SHERWIN WILLIAMS SW6006 BLACK BEAN
10 CLOPAY METAL/GLASS OVERHEAD DOOR SERIES, MODEL 902/903
ALUM COLOR: DARK BRONZE; GLASS COLOR GRAY
11 COILING OVERHEAD DOOR
ALUM COLOR: DARK BRONZE
12 LIGHT FIXTURE
COLOR: DARK BRONZE
13 ALUM SCUPPERS AND DOWNSPOUTS
COLOR: DARK BRONZE
423 FISCI3ER TRAIL
ELLIJAY. GEORGIA 30540
DESIGN GROUP
3450 Acworth Due West Road
Building 100, Suite 120
Kennesaw, Georgia 30144
P.770-917-9172
F.770-917-9470
www.mrpdesign.com
ENTRANCE END `S-OUM ELEVATfON
A105 SCALE: 3/16"= 1'-0" ISSUES/REVISIONS
1 DATE DESCRIPTION
O 1 .27.21 REVIEW SET
A107 02.15.21 PERMIT SET
04.18.22 Revision # I
I 1 1 I I I
A106 A108
I
I I I I
I I
AFF
DRAWN BY: Qe
CHK'D BY: TM
PROJECT TITLE:
2 >Q
Q
W
r J
U �
U)
cn w
0�
w�
0�O
0- J
W Q
� U
SHEET TITLE:
SOUTH AND EAST
EXTERIOR ELEVATIONS
PROJECT NO: 19066
SHEET NUMBER:
A105
a -
1
L_
WP�WP ON ROOF
CU-1
0 ON ROOF
EF-6
INDOOR VAC SPACE
101
I%///////////%I
W OMA N'S
RESTROO12
103
UH-3
ACT rr=/
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
WIRE AND COND.
FHU-1
CIRCUIT DESIGNATION
VOLT
PH
LOAD
THWN COPPER
DISCONNECTING MEANS
NOTES
THRU CU-1
120
1
1.0
MCA
2#12,1#12(G),1/2'
30/1/1/NF
1,4
L-28,30
208
1
13.0
MCA
2#12,1#12(G),1/2'
30/2/3R/F15A
1,4
L-12
120
1
0.1
KW
2#121#1 (G)2"C.
RS
1,3
F
L-12
120
1
0.1
KW
2#12,1#12(G),1/2"C.
MRS
1,3
L-6
120
1
0.1
KW
2#12,1#12(G),1/2"C.
MRS
1
-
L-6
120
1
0.1
KW
2#12,1#12(G),1/2"C.
MRS
1
EF-5
L-10
120
1
1/8
HP
2#12,1#12(G),1/2"C.
30/1/1/NF
1
EF-6
L-12
120
1
0.14
KW
2#12,1#12(G),1/2"C.
MRS
1,3
I -
1
.6
LA
/
1
IRH-2
L-14
120
1
2.6
FLA
2#12,1#12(G),1/2"C.
30/1/4X/NF
1
DJ-1
H-2,4,6
480
3
1-1/2
HP
3#12,1#12(G),1/2"C.
30/3/4X/NF
1,3
DJ-2
H-8,10,12
480
3
1-1/2
HP
3#12,1#12(G),1/2"C.
30/3/4X/NF
1,3
UH-2
L-2,4
208
1
4
KW
2#10,1#10(G),3/4"C.
30/2/1/NF
1
UH-3
L-57,59
208
1
4
KW
2#10,1#10(G),3/4"C.
30/2/1/NF
1
WHA
L-26
120
1
2
FLA
2#12,1#12(G),1/2"C.
MRS
1
NOTES
1. PROVIDE OVERCURRENT PROTECTION AND BRANCH CIRCUITS PER UL LISTED REQUIREMENTS FOR EQUIPMENT SERVED. REFER TO
MANUFACTURER DATAAND EQUIPMENT CUT -SHEETS FOR ROUGHIN LOCATIONS OF ELECTRICAL CONNECTIONS AND INTERCONNECTIONS FOR
ALL EQUIPMENT. COORDINATE EXACT NAMEPLATE DATA OF EQUIPMENT BEING INSTALLED WITH MECHANICAL CONTRACTOR.THIS MEANS FOR
THE ELECTRICAL CONTRACTOR TO MEET WITH THE MECHANICAL CONTRACTOR AND ACQUIRE A COPY OF THE SHOP DRAWINGS FOR THE EXACT
PIECES OF EQUIPMENT THAT WILL BE INSTALLED. THE ELECTRICAL CONTRACTOR SHALL COMPARE THE MANUFACTURER'S DATA SHEETS FOR
THE ACTUAL EQUIPMENT THAT IS BEING USED WITH THE ELECTRICAL PLANS PRIOR TO ORDERING THE ELECTRICAL GEAR. IF THERE ARE ANY
DIFFERENCES BETWEEN WHAT THE MECHANICAL CONTRACTOR IS PLANNING TO USE AND WHAT THE ELECTRICAL PLANS INDICATE, THE
ELECTRICAL CONTRACTOR SHALL BRING THE DISCREPANCIES TO THE ATTENTION OF THE GENERAL CONTRACTOR AND THE CONTRACTORS
SHALL WORK OUT ANY ADDITIONAL MONIES REQUIRED WITHOUT ANY COST TO THE OWNER. IF THIS ON SITE COORDINATE DOES NOT HAPPEN, IT
WILL BE ASSUMED THAT THE ELECTRICAL CONTRACTOR SHALL ABSORB ANY AND ALL COSTS THAT MAY BE ASSOCIATED WITH THE MECHANICAL
CONTRACTOR'S EQUIPMENT. NOTE THAT THE MECHANICAL CONTRACTOR MAY USE DIFFERENT MANUFACTURERS THAN THE DESIGN INTENT
PLANS INDICATE AND THESE DIFFERENT MANUFACTURERS MAY HAVE DIFFERENT ELECTRICAL REQUIREMENTS.
2. NOT USED.
3. EXTEND AND CONNECT EXHAUST FAN TO LOCAL LIGHTING CIRCUIT WITHIN THIS ROOM. FAN SHALL BE CONTROLLED BY LOCAL LIGHT SWITCH
AND SWITCHED WITH THE LIGHTS. PROVIDE MAGNETIC STARTER FOR CONTROL INTERFACE.
4. INDOOR UNIT POWERED FROM OUTDOOR UNIT. PROVIDE WITH MRS ON INDOOR UNIT IN ORDER TO COMPLY WITH CODE.
DOWN
0
PANEL L--C � U
L- 4 PANEL H
32 TRANSFORMER'TL'
rL-55 (WALL MOUNTED) O
® EF-4
106
E >
2Q W-W 2Q
Q
24-G
E
0
2-A 1-A]Q 1-E Q W® Q 1-X 1-P Q 1-H Q
1-D Q
L-36 5
L-6
ELECTRICAL AND
EQUIPMENT ROOM
105
L-1
moo ®�
F
Al Al ® Al
'•'•'•'•'•'•'•''''"iiiii%%///////////////////%P
-001 l9 ®
1 0 25-1
®Q 25-J
Q 25-K
DJ-1
L
10-A Q 10-A Q
Hog
Q 2-A 18-B Q 27-9
18-B Q Q
4
ARCHITECT OF RECORD:
THOMAS E. MORGAN, JR.
ARCHITECT
423 FISCHER TRAIL
ELLIJAY, GEORGIA 30540
TT W. UNDELOW
Lk. No. 055170
.+er
mmm
DESIGN GROUP
Q 3450 Acworth Due West Road
Building 100, Suite 120
130-Cl Kennesaw, Georgia 30144
P.770-917-9172
F.770-917-9470
www.mrpdesign.com
ISSUES/REVISIONS
1 ELECTRICAL - POWER PLAN
LEGEND NOTES:X
O
08.A
18.20
COOKED ELEVATION55UBMITTAL
101 SCALE: 3/16" = V-0"
COORDINATE EXACT REQUIREMENTS AND LOCATIONS WITH OWNER PRIOR TO
04/20/22
REV1510N
AT1.
ROUGH -IN.
2.
PROVIDE CONCRETE HOUSEKEEPING PAD UNDER THE MOTOR CONTROL
CARWASH EQUIPMENT GENERAL NOTES:
CENTER.
1. COORDINATE ALL CARWASH EQUIPMENT LOCATIONS, LOAD, VOLTAGES,
3.
PROVIDE WALL MOUNT BRACKETS FOR THE TRANSFORMER.
ETC. WITH THE CARWASH EQUIPMENT INSTALLER PRIOR TO ROUGHING IN
ANY ELECTRICAL CIRCUITS TO THE EQUIPMENT.
4.
PROVIDE POWER CONNECTION FOR THE GAS WATER HEATER CONTROL PANEL.
2. THIS PLAN ONLY INDICATES LINE VOLTAGE CIRCUITS.
5.
MOTORIZED DAMPER. INTERLOCK WITH EXHAUST FAN. REFER TO MECHANICAL
PLANS FOR ADDITIONAL INFO.
3. PROVIDE ALL CONTROL CIRCUITS FOR THE CARWASH EQUIPMENT PER THE
CARWASH EQUIPMENT PLANS. PROVIDE WIRE, CABLE, AND CONDUIT SIZES
6.
PROVIDE CONNECTION FOR OWNER PROVIDED WASHER. VERIFY WASHER
DRAWN BY:
MTC
CHK'D BY:
SWL
AND TYPES PER THE CARWASH EQUIPMENT PLANS. INSTALL ALL CONTROL REQUIREMENTS WITH -OWNER PRIOR TO ROUGH -IN.
CIRCUITS IN SEPARATE CONDUIT FROM LINE VOLTAGE CONDUCTORS.
7.
CONDUIT SHALL TRAVEL DOWN FACE OF CMU WALL, UNDER WINDOW TO
PROJECT TITLE:
4. PROVIDE CONDUIT UNDER FLOOR SLAB FROM EQUIPMENT ROOM TO
LOCATION. COORDINATE SPECIFICS WITH OWNER PRIOR TO INSTALLATION.
CARWASH TUNNEL FOR CONTROL WIRING, PNEUMATIC TUBING, HYDRAULIC
LINES, ETC. AS SHOWN ON THE CARWASH EQUIPMENT PLANS.
8.
J-BOXS FOR VACUUM ROOM. COORDINATE LOCATIONS WITH OWNER PRIOR TO
ROUGH -IN.
1
INDOOR WET LOCATIONS NOTES:
GENERAL NOTES:
1. COORDINATE MECHANICAL EQUIPMENT LOCATIONS AND
U)
Q
;
CARWASH TUNNEL IS AN INDOOR WET LOCATION. USE ONLY THE FOLLOWING
WIRING METHODS IN THE AREA.
ELECTRICAL EQUIPMENT REQUIREMENTS WITH THE
MECHANICAL PLANS AND CONTRACTOR.
W
1. CONCEAL ALL CONDUITS WITHIN FINISHED WALLS AND CEILING. EMT
CONDUIT MAY BE USED ABOVE CEILINGS AND CONCEALED IN CONCRETE
2.
PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH NEW
BRANCH CIRCUIT.
J
_
BLOCK WALLS.
2. PROVIDE GASKETED COVER PLATES FOR ALL FLUSH MOUNTED OUTLET AND
DEVICE BOXES.
3.
PROVIDE AN INSULATED GREEN EQUIPMENT GROUND
CONDUCTOR IN EACH RACEWAY.
U
`^
V)
\
r^
v )
w
3. PROVIDE SCHEDULE 40 PVC CONDUIT WITH PVC BOXES WHERE EXPOSED
CONDUIT IS BEING UTILIZED.
4.
PRIOR TO ROUGH -IN, FIELD COORDINATE ALL RECEPTACLE AND
DATA OUTLET LOCATIONS IN THE OFFICE AREA WITH THE GC
AND THE MILLWORK INSTALLER.
) `^
v
WN
I—
4. PROVIDE SCHEDULE 40 PVC CONDUIT FOR UNDER FLOOR CONDUIT AS
REQUIRED BY THE ELECTRICAL SPECIFICATION NOTES, SHEET E001,
EXCEPT THAT GALVANIZED RIGID STEEL CONDUIT (GRC) ELBOWS WILL NOT
5.
COORDINATE MECHANICAL EQUIPMENT DISCONNECT SWITCH
LOCATIONS WITH THE MC PRIOR TO ROUGH -IN. DISCONNECT
SWITCH SHALL BE READILY ACCESSIBLE PER ARTICLE 100 OF
Q�1
0-
X
O
BE REQUIRED FOR CONDUIT RUNS LESS THAT 150 L.F. AND GRC
PENETRATIONS THROUGH FLOOR WILL NOT BE REQUIRED WHERE NOT
SUBJECT TO DAMAGE.
5. PROVIDE LIQUID -TIGHT FLEXIBLE STEEL CONDUIT WITH STAINLESS STEEL
6.
THE NEC.
REFER TO SHEET E202 FOR THE MOTOR CONTROL CENTER
SCHEDULE'MCC' AND THE CARWASH EQUIPMENT CONNECTION
SCHEDULE. PROVIDE "LOCK -OUT' PADLOCK PROVISIONS FOR
S
_
V
OR NYLON COMPRESSION CONNECTORS WHERE REQUIRED FOR
EACH MOTOR CONNECTION THAT DOES NOT HAVE A LOCAL
CONNECTION TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION.
DISCONNECTING MEANS AT THE MOTOR. COORDINATE WITH THE
MAKE ALL CONNECTORS WRENCH -TIGHT.
CAR WASH EQUIPMENT INSTALLER FOR ALL ELECTRICAL
REQUIREMENTS.
SHEET TITLE:
ELECTRICAL
POWER PLAN
SAVANT
Engineering, LLC
5064 Roswell Road, Suite D-301
Sandy Springs GA 30342 770.319.7400
Project20147 02020
'FRTTFTCATF OF AT TTHORT7ATn1N 8006R 17
PROJECT NO: 19066
E101
ARCHITECT OF RECORD:
ELECTRICAL - LIGHTING PLAN
SCALE: 3/16" = V-0"
LIGHTING CONTROL SCHEDULE
DESIG.
CIRCUITS CONTROLLED
TYPE
POLES
SCHEDULE
CC1
H-7,9
EOMH
4
TIMECLOCK ON/TIMECLOCK OFF
CC2
H-1,3,5
EOMH
6
PHOTOCELL ON/TIMECLOCK OFF
NOTES:
GENERAL NOTES:
1. COORDINATE LIGHT FIXTURE LOCATIONS WITH THE ARCHITECTS
REFLECTED CEILING PLAN.
2. WHERE BRANCH CIRCUIT HOMERUNS INDICATE WIRE SIZES, USE
THAT WIRE SIZE THROUGHOUT THE BRANCH CIRCUIT, INCLUDING
SWITCH LEGS.
3. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW BRANCH
CIRCUIT. MULTI -WIRE BRANCH CIRCUITS WILL NOT BE ALLOWED.
4. PROVIDE AN INSULATED GREEN EQUIPMENT GROUND
CONDUCTOR IN EACH RACEWAY.
LEGEND NOTES:0
1. TO LIGHTING FIXTURES AT PAY CANOPIES. SEE SHEET E100 FOR MORE DETAILS.
2. LIGHTING CONTROLS TO PROVIDE DUAL LEVEL ILLUMINATION ARE NOT
REQUIRED WHEN LIGHTING FOR THE SPACE CONSUMES LESS THAN 0.6 W/SF,
PER 2015 IECC 405.2.2.1 EXCEPTION 2.2.
THOMAS E. MORGAN, JR.
ARCHITECT
423 FISC TIER TRAIL
ELLIJAY. GEORGIA 30540
TT W. UNDELOW
Lk. No. 055170
1- I I- t -,4
mmm
DESIGN GROUP
3450 Acworth Due West Road
Building 100, Suite 120
Kennesaw, Georgia 30144
P.770-917-9172
F.770-917-9470
www.mrpdesign.com
ISSUES/REVISIONS
DATE I DESCRIPTION
J8. 18.201 COLORED ELEVATIONS SUBMITTAL
DRAWN BY: MTC
CHKD BY: SWL
PROJECT TITLE:
5. PROVIDE BLOCKING IN CEILING AS REQUIRED FOR SURFACE
MOUNTED FIXTURE SUPPORTS. DO NOT USE SHEETROCK OR
OTHER CEILING SYSTEMS AS THE ONLY MEANS OF FIXTURE
_
SUPPORT.
'
6. VERIFY THE COLOR OF THE DEVICES AND COVER PLATES FOR
`
>
THE LIGHTING CONTROL SYSTEM WITH THE ARCHITECT.
G�
_
W
N�
INDOOR WET LOCATIONS NOTES:
J
Q
CARWASH TUNNEL IS AN INDOOR WET LOCATION. USE ONLY THE FOLLOWING
/ 1
>
WIRING METHODS IN THE AREA.
U)
1. CONCEAL ALL CONDUITS WITHIN FINISHED WALLS AND CEILING. EMT
CONDUIT MAY BE USED ABOVE CEILINGS AND CONCEALED IN CONCRETE
`�^^J
)
V�/
U)
W
(—
BLOCK WALLS.
w
2. PROVIDE GASKETED COVER PLATES FOR ALL FLUSH MOUNTED OUTLET AND
mo/
(�1)
O
DEVICE BOXES.
0—
J
X
3. PROVIDE SCHEDULE 40 PVC CONDUIT WITH PVC BOXES WHERE EXPOSED
CONDUIT IS BEING UTILIZED.
W
Q
4. PROVIDE SCHEDULE 40 PVC CONDUIT FOR UNDER FLOOR CONDUIT AS
i
REQUIRED BY THE ELECTRICAL SPECIFICATION NOTES, SHEET E001,
EXCEPT THAT GALVANIZED RIGID STEEL CONDUIT (GRC) ELBOWS WILL NOT
BE REQUIRED FOR CONDUIT RUNS LESS THAT 150 L.F. AND GRC
PENETRATIONS THROUGH FLOOR WILL NOT BE REQUIRED WHERE NOT
SUBJECT TO DAMAGE.
5. PROVIDE LIQUID -TIGHT FLEXIBLE STEEL CONDUIT WITH STAINLESS STEEL
OR NYLON COMPRESSION CONNECTORS WHERE REQUIRED FOR
CONNECTION TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION.
MAKE ALL CONNECTORS WRENCH -TIGHT.
SAVANT
Engineering,
SHEET TITLE:
ELECTRICAL
LIGHTING PLAN
PROJECT NO: 19066
E102
5064 Roswell Road, Suite D-301
ly Springs GA 30342 770.319.7400
Proiect 20147 02020
ARCHITECT OF RECORD:
EQUIPMENT LIST
RESPONSIBILITY MATRIX
ITEM #
DESCRIPTION
VOLT
HP
0
AMP
GCB
MS
ELECTRICAL WORK
PANEL/CIRCUIT
WIRE SIZE
FURN. BY:
ERECTED BY:
WIRED BY:
CWC-SYS
CARWASH CONTROL SYSTEMS
120
1
20
SONNY'S
GC
GC
L-2
2#12,1912(G), 1r2'C.
1-A
RECLAIM PUMP STATION
480
5HP
3
7.6A
15
SONNY'S
SCWI
GC
H-14,16,18 (CONTROL: L-24)
3912, 1#12(G), 3/4"C.
1-D
(R.O.) FILTRATION SYSTEM
480
2HP
3
3.4A
15
SONNY'S
SCWI
GC
H-20,22,24 (CONTROL: L-38)
3912, 1#12(G), 3/4"C.
1-E
(R.O.) REPRESSURIZER
480
2HP
3
3.4A
15
SONNY'S
SCWI
GC
H-26,28,30 (CONTROL: L-38)
3912, 1#12(G), 3/4"C.
1-H
WATER PRESSURIZATION PUMP
480
5HP
3
7.6A
15
SONNY'S
SCWI
GC
H-32,34,36
3912, 1#12(G), 3/4"C.
1-P
WATER SOFTENER SYSTEM (25CF)
120
1
OAA
15
SONNY'S
SCWI
GC
H-32,34,36
3912, 1#12(G), 3/4"C.
1-X
R.O. REJECT PUMP
480
5HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-1
NOTE 1
2-A
PREP GUN UNIT
480
7.5HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-2
NOTE 1
2-A
PREP GUN UNIT
480
7.5HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-3
NOTE 1
1 O-A
AIR COMPRESSOR
480
10HP
3
14A
25
BY OTHERS
N/A
GC
H-27,29,31
3910, 1910(G), 3/4"C.
1 O-A
AIR COMPRESSOR
480
10HP
3
14A
25
BY OTHERS
N/A
GC
H-33,35,37
3910, 1910(G), 3/4"C.
10-L
AIR DRYER SO.CFM (COMPRESSOR 15)
120
114HP
1
5.8A
15
BY OTHERS
N/A
GC
L-16
2#12, 1#12(G), 1r2'C.
11-B
WRAP BRUSH POWER PACK
480
7.6HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG4
NOTE 1
11-BB
WRAP BRUSH POWER PACK
480
7.6HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-5
NOTE 1
11-1
TGB_FPS POWER PACK
480
7.SHP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-6
NOTE 1
12 -A
OMNI POWER UNIT
480
5HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-7
NOTE 1
13-C
H-25 OMNI PUMP TOP (91)
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-8
NOTE 1
13-F
H-25 OMNI PUMP SIDE (#1)
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-9
NOTE 1
13-M
H-25 PENDULUM PUMP
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-10
NOTE 1
18-B
CONVEYOR POWER UNIT
480
10HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-11
NOTE 1
18-B
CONVEYOR POWER UNIT
480
10HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-12
NOTE 1
20-B
PROGRAMMER PUSHBUTTON STATION
120
1
20
SONNY'S
GC
L-25
2912, 1#12(G), 1r2'C.
20-C
PAY STATION (3)
120
1
20
SONNY'S
SCWI
GC
L-13,15,17
(3) 2912, 1#12(G), 1r2'C.
20-D
GATE (3)
120
1
20
SONNY'S
SCWI
GC
L49,51,53
(3)2912,1912(G), 1r2'C.
20-1
LICENSE PLATE RECOGNITION (3)
120
1
20
SONNY'S
SCWI
GC
L-50,52,54
(3) 2#12, 1#12(G), 1r2-C.
21
MOTOR CONTROL CENTER (MCC)
480
3
SONNY'S
SCWI
GC
SEE"MCC"SCHEDULE
SEE RISER DIAGRAM
22-E
WARNING HORN
120
1
SONNY'S
SCWI
GC
L-27
2#12, 1#12(G), 1Y2"C.
234
MITTER/MOTOR SFM901 (FB)
480
2HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-13
NOTE 1
24-G
TOP BRUSH MOTOR
480
1HP
1 3
INOTEI
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-14
NOTE 1
2"
TOP BRUSHIMOTOR BnD
480
1HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-16
NOTE 1
25-A
BLOWER MOTOR NO. 1
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-16
NOTE 1
25-13
BLOWER MOTOR NO. 2
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-17
NOTE 1
25-C
BLOWER MOTOR NO. 3
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-18
NOTE 1
25-D
BLOWER MOTOR NO.4
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCC-19
NOTE 1
25-E
BLOWER MOTOR NO. 5
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-20
NOTE 1
25-F
BLOWER MOTOR NO.6
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-21
NOTE 1
25-G
BLOWER MOTOR NO. 7
480
15HP
3
NOTE 1
NOTE 1
NOTEI_
SONNY'S
SCWI
GC
MCG-22
NOTE 1
25-H
BLOWER MOTOR NO. 8
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-23
NOTE 1
254
BLOWER MOTOR NO. 9
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-24
NOTE 1
25J
BLOWER MOTOR NO. 10
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-25
NOTE 1
25-K
BLOWER MOTOR NO. 11
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-26
NOTE 1
25-1-
BLOWER MOTOR NO. 12
480
15HP
3
NOTE 1
NOTE 1
NOTE 1
SONNY'S
SCWI
GC
MCG-27
NOTE 1
27-B
U. SOUND SENSOR CONTROL BOX
120
-
1
0.25A
20
-
SONNY'S
SCWI
GC
L-7
2912, 1#12(G), 1r2-C.
27-C
CONVEYER PULSE CONTROL BOX
120
1
0.25A
20
SONNY'S
SCWI
GC
L-7
2912, 1#12(G), 1r2-C.
29-3
PIPE LIGHT, LED IP69K (SIGN)
120
1
0.57A
20
SONNY'S
SCWI
GC
L-7
2912, 1#12(G), 1r2-C.
30-C
(WAIT& GO) INSTRUCTIONAL SIGN
120
1
2.5A
20
SONNY'S
SCWI
GC
L-39
2912, 1#12(G), 1r2-C.
30-E
ENTRANCE INSTRUCTIONAL CABINET
120
1
20
SONNY'S
SCWI
GC
L-11
2912, 1#12(G), 1r2-C.
30-G
PKG. RECEIVED SIGN
120
1
20
SONNY'S
SCWI
GC
L-29
2912, 1#12(G), 1r2-C.
304
MENU 6'HX3W
120
1
20
SONNY'S
SCWI
GC
L-19,21,23
(3) 2#12, 1#12(G), 1r2-C.
33-D
BOOSTER PUMP
480
7.SHP
3
11A
20
1
SONNY'S
SCWI
GC
MCG-28
5#12, 1#12(G), 3/4"C.
NOT USED
-
37-K
VACUUM (30HP)
480
30HP
3
40A
80
3
SONNY'S
SCWI
GC
MCC-30
3#8, 1#8(G), 1"C.
37-K
VACUUM (30HP)
480
30HP
3
40A
80
3
SONNY'S
SCWI
GC
MCC-31
3#8, 1#8(G), 1"C.
37-K
VACUUM (30HP)
480
30HP
3
40A
80
3
SONNY'S
SCWI
GC
MCC-32
3#8, 1#8(G), 1"C.
38
MAT. MACHINE
120
1
20
SONNY'S
SCWI
GC
L-32
2#12, 1#12(G), 1r2"C.
NOTES:
SEE MCC SCHEDULE.
SCWI = SONNY'S (CAR WASH INSTALLER)
GC= GENERAL CONTRACTOR
NOTE:
VERIFY ALL REQUIREMENTS WITH
CARWASH INSTALLER PRIOR TO
ROUGH -IN.
MOTOR CONTROL PANEL: MCC TYPE: UL508
INDUSTRIAL CONTROL PANEL SEE NOTES 1 & 3
SERVICE: 480V/30/3W
I MAIN: 600A MAIN LUGS
CKT
#
SONNY'S
EQUIP #
(NOTE 2)
EQUIPMENT SERVED
(NOTE 5)
HP
FLA
CKT BKR
SIZE
STARTER
SIZE
MINIMUM WIRE & CONDUIT
(SEE NOTE 4)
1
1-X
R.O. REJECT PUMP
5
7.6
15/3
N/A
3#12, 1#12(G), 3/4"C.
2
2-A
PREP GUN UNIT
7.5
11.0
20/3
1
3#12, 1#12(G), 3/4"C.
3
2-A
PREP GUN UNIT
7.5
11.0
20/3
1
3#12, 1#12(G), 3/4"C.
4
11-B
WRAP BRUSH POWER PACK
7.5
11.0
20/3
1
5#12, 1#12(G), 3/4"C.
5
11-BB
WRAP BRUSH POWER PACK
7.5
11.0
20/3
1
5#12, 1#12(G), 3/4"C.
6
11-1
TGB_SF13 POWER PACK
7.5
11.0
20/3
1
5#12, 1#12(G), 3/4"C.
7
12-A
OMNI POWER UNIT
5
7.6
15/3
0
5#12, 1#12(G), 3/4"C.
8
13-C
H-25OMNI TOP PUMP
15
21.0
40/3
2 (VFD)
3#8, 1#8(G), 1"C.
9
13-F
H-25 OMNI SIDE PUMP
15
21.0
40/3
2 (VFD)
3#8, 1#8(G), 1"C.
10
13-M
H-25 PENDULUM PUMP
15
21.0
40/3
2 (VFD)
3#8, 1#8(G), 1"C.
11
18-B
CONVEYOR POWER PACK
10
14.0
30/3
1
5#10, 1#10(G), 3/4"C.
12
18-B
CONVEYOR POWER PACK
10
14.0
30/3
1
5#10, 1#10(G), 3/4"C.
13
23-4
MITER MOTOR (FB)
2
3.4
15/3
00 (VFD)
3#12, 1#12(G), 3/4"C.
14
24-G
TOP BRUSH MOTOR
1
2.1
15/3
00 (VFD)
3#12, 1#12(G), 3/4"C.
15
25-8
TOP BRUSH/MOTOR BnD
1
2.1
15/3
00
3#12, 1#12(G), 3/4"C.
16
25-A
BLOWER MOTOR NO. 1
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
17
25-B
BLOWER MOTOR NO. 2
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
18
25-C
BLOWER MOTOR NO. 3
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
19
25-D
BLOWER MOTOR NO. 4
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
20
25-E
BLOWER MOTOR NO. 5
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
21
25-F
BLOWER MOTOR NO. 6
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
22
25-G
BLOWER MOTOR NO. 7
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
23
25-H
BLOWER MOTOR NO. 8
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
24
25-1
BLOWER MOTOR NO. 9
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
25
25-J
BLOWER MOTOR NO. 10
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
26
25-K
BLOWER MOTOR NO. 11
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
27
25-L
BLOWER MOTOR NO. 12
15
21.0
40/3
2
3#8, 1#8(G), 1"C.
28
33-D
BOOSTER PUMP
7.5
11.0
20/3
N-A
5#12, 1#12(G), 3/4'C.
29
SPARE
30
37-K
VACUUM
30
40.0
80/3
3
3#8, 1#8(G), 1"C.
31
37-K
VACUUM
30
40.0
80/3
3
3#8, 1#8(G), 1"C.
32
37-K
VACUUM
30
40.0
80/3
3
3#8, 1#8(G), 1"C.
ALL TERMINATIONS SHALL BE SUITABLE FOR
75°C COPPER OR ALUMINUM
TOTAL CONN. AMPS 585.8
FURNISHED WITH INTERIOR MAINTENANCE
LIGHT (SEE NOTE 6)
TOTAL VOLT AMPS 486,780
NOTES:
1. CONTROL PANEL IS FURNISHED WITH WASH TUNNEL EQUIPMENT (BY SONNY'S ENTERPRISES, INC.). EC TO COORDINATE EXACT LOCATIONS
OF INDICATED EQUIPMENT, MAKE FINAL CONNECTIONS, AND WIRE COMPLETE.
2. ALPHA -NUMERIC DESIGNATIONS IN THIS COLUMN CORRESPOND TO CARWASH EQUIPMENT PROVIDED BY CARWASH MANUFACTURER. SEE
SONNY'S CARWASH PLANS (CWP) FOR LOCATIONS.
3. INFORMATION SHOWN ON THIS SCHEDULE SHOWS MINIMUM POWER WIRING REQUIREMENTS FOR LOADS SERVED BY THIS UL 508 1
INDUSTRIAL CONTROL PANEL. CONTRACTOR SHALL REFERENCE SONNY'S CARWASH PLANS (CWP) FOR PRECISE LOAD LOCATIONS,
CONTROL WIRING, & RACEWAY REQUIREMENTS. DESIGN OF 24 VAC CONTROLS ARE NOT A PART OF THIS DESIGN BUT SHALL BE INCLUDED
IN CONTRACTOR'S SCOPE OF WORK. SEE SONNY'S CARWASH PLANS (CWP), ATTACHED TO THIS SET, FOR OTHER WIRING AND RACEWAY
REQUIREMENTS. 24 VAC CONTROL WIRING & RACEWAYS SHALL BE INSTALLED BY CONTRACTOR PER CWP PLANS.
1
4. FEEDERS INDICATED IN THIS SCHEDULE ARE SUFFICIENT FOR THE SCHEDULED LOADS INDICATED. HOWEVER, IN SOME CASES, THE
EQUIPMENT MANUFACTURER MAY INDICATE AN ENHANCED INSTALLATION (SHOWING LARGER WIRE AND/OR RACEWAYS). EC SHALL
COORDINATE FINAL LAYOUT AND, WHERE FEASIBLE AND OTHERWISE ALLOWED BY THE NATIONAL ELECTRICAL CODE, CONTRACTOR MAY
INSTALL THE LARGER CONDUCTORS AND/OR RACEWAYS INDICATED ON THE SONNY'S DOCUMENTS.
5. SAFETY DISCONNECTS SHALL BE PROVIDED ADJACENT TO ALL EQUIPMENT THAT IS >50'-0" OR NOT IN THE LINE OF SIGHT OF THE MCC.
6. PROVIDE A 120-VOLT CIRCUIT TO POWER INTERIOR MAINTENANCE LIGHT (I.E. LIGHT IS OPERABLE WHEN PANEL IS DE -ENERGIZED FOR t
MAINTENANCE).
SCHEDULE OF PANEL H
CKT.
NO.
TRIP
L
DESCRIPTION
LTS
REC
HTG
A/C
MTR
MISC
A B C
MISC
MTR
A/C
HTG
REC
LTS
DESCRIPTION
TRIP
ni F
CKT.
NO.
1
20/1
SIGN LIGHTING
1.2
40
0.8
DOOR JET HEATER (DJ-1)
15
2
3
20/1
CANOPY & POLE LIGHTING
1.1
0.8
DOOR JET HEATER (DJ-1)
4
5
20/1
SECURITY/SITE LTG
0.3
0.8
DOOR JET HEATER (DJ-1)
3
6
7
20/1
OFFICE/EQUIP RM LTG
0.9
40
0.8
DOOR JET HEATER (DJ-2)
15
8
9
20/1
WASH TUNNEL LTG
1.0
0.8
DOOR JET HEATER (DJ-2)
10
11
20/1
SPARE
0.0
0.8
DOOR JET HEATER (DJ-2)
3
12
13
20/1
SPARE
0.0
40
2.1
RECLAIM P.S. (1-A)
15
14
15
SPACE
2.1
RECLAIM P.S. (1-A)
16
17
SPACE
2.1
RECLAIM P.S. (1-A)
3
18
19
SPACE
40
0.9
R.O. FILT. PUMP (1-D)
15
20
21
SPACE
0.9
R.O. FILT. PUMP (1-D)
22
23
SPACE
0.9
R.O. FILT. PUMP (1-D)
3
24
25
25
AIR COMPRESSOR (10-A)
3.9
0.9
R.O. PRESS. PUMP (1-E)
15
26
27
AIR COMPRESSOR (10-A)
3.9
0.9
R.O. PRESS. PUMP (1-E)
28
29
3
AIR COMPRESSOR (10-A)
3.9
40
0.9
R.O. PRESS. PUMP (1-E)
3
30
31
25
AIR COMPRESSOR (10-A)
3.9
2.1
WATER PRESS. PUMP (1-H)
15
32
33
AIR COMPRESSOR (10-A)
3.9
2.1
WATER PRESS. PUMP (1-H)
34
35
3
AIR COMPRESSOR (1O-A)3.9
2.1
WATER PRESS. PUMP (1-H)
3
36
37
600
MOTOR CONTROL PANEL
162.3
0.0
S.O.
15
38
39
MOTOR CONTROL PANEL
162.3
0.0
S.O.
40
41
3
MOTOR CONTROL PANEL
162.3
0.0
S.O.
3
42
43
SPACE
4
2.4
0.3
0.9
0.4
2.6
0.4
PANEL L
50
44
45
SPACE
2.4
0.3
0.9
0.4
2.6
0.4
PANEL L
46
47
1
SPACE
2.4
0.3
0.9
0.4
2.6
0.4
PANEL L
3
48
CATEGORY TOTALS CONNECTED (KVA)
4.5
510.3
7.21
18.9
2.7
6.0
7.8
1.2
CATEGORY TOTALS CONNECTED (KVA)
800A MCB MAIN RATING
1 277/480 VAC
3 PHASE
4 WIRE
PROVIDE FEED-THRU LUGS: NO
TOTAL CONNECTED LOAD: 558.4
MINIMUM BREAKER AIC: 65,000
PROVIDE IG BUS BAR: NO I
NEMA RATING: 1
I MOUNTING: SURFACE
I TOTAL DEMAND LOAD: 593.0
�c -DENOTES PROVIDE LOCK -ON CIRCUIT BREAKER
+ -DENOTES PROVIDE GFCI CIRCUIT BREAKER
# -DENOTES PROVIDE AFCI CIRCUIT BREAKER
NOTES:
1. BREAKER TO BE 100% RATED FOR CONTINUOUS DUTY.
SCHEDULE OF PANEL L
CKT.
NO.
TRIP
DESCRIPTION
LTS
REC
HTG
A/C
MTR
MISC
A B C
MISC
MTR
A/C
HTG
REC
LTS
DESCRIPTION
TRIP
CKT.
1
20/1
RCPT- EQUIP ROOM
0.8
2.0
UH-2
30
2
3
20/1
RCPT - ELEC ROOM
0.8
2.0
UH-2
2
4
5
20/1
SPARE
0.2
7
20/1
TUNNEL (29-3, 27-B,C)
0.3
40
SPARE
20/1
8
9
20/1
SPARE
0
0.7
EXHAUST FAN (EF-5)
20/1
10
11
20/1
ENTRANCE SIGN (30E)
0.2
40
0.2
0.6
BATHROOM LTG/EF-1/2
20/1
12
13
20/1
PAY STATION (20-C)
0.2
40
0.5
GAS IR & UNIT HTRS
20/1
14
15
20/1
PAY STATION (20-C)
0.2
40
0.7
AIR DRYER (10-L)
20/1
16
17
20/1
SPARE
40
0.5
WATER SOFTENER (1-P)
20/1
18
19
20/1
MENU SIGN (30-1)
0.2
40
0.3
NEON SIGNS
20/1
20
21
20/1
MENU SIGN (30-1)
0.2
40
0.3
NEON SIGNS
20/1
22
23
20/1
SPARE
40
0.3
CONTROL (1-A)
20/1
24
25
20/1
INPUT TERMINAL (20-13)
0.2
0.5
WATER HEATER (WH-1)
20/1
26
27
20/1
WARNING HORN (22-E)
0.2
40
1.4
CU-1
20
28
29
20/1
PKG RCVD SIGN (30G)
0.2
40
1.4
C1 1-1
2
30
31
20/1
SPARE
1.0
MAT WASH (38)
20/1
32
33
20/1
SPARE
1.0
+ RCPT - VENDING
20/1
34
35
20/1
SERVER COMPUTER
0.8
1.0
+ RCPT - VENDING
20/1
36
37
20/1
RECEPTACLES
1.0
40
0.3
CONTROL (1-D,E)
20/1
38
0.3
40
SPARE
20/1
40
41
20/1
RCPT - OPERATIONS
0.36
1.5
GATE OVERRIDE
20/1
42
43
20/1
RCPT -OFFICE
0.8
40
/
I
1.5
VACUUM RM JB
20/1
46
47
20/1
RECEPTACLES
1.08
40
1.5
VACUUM RM JB
20/1
48
49
20/1
GATE (20-D)
0.2
40
51
20/1
GATE (20-D)
0.2
40
0.2
LICENSE (20-1)
20/1
52
53
20/1
SPARE
0.2
LICENSE (20-1)
20/1
54
5
20/1
WASHER
0.2
SPACE
56
57
30
UH-3
2.0
SPACE
58
59
2
1 IH-3
2.0
P C
6
CATEGORY TOTALS CONNECTED (KVA)
5.8
4.0
3.4
8.4
1.1
2.8
4.5
2.0
1.2
CATEGORY TOTALS CONNECTED (KVA)
100A MCB MAIN RATING
1 120/208 V C 1
3 PHASE
4 WIRE
PROVIDE FEED-THRU LUGS: NO
TOTAL CONNECTED LOAD: 33.2
MINIMUM BREAKER AIC: 42,000
PROVI E IG BUS BAR: NO
NEMA RATING: 1
MOUNTING: RECESSED
TOTAL DEMAND LOAD: 33.5
�c -DENOTES PROVIDE LOCK -ON CIRCUIT BREAKER
+ -DENOTES PROVIDE GFCI CIRCUIT BREAKER
-DENOTES PROVIDE AFCI CIRCUIT BREAKER
NOTES:
SAVANT
Engineering,
THOMAS E. MORGAN, JR
ARCHITECT
423 FISCHER TRAIL
ELLIJAY. GEORGIA 30540
TT W. UNDELOW
Lk. No. 055170
h-I,,tL'
mmm
DESIGN GROUP
3450 Acworth Due West Road
Building 100, Suite 120
Kennesaw, Georgia 30144
1 P.770-917-9172
F.770-917-9470
W W W.mrpdesign.com
ISSUES/REVISIONS
DATE I DE5CPJPTION
D8. 18.201 COLORED ELEVATIONS SUBMITTAL
DRAWN BY: MTC
CHK'D BY:
PROJECT TITLE:
1 U'^)
vJ \
Q
N� W
U >
1 W�/w
U)
LL]
0�0
0- J
X ry
W Q
� U
SHEET TITLE:
SWL
ELECTRICAL
PANEL SCHEDULES
PROJECT NO: 19066
E202
5064 Roswell Road, Suite D-301
ly Springs GA 30342 770.319.7400
Proiect 20147 02020
ARCHITECT OF RECORD:
H.V.A.C. LEGEND:
®
SUPPLY DIFFUSER
RETURN AIR GRILLE
®
EXHAUST AIR GRILLE
x/x
RIGID DUCTWORK (WIDTH/DEPTH)
FLEX DUCTWORK (DIAMETER)
ELBOW WITH TURNING VANES
{
MANUAL VOLUME DAMPER
MVD
MOTORIZED VOLUME DAMPER
ED
FIRE DAMPER
SD
DUCT MOUNTED SMOKE DETECTOR
OT
THERMOSTAT
IS
HUMIDISTAT
TS
TEMPERATURE SENSOR
1
1
1
H.V.A.C. KEYNOTES OX :
1. ROUTE FULL SIZE CONDENSATE FROM AHU WITH
P-TRAP DOWN IN EXTERIOR WALL AND
TERMINATE 8" ABOVE FINISHED GRADE WITH
TURNED DOWN ELBOW.
2. ROUTE REFRIGERANT LINE FROM AHU TO
CONDENSING UNIT.
3. ROUTE INSULATED OUTSIDE AIR DUCT TO
EXTERIOR WALL CAP. CAP MINIMUM 10'-0"
FROM ANY EXHAUST OR PLUMBING VENTS.
PROVIDE MANUAL VOLUME DAMPER TO
BALANCE OUTSIDE AIR AS REQUIRED.
4. COMBUSTION AIR FOR UHUH=1 PROVIDED BY
UNCONFINED SPACE - APPROX. 10,000 CF.
5. COMBUSTION AIR PROVIDED BY UNCONFINED
SPACE - APPROX. 22,000 CF.
6. 24X24 DUCT WITH 120V MOTORIZED DAMPER
INTERLOCKED WITH EF-3. SET DAMPER TO
OPEN AT OPERATION OF FAN.
7. COORDINATE LOCATION WITH ROLL -UP DOORS.
INSTALL 2 FT BELOW PLASTIC LINER ON
CEILING PER MANUFACTURER'S
8. COORDINATE AHU LOCATION ABOVE CEILING.
THERMOSTAT SHALL BE DESIGNED FOR WET
LOCATIONS.
10. ROUTE FLUE VENT TO ROOF. PROVIDE ALL
REQUIRED CLEARANCES. INSTALL PER
MANUFACTURER'S INSTRUCTIONS.
11. ROUTE GALV. STEEL EXHAUST DUCT TO CAP
AT EXTERIOR WALL.
12. 4" DRYER DUCT FROM OWNER PROVIDED DRYER
13. ROUTE GALV. STEEL EXHAUST DUCT TO CAP
ON ROOF. MAINTAIN 10'-0" FROM ANY AIR
INTAKES.
1 FLOOR PLAN - H.V.A.C.
M101 3/ 1 G" = 1'-0"
H.V.A.C. GENERAL NOTES:
1. COORDINATE ALL MECHANICAL WORK WITH ALL
OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS BEFORE THE START OF WORK.
2. TRANSITION ALL SUPPLY AND RETURN
DUCTWORK FROM PACKAGED ROOFTOP
EQUIPMENT TO DUCT THROUGH ROOF (DTR)
SIZE. COORDINATE EXACT LOCATIONS WITH
ROOF AND WALL STRUCTURAL SYSTEM. VERIFY
ADEQUACY OF STRUCTURE TO SUPPORT
MECHANICAL EQUIPMENT WITH ARCHITECT PRIOR
TO INSTALLATION.
3. LINE ALL RECTANGULAR AIR CONDITIONING
DUCTWORK WITH 1" THICK DUCT LINER PER
SPECIFICATIONS.
4. ALL DUCT ELBOWS SHALL BE MITERED WITH
SINGLE THICKNESS TURNING VANES UNLESS
INSTRUCTED OTHERWISE ON DRAWINGS. PROVIDE
45 DEGREE ENTRY FITTINGS AT BRANCH DUCT
CONNECTIONS TO DUCT MAINS. FLEXIBLE DUCTS
SHALL BE INSTALLED TO MAINTAIN FULL
CROSS -SECTIONAL FREE AREA. PROVIDE RIGID
SHEET METAL ELBOWS OR LINED PLENUM
BOXES AT AIR DEVICES WHEN REQUIRED.
5. COORDINATE EXACT LOCATION OF ALL AIR
DEVICES WITH ARCHITECTURAL REFLECTED
CEILING PLAN.
6. ROUTE CONDENSATE WITH MINIMUM SLOPE OF
1/8" PER 1'-0".
7. ROUTE DUCTS FROM TOILET EXHAUST FANS TO
ROOF CAPS. CONCEAL DUCTWORK. ROOF CAPS
SHALL BE FLASHED WEATHERTIGHT. OFFSET
EXHAUST DISCHARGE AS REQUIRED ENSURING A
MINIMUM 10'-0" CLEARANCE FROM ALL
OUTSIDE AIR INTAKES.
8. ALL LOW VOLTAGE CONTROL WIRING AND ITS
INSTALLATION TO BE BY MECHANICAL
CONTRACTOR. INSTALL PER ELECTRICAL
SPECIFICATIONS. MOUNTING HEIGHT OF
THERMOSTATS SHALL BE PER ADA
REQUIREMENTS.
9. VERIFY ADEQUACY OF GAS APPLIANCE VENT
SIZES BASED ON ACTUAL INSTALLATION (TOTAL
VENT HEIGHT AND ANY LATERAL OFFSETS).
INSTALLATION SHALL COMPLY WITH ALL CODE
REQUIREMENTS. PROVIDE TYPE "B" VENT PIPING
AND U.L. LISTED CAP.
10. MECHANICAL CONTRACTOR SHALL REVIEW ALL
ELECTRICAL DRAWINGS BEFORE PURCHASING
EQUIPMENT TO ENSURE THAT PROPER
ELECTRICAL SERVICE IS TO BE PROVIDED FOR
ALL NEW EQUIPMENT.
11. CLOTHES WASHER EXHAUST DUCT SHALL BE 4"
NOMINAL IN DIAMETER. THE MAXIMUM LENGTH
OF THE EXHAUST DUCT SHALL BE 35
EQUIVALENT FEET FROM THE CONNECTION TO
THE TRANSITION DUCT FROM THE DRYER TO
THE OUTLET TERMINAL.
12. COMPLY WITH THE INTERNATIONAL ENERGY
CONSERVATION CODE AS ADOPTED PER
SECTION 101.2 AND ANY AMENDMENTS OF THE
2015 VIRGINIA CONSTRUCTION CODE.
13. ALL EQUIPMENT IN WASH TUNNEL SHALL BE
APPROVED FOR INSTALLATION IN A WET
LOCATION.
H.V.A.C. SPECIFICATIONS:
15010 MECHANICAL REQUIREMENTS:
DO ALL WORK IN COMPLIANCE WITH ALL APPLICABLE
CODES, LAWS AND ORDINANCES, THE FLORIDA BUILDING
CODE AND THE REGULATIONS OF THE LOCAL UTILITY
COMPANIES. OBTAIN AND PAY FOR ANY AND ALL
REQUIRED PERMITS, INSPECTIONS, CERTIFICATES OF
INSPECTIONS.
COOPERATE WITH OTHER TRADES AND CONTRACTORS AT
JOB. PERFORM WORK IN SUCH MANNER AND AT SUCH
TIMES AS NOT TO DELAY WORK OF OTHER TRADES.
OBTAIN MANUFACTURER'S DATA ON ALL EQUIPMENT, THE
DIMENSIONS OF WHICH MAY AFFECT INSTALLATION. USE
THIS DATA TO COORDINATE PROPER SERVICE
CHARACTERISTICS, ENTRY LOCATIONS, ETC., AND TO
ENSURE MINIMUM CLEARANCES ARE MAINTAINED.
WORKMAN SHALL BE EXPERIENCED IN THEIR RESPECTIVE
TRADE. WORKMANSHIP OF INSTALLED WORK SHALL BE
FIRST CLASS AND WILL BE SO JUDGED. SUBSTANDARD
WORK SHALL BE REMOVED AND REPLACED AT
CONTRACTOR'S EXPENSE.
CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL
MATERIALS AND EQUIPMENT FURNISHED UNDER THIS
SECTION TO BE FREE FROM DEFECTS AND TO FUNCTION
OR OPERATE SATISFACTORILY FOR ONE YEAR AFTER FINAL
ACCEPTANCE OF THE WORK, AND THAT ANY ITEMS NOT
MEETING THIS REQUIREMENT WILL BE MADE GOOD BY HIM
WITHOUT ANY COST TO THE OWNER.
PROVIDE ONLY NEW, STANDARD FIRST -GRADE MATERIALS
THROUGHOUT, CONFORMING TO STANDARDS ESTABLISHED
BY UNDERWRITER LABORATORIES INC., AND SO MARKED
AND LABELED, TOGETHER WITH MANUFACTURER'S BRAND
OR TRADEMARK. ALL LIKE ITEMS SHALL BE OF ONE
MANUFACTURER.
ALL WORK SHALL BE EXECUTED IN A MANNER THAT
SHALL PRESENT A NEAT APPEARANCE UPON COMPLETION.
CARE SHALL BE EXERCISED THAT ALL ITEMS ARE PLUMB,
STRAIGHT AND LEVEL.
UPON COMPLETION OF WORK, ALL SYSTEMS SHALL BE
TESTED, AND SHALL BE SHOWN TO BE IN PERFECT
WORKING CONDITION IN ACCORDANCE WITH THE INTENT OF
THE DRAWINGS.
ANY WALLS, CEILINGS, EQUIPMENT, ETC., DAMAGED BY THE
CONTRACTOR IN CONSTRUCTION OF THIS PROJECT SHALL
BE REPAIRED, RESTORED AND/OR REPLACED BY THE
CONTRACTOR TO ITS ORIGINAL CONDITION, OR TO
PERFORM ITS INTENDED FUNCTION, AT NO ADDITIONAL
COST TO OWNER.
H.V.A.C. SPECIFICATIONS (,CONT.
15055 PIPING:
PIPING SHALL BE NEW AND IN GOOD CONDITION. ALL
PIPING SHALL CONFORM TO ALL APPLICABLE STATE,
COUNTY AND LOCAL CODES.
PIPING SHALL BE INSTALLED PARALLEL TO BUILDING LINES
PIPING SHALL BE COORDINATED WITH OTHER TRADES
PRIOR TO INSTALLATION. OFFSETS AS REQUIRED TO
COORDINATE WITH STRUCTURE AND OTHER TRADES SHALL
BE MADE AT NO ADDITIONAL COST.
PIPING SHALL BE TESTED IN ACCORDANCE WITH INDUSTRY
ACCEPTED METHODS. LEAKS SHALL BE REPAIRED AND
ANY LOST REFRIGERANT SHALL BE REPLACED AT NO
ADDITIONAL COST.
DIELECTRIC UNIONS SHALL BE INSTALLED IN ALL COPPER
AND FERROUS PIPING CONNECTIONS.
15891 DUCTWORK:
ALL DUCTWORK MATERIALS AND INSTALLATION SHALL
CONFORM TO APPLICABLE STATE, COUNTY AND LOCAL
CODES. DUCTWORK SHALL BE ALL NEW AND IN GOOD
CONDITION.
DUCT DIMENSIONS NOTED ARE INSIDE DIMENSIONS AND DO
NOT INCLUDE INSULATION OR LINER.
DUCTWORK SHALL BE INSTALLED TO AVOID CONFLICT WITH
OTHER TRADES. ANY OFFSETS REQUIRED SHALL BE
INSTALLED AT NO ADDITIONAL COST.
FABRICATE DUCTWORK FROM SHEET METAL. DUCT SHALL
BE INSULATED WITH DUCT WRAP INSULATION. DUCTWORK
SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA LOW
PRESSURE DUCTWORK STANDARDS.
ibY:kI10i1261 W-1lkIIl:L1A_121012F
CONTRACTOR SHALL BE CERTIFIED BY NATIONAL
ENVIRONMENTAL BALANCING BUREAU (NEBB) OR BY
ASSOCIATED AIR BALANCE COUNCIL (AABC).
TEST AND BALANCE ALL AIR SYSTEMS IN ACCORDANCE
WITH AABC AND/OR NEBB REQUIREMENTS. ALL EQUIPMENT
USED FOR TESTING SHALL BE IN PROPER WORKING ORDER.
THE CONTRACTOR SHALL REGULATE AND ADJUST ALL
SPUTTERS, DEFLECTORS AND DAMPERS SO THAT THE
INLET OR OUTLET SHALL DELIVER OR REMOVE THE
REQUIRED NUMBER OF CUBIC FEET OF AIR PER MINUTE
(CFM) AT THE RESPECTIVE OPENINGS.
ALL TESTS SHALL BE CONDUCTED IN THE PRESENCE OF
THE CONSTRUCTION SUPERINTENDENT, OR HIS
REPRESENTATIVE.
THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS,
TESTING EQUIPMENT AND PERSONNEL THAT MAY BE
REQUIRED FOR THE TESTS.
i6XkjM91.1MvIlei .f<_1.U10zN&12 9,
PROVIDE VIBRATION ISOLATORS AND ACOUSTIC INSULATION
AS REQUIRED TO ELIMINATE ANY OBJECTIONABLE NOISE
OR VIBRATION.
SAVANT
Engineering, LLC
5064 Roswell Road, Suite D-301
Sandy Springs GA 30342 770.319.7400
Project 20147 02020
THOMAS E. MORGAN, JR.
ARCHITECT
423 FISC TIER TRAIL
ELLIJAY, GEORGIA 30540
OF
O,
I �QV1r2
01A0N 049916
T1o.
mmm
DESIGN GROUP
3450 Acworth Due West Road
Building 100, Suite 120
Kennesaw, Georgia 30144
P.770-917-9172
F.770-917-9470
www.mrpdesign.com
ISSUES/REVISIONS
DATE DESORIPTION
3.18.20 COLORED ELEVATIONS SUBMITTAL
DRAWN BY: RGV
CHK'D BY: RGV
PROJECT TITLE:
2 >Q
N� w
L.L J
U
``^^ vJ
C`/^) w
vJ
W �
01-10 0
0- J
X 0�
W Q
U
SHEET TITLE:
FLOOR PLAN
H.V.A.C.
PROJECT NO: 19066
M101
:F.RTIFiCATF. OF AUTHORIZATION #006812
COMMERCIAL SPLIT SYSTEM AIR CONDITIONING SCHEDULE
COOLING
HTG
INDOOR UNIT
OUTDOOR UNIT
UNIT
AREA
MANUFA
NOM.
CAPACITY
CAP
FAN
ELECTRIC HEATER
CONDENSER FANS)
COMPRESSOR(S)
WEIG
MODEL
VtEIGH
SEER
HSPF
NOTE(S)
TIC
SC
TOTAL
OA
E.S.P.
FLA
RLA
LRA
LABEL
SERVED
CTURER
TONS
@47°F
MCA
MOCP
MCA
MOCP
HT
(MBH)
(MBH)
(MBH)
CFM
CFM
(IN)
HP
FLA
V/0
KW
STG
V/0
T(LBS)
QTY
V/0
(EA)
Q�
V/0
(EA)
(EA)
(LBS)
AHU-1/
LCN128HV4/
OFFICE
LG
1
12.4
9.9
15.5
250
25
0.1
1.0
30
1
208/1
1.1
1
208/1
12.3
15
90
19.4
10.4
1-5
CU-1
LUU127HV
NOTES:
1. PROVIDE WITH 410A REFRIGERANT.
2. PROVIDE A WALL MOUNTED, 7-DAY PROGRAMMABLE ELECTRONIC THERMOSTATAND WALL MOUNTED ZONE SENSOR.
3. ELECTRICAL CONNECTIONS FOR AHU FAN ARE PROVIDED THROUGH THE CONDENSING UNIT.
4. PROVIDE WITH CASSETTE GRILLE PT-UQC
5. CONTRACTOR TO PROVIDE & INSTALL 24 VAC MOTOROIZED DAMPER IN CA DUCT TO INTERLOCK WITH AHU OPERATION. AHU TRANSFORMER SHALL BE APPROPRIATELY SIZED TO POWER CA DAMPER.
VENTILATION
REQUIREMENT
SCHEDULE
SERVED BY
ROOM
SPACE TYPE
NUMBER
OF PEOPLE
AIRFLOW
RATE REQ'D
PER PERSON
(Rp)
AREA (sf)
OUTDOOR
AIRFLOW
RATE REQ'D
PER SF (Ra)
Rp x P,
Re x A,
BREATHING
ZONE OUTDOOR
AIRFLOW ( bJ
ZONE AIR
DIST.
EFFECT. (EJ
ZONE
OUTDOOR
AIRFLOW
(Vol=Vbz/E,)
OUTDOOR
AIR
INTAKE
REQ'D (V°t)
OUTDOOR
AIR
INTAKE
PROVIDED
OFFICE
OFFICE SPACE
2
5
85
0.06
10
6
16
0.8
20
20
25
AHU-1
20
25
REQUIRED OUTSIDE AIR CFM VALUES BASED ON ASHRAE/ANSI 62.1-2019.
EXHAUST FAN SCHEDULE
UNIT
S.P.
MAX
MOTOR
AREA SERVED
MANUFACTURER
MODEL
LOCATION
TYPE
DRIVE
CFM
NOTE(S)
W
HP
RPM
V/0
LABEL
(IN WG)
SONES
102 - PUBLIC
EF-1
GREENHECK
SP-A110
CEILING
CENTRIFUGAL
DIRECT
75
0.25
5
74
-
950
120/1
1 - 3, 5
RESTROOM
103 - PUBLIC
EF-2
GREENHECK
SP-A110
CEILING
CENTRIFUGAL
DIRECT
75
0.25
5
74
-
950
120/1
1 - 3, 5
RESTROOM
RESTROOM
EF-3
1 -
GREENHECK
SP-A110
CEILING
CENTRIFUGAL
DIRECT
75
0.25
5
74
-
950
120/1
1 - 3, 5
105 -ELECTRICAL/
EF-4
GREENHECK
SP-A390
CEILING
CENTRIFUGAL
DIRECT
300
0.25
5
135
-
1350
120/1
1, 3 - 5
EQUIPMENT RM
105- ELECTRICAL /
P O R
DIRE
1 0
0 5
8
550
1 1
EQUIPMENT RM
101-INDOOR VAC
EF-6 SPACE GREENHECK SP-A390 CEILING CENTRIFUGAL DIRECT 300 0.25 5 135 -
NOTES: 1. PROVIDE WITH FAN SPEED CONTROLLER, BACKDRAFT DAMPER, DISCONNECT SWITCH.
2. FAN SHALL BE CONTROLLED BY LIGHT SWITCH.
3. FAN SOUND RATING SHALL BE 5 SONES OR LESS.
4. FAN SHALL BE CONTROLLED VIA LINE VOLTAGE THERMOSTAT SET TO 80 -F (ADJUSTABLE).
5. PROVIDE WITH GRILLE, FILTER FOR GRILLE AND BRICK VENT FOR WALL TERMINATION.
6. PROVIDE FAN SPEED CONTROLLER, WITH GRAVITY OPERATED DAMPER, OSHA GUARD, NEMA-1 SWITCH, DAMPER GUARD AND CLOSURE ANGLES.
UNIT HEATER SCHEDULE
UNIT
AREA
FUEL
INPUT
OUTPUT
EFF
MOTOR
MANUFACTURER
MODEL
LOCATION
77-7
HP
KW
V/0
LABEL
SERVED
SOURCE
(MBH)
(MBH)
(%)
CEILING
NATURAL
IRH-1
109-TUNNEL
SPACE RAY
PTS-40-N5
40
32
80%
-
-
120/1
HUNG
GAS
CEILING
NATURAL
IRH-2
109-TUNNEL
SPACE RAY
PTS-40-N5
40
32
80%
-
-
120/1
HUNG
GAS
CEILING
NATURAL
DJ-1
109 - TUNNEL
DOOR JET
JDTE 75
750
600
80%
1.5
-
480/3
HUNG
GAS
CEILING
NATURAL
DJ-2
109 - TUNNEL
DOOR JET
JDTE 75
750
600
80%
1.5
-
480/3
HUNG
GAS
108 - EQUIP
CEILING
NATURAL
UH-1
REZNOR
UDAP60
60
50
83%
0.06
-
120/1
ROOM
_tUN
G
WALL
UH-2
RESTROOM
QMARK
AWH4408F
ELECTRIC
-
-
4
208/1
HUNG
WALL
UH-3
RESTROOM
QMARK
AWH4408F
ELECTRIC
4
208/1
HUNG
2. PROVIDE B VENT TYPE FLUE AND HANGER KIT.
3. BURNER CONTROLS ARE TO BE ISOLATED FROM COMUSTION AIR.
4. ALL RADIANT TUBE IS TO BE ALUMINIZED STEEL CONSTRUCTION.
5. RADIANT TUBE LENGHTS SHALL NOT BE ANY SHORTER THAN INDICATED ON DRAWINGS.
GRILLE/DIFFUSER
SCHEDULE
MARK
CFM
SE7F
TYPE
MFG
MODEL
NOTES
0-100
6X6
101-200
8X8
STEEL LOUVERED FACE
A
201-400
10X10
SUPPLY DIFFUSER (4-
PRICE
SMD
1-5
401-525
12X12
WAY)
526-800
14X14
0-150
6X6
151-300
8X8
STEEL PERFORATED
301-500
10X10
CEILING OR SIDEWALL
B
PRICE
PDDR
2-5
501-900
12X12
RETURN OR EXHAUST AIR
901-1400
14X14
GRILLE
1401-2100
18X18
0-150
12X12
151-300
18X12
WIND -DRIVEN RAIN
301-600
18X18
RESISTANT OUTSIDE AIR
OAL, EL
601-850
24X18
GREENHECK
EHH-601
4,16
INTAKE OR EXHAUST
851-1200
24X24
LOUVER
1201-1600
30X24
1601-2000
36X24
NOTES: 1. PROVIDE WITH OPPOSED BLADE BACKDRAFT DAMPER.
2. PROVIDE 24)(24 FULLY LOUVERED FACE LAYIN MODULE WHERE LOCATED IN
LAYIN CEILING.
3. PROVIDE SQUARE TO ROUND NECK TRANSITION WHERE APPLICABLE.
4. COORDINATE BORDER TYPES WITH ARCHITECTURAL FLOOR PLAN AND
REFLECTED CEILING PLAN.
5. COORDINATE FINISH WITH ARCHITECT.
6. LOUVER SHALL BE WIND -DRIVEN RAIN RESISTANT.
1350 120/1 1. 3 - 5
1
UNION
DRAIN PAN
EACH DIMENSION IS
EQUAL TO FAN NEGATIVE
STATIC PRESSURE
1
REMOVABLE CAP
ROUTE TO NEAREST
CONDENSATE RISER
FULL SIZE
OF DRAIN
CONNECTION
3 CONDENSATE DRAIN DETAIL
M201 SCALE: NTS
NOTES
SPIN -IN
COLLAR
MANUAL
VOLUME
DAMPER
SUPPLY
DUCT
INSULATED FLEX DUCT
(MAX LENGTH OF 4 FT)
INSULATE BACK
OF DIFFUSER
CEILING
DIFFUSER
WIRE HANGER
(TYPICAL)
ROUND TO
SQUARE ADAPTER
OPPOSED
BLADE DAMPER
CEILING
1 DIFFUSER CONNECTION DETAIL
M201 SCALE: NTS
SQUARE ELBOW
AIR FLOW
MAX.
DOUBLE L
THICKNESS
VANES L = 0.25xW
BRANCH 3" MIN.
DUCT
SUPPLY TAP
4 DUCTWORK DETAILS
M201 SCALE: NTS
M2017
GALV. STEEL OR
ALUMINUM DUCT MADE
WATERTIGHT. STIFFENERS
MAY BE INSIDE.
071942IRM2I_i10.19ZARMM
SLOPED ROOF
AT THE JOINING OF THE
PIPE AND THE COLLARED
ROOFCAP, CONNECT DUCT
INSIDE COLLAR AND SEAL
WITH FOIL BACKED TAPE.
1. PRIME COAT AND PAINT TO MATCH ROOF COLOR.
2. PROVIDE FLASHING AND COUNTER FLASHING.
3. PROVIDE BIRD SCREEN.
4. OUTSIDE AIR INTAKE SHALL BE A MINIMUM OF 10 FT.
AWAY FROM ANY EXHAUST OR PLUMBING VENT.
ROOF CAP DETAIL
M201 SCALE: NITS
ARCHITECT Of RECORD:
OPTION 1: OPTION 2: THOMAS E. MORGAN, JR.
12 GAUGE WIRE OR 1/4" 1" WIDE 22 GAUGE STEEL
ALL THREAD ROD TO STRAP WRAPPING UNDER ARCHITECT
STRUCTURAL SUPPORT DUCT DUCT AND ATTACHED TO
STRUCTURAL SUPPORT
8' MAX 1" 423FISCHERTRAIL
ELLIJAY, GEORGIA 30540
1" X 2" X 1" 22 GAUGE ANGLE
CHANNEL 4" X 2" X 2" -
HANG FLEXIBLE DUCTS WITH 1" WIDE
22 GA. STEEL STRAPS WRAPPING
UNDER DUCT EVERY 5 FT. MAX.
ALSO SUPPORT 18" FROM ANY
CONNECTION. MINIMUM 2" WIDE NO
BURN RATE/SELF EXTINGUISHING
FABRIC HANGER STRAP MAY BE
USED IN LIEU OF METAL STRAPS
O. -'1�r
'
r
"�aaus2
ON 9916
Lic.140.
2 DUCT HANGER AND SUPPORT DETAILS
M201 SCALE: NTS
LOUVER FF' '-
BIRDSCREI
AIR FLOW FOR DRYE
1 LOUVERS)
45' L
L = 0.25xW LOUVER
3" MIN.
DUCT
RETURN TAP CAULK ALL AROI
2" METAL FLANGE.
SECURE TO WALL WITH
DRYWALL SCREWS.-,
mmm
DESIGN GROUP
3450 Acworth Due West Road
Building 100, Suite 120
Kennesaw, Georgia 30144
P.770-917-9172
F.770-917-9470
www.mrpdesign.com
V
5 WALL LOUVER DETAIL SSUES/REVISIONS
SCALE: NTS once DESCRIPTION
M20108. 18 201 COLORED ELEVATIONS SUBMITTAL
041201221 REVISION I ,
MIN. 26 GAUGE
GALVANIZED STEEL DRYER
VENT IN WALL (MIN. 4")
PROVIDE STAINLESS STEEL
RADIATOR STYLE CLAMP
FOR CONNECTION OF
FLEXIBLE DRYER VENT.
MIN. 26 GAUGE
METAL BOX RECESSED
IN STUD WALL.
MIN. 18" /
8 DRYER WALL BOX DETAIL
M201 SCALE: NTS
SAVANT
Engineering, LLC
5064 Roswell Road, Suite D-301
Sandy Springs GA 30342 770319.7400
Project 20147 02020
DRAWN BY: RGV
CHK'D BY: RGV
PROJECT TITLE:
SHEET TITLE:
H.V.A.C. SCHEDULES
AND DETAILS
PROJECT NO: 19066
M201
CERTIFICATE OF AUTHORIZATION #006912