November 6, 2017
Paty Saternye,
County of Albemarle
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, VA 22902
Regarding: ARB2017-72: Hollymead Town Center Hotel (Comfort Inn &Suites)
Dear Ms. Saternye,
Thank you for your review of the final site plan for HTC Hotel. We have reviewed and revised the plan per
your most recent comments dated November 6, 2017. See below for detailed responses to each of your
comments.
1. Provide street trees along both sides of all interior roads spaced 40'on center or provide the
required information on existing trees that are being utilized to meet the minimum
requirements.
Street trees provided around development.Street trees on eastern and western sides of development to
be preserved from previous developments.
2. If existing trees are to be utilized to meet requirements,then show them as preserved, provide the
signed conservation checklist,and provide tree protection fencing throughout the grading,
landscaping and E&SC plan sheets.
Existing trees are not used to meet requirements,and conservation checklist provided.
3. Relocate proposed utilities to reduce their impact on the landscaping areas.
Utilities have been relocated where possible to improve planting areas.
4. Adjust the location of the building to increase the planting area on the north side of the building
and add shrubs and trees to further mitigate the blankness.
Building location has been adjusted to increase planting area on the north side.
5. A Certificate of Appropriateness is required prior to final site plan approval.
Acknowledged
• Regarding recommendations on the plan as it relates to the guidelines:
None.
• Regarding conditions to be satisfied prior to issuance of a grading permit:
1. If existing trees are to be utilized to meet requirements,then show them as preserved, provide
the signed conservation checklist,and provide tree protection fencing throughout the grading,
landscaping and E&SC plan sheets.
Existing trees are not used to meet requirements,and conservation checklist provided.
• Regarding the final site plan submittal:
1. Increase the quantity of stone(or other masonry material)in the building,establishing a masonry
base,extending the full length of the building,and/or adding masonry in the bays above the
base.
Noted by architect
2. Revise detailing of the western bay of the north elevation to achieve greater consistency with
the rest of the elevation.Alternatively add a tree to relieve the blankness.
Noted by architect
3. Revise the "Finish Legend" to include and differentiate between the Hardie Board and the EIFS
that are both "Sawdust" color. Ensure that the labels on the elevations of the building specify a
different label number for these two materials.
Noted by architect
4. Ensure that the dimension for the"Top of Parapet"of the entrance extends to the actual top of
parapet.
Noted by architect
5. Provide information on the VLT and VLR ratings for the window glass. Ensure that the glass
meets the required limits.
Noted by architect
6. Add the standard window glass note to the drawings with the next submission: Visible light
transmittance(VLT)shall not drop below 40%. Visible light reflectance(VLR)shall not exceed
30%.
Noted by architect
7. Revise the louver color note on the elevation drawings to specify that HVAC units will be sawdust
colored. Ensure that the color of the HVAC units in the architectural rendering are shown as
sawdust.
Noted by architect
8. Show the location of all mechanical equipment and accessory structures, including rooftop
equipment and equipment associated with elevators,on the plans.Show how visibility of the
equipment and accessory structures will be eliminated from the EC.
Acknowledged by architect. Note provided on cover sheet
9. Locate loading, service and storage areas on the plans.Show how visibility of these features will
be eliminated.
Acknowledged
10.Add the standard mechanical equipment note to both the site and architectural plans with the next
submission.
Mechanical equipment note on cover sheet
1 1.Provide information on any lighting for the porte cochere and its related elements. Limit
illumination levels under the porte cochere, and its related elements,to 20 fc maximum. Include all
building— and ground- mounted lights in the lighting plan.
Lighting under porte cochere under 20 fc.
12.Provide "Lamp" information for the LSI Industries light fixture light in the lighting schedule.
Lighting Plan and fixtures have been updated.
13.Provide an offsite planting easement to meet the EC landscape requirements.
Note provided on Landscape Plan
14.Provide a street tree calculation, specifying linear feet of street and the number of trees required
in order to provide one tree every 40' on both sides of the streets.
Street trees at 40' O.C. along both sides of the street when possible.
9 pin oaks 40' O.C.from Bojangles planting on eastern side of development to be preserved.
Red maple and river birch spacing roughly 15'-20'along western edge of development by Target to be
preserved.
15.Revise the proposed landscape schedule, landscape required and landscape provided to meet all
requirements and eliminate errors.
Landscape required and schedule have been updated
16.Limit the number of proposed plants for any one species to 25%of the total proposed for that
plant type (tree, shrub).
No species exceeds 25% of planting
17.Add shrubs on the east side of the building to further mitigate blankness.
Shrubs have been added to mitigate blankness
18.Limit the number of proposed plants for any one species to 25%of the total proposed for that
plant type (tree, shrub).
See comment 16.
19.Ensure that any loading,service,or refuse areas and ground level mechanical equipment is
screened and integrated into the site with appropriate landscaping.
All landscape screening is appropriately located
20.Note that a separate sign application will be required.
Acknowledged
21.Indicate why LED lamp is needed; it is preferred that all fixtures be consistent in appearance and
lamp type.
LED's generally have lower input requirements and long life expectancy than traditional lamp types.
If you have any questions or concerns about these revisions please feel free to call me at(434) 227-5140 or
email Peter Russell at peter@shimp-engineering.com and we can discuss any questions that you may have in
further detail.
Best Regards,
Peter Russell
Shimp Engineering, P.C.
Page 4 of 4
CONCEPTUAL LAYOUT FOR
hollymead Towncenter North Connor Drive
568
ProF2ertie5 566 Stop Sign Building treet access
CURRENT ZONING PDMC 564 \ from Plaza access
November 27, 20 I 7 562 568 from street
560 18 oI \ al L---- 11111114 J0.
JSiStoFE57)tie Into existig grades 63 x Nif 4500 SF (100'x45')
Retail Site Plaza 562
el'
PARKING SUMMARY 180� 1,1111110 /560
IRamp `° '
IIIW
LOT C \Stop Sign aZo 2410 1.92 acres 61 Stair /p_ 00,0(� ` 558
4.5 PARKING SPACES PER 1 ,000 SF �\ 0umpster 66 Parking Spaces x Ps o s,��F
RETAIL SPACE PER HTC ZMA 8r / \ °�,.os- SscJ ` 556
—4,500 SF RETAIL = 20.25 SPCAES 551 „✓'� 18.0' N .
` \ `` `
I d lo% ..
—4,500 SF RESTAURANT = 20.25 SPACES - ' ` _ N ` 554
REQUIRED= 42 SPACESRaised `
PROVIDED= 66 SPACES 55E ,----1— -7 MT td
Outdoor 552
Seating 1
55 1 4�0, ,I /Stop Sign
HTC HOTEL — COMFORT INN I / 550
1 ;. t
11
1 SPACE PER HOTEL ROOM I st . Sign osswalk
86 X 1 SPACE/ROOM = 86 59 . 2 0 N41'1/
REQUIRED= 86 (INC. 4 HC) ( ♦ DN�
PROVIDED= 81 (INC. 4 HC) ft
HTC BOJANGLES 55 I
L b
13 SPACES PER 1 ,000 RESTAURANT GFA ®® o ®® 41'1758M
BOJANGLES = 3,516 / 1 ,000 X 13 = 46 I ®® ®®
. . "
REQUIRED= 46 SPACES o1 11 ^
PROVIDED= 46 SPACES I 11157c 0 I.J 69. I- _
<� 1111110 U
TOTAL PROVIDED= 193 SPACES 1 —
1 ,
t 1 1 , 'I 1 1 1 1 1 1 1 1.
( I--� I I I 1 1 1- 1 :1 1 4 - I
-I-1 1 - 5 1 I 1 - 1 I 1 1 1 1 1- Existing
I r-1 1 I I 1 1 4 1 1 , 1
-I 1 , 1 c ,> I 1 Retention
L- r J _J Y- 1 1 1
I ---J I HTC HOTEL — I I
_- Pond
----,-----T- COMFORT INN 1 �- --T---i-
4 t { EL
I ___�_- 1 :: Y ., 1: 1 1.. 1 1 1: 1. I
1. t 1 1 1 1 1 1 1: 1 w
I I I I - 1 1 1 :1 1. r 'm
III I 1 1 1 - I I N
1 I /+
` ® CJ �J'�.d LL 2
®®
di :-1, ®® ,J I SHIMPENGINE RING, P.C.
®® O / j ENGINEERING-LANDPLANNING-PROJECT MANAGEMENT
j
201 n ® ® - PHONE (434) 227-5140
CHARLOEMAINTTESVST,ILLE,STE VAM
22902 JUS11N49SHIMP-ENGINEERING.COM
c N41•17 56'E 252 91 30 0 50.
60
c
:.i \
1.
/ L - - _ _
Scale: 1 "=30'
sHimp , PROJ Mr\lN
CIVILECT ENGINEERINGAGEMENT
LAND PLANNING
ENGINEERING
November 6, 2017
Bobby Jocz,
County of Albemarle
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, VA 22902
Regarding: SDP 201700046 HTC Hotel—Comfort Inn— Initial Site Plan
Dear Mr.Jocz,
Thank you for your review of the final site plan for HTC Hotel. We have reviewed and revised the plan per
your most recent comments dated November 6, 2017. See below for detailed responses to each of your
comments.
1. WPO VSMP plan must be submitted and approved prior to final site plan approval
Acknowledged
2. Provide/display parcel and ownership information for surrounding parcels
Provided on sheet C2
3. Provide location/type of traffic control signs/markings
Provided
4. Provide current/proposed travelway or access easements
Provided
If you have any questions or concerns about these revisions please feel free to call me at (434) 227-5140 ext. 5
or email Peter Russell at peter@shimp-engineering.com and we can discuss any questions that you may have in
further detail.
Best Regards,
Peter Russell
Shimp Engineering, P.C.
Page 1 of 1
sHimpPROJECT MANAGEMENT
CIVIL ENGINEERING
LAND PLANNING
ENGINEERING
November 6, 2017
Alexander Morrison,
Albemarle County Service Authority
168 Spotnap Road
Charlottesville, VA 22911
Regarding: SDP 201700046 HTC Hotel—Comfort Inn—Initial Site Plan
Dear Mr. Morrison,
Thank you for your review of the final site plan for HTC Hotel. We have reviewed and revised the plan per ,
your most recent comments dated November 6, 2017. See below for detailed responses to each of your
comments.
1. I have reviewed the initial site plan and am recommending approval with the following conditions:
• A water/sewer construction plan review submittal is required at the final site plan stage Submit 3 copies
of the plan along with water and sewer data sheets to the ACSA, Attn: Alexander J Morrison, PE_to
start the review
Acknowledged. Water and sewer data sheets attached included with this submittal to ACSA.
• A sewer capacity agreement will be required prior to final site plan approval
Acknowledged
I also want to note that based on the number of rooms the connection fees will be approximately $582,000. I
wanted to pass this information along for project budgeting purposes
Acknowledged
If you have any questions or concerns about these revisions please feel free to call me at (434) 227-5140 ext. 5
or email Peter Russell at peter@shimp-engineering.com and we can discuss any questions that you may have in
further detail.
Best Regards,
Peter Russell
Shimp Engineering, P.C.
Page 1 of 1
WATER DATA SHEET
Date 11/27/2017
(1) Project Name Hollymead Town Center Hotel
(2) Project Location Timberwood Blvd.Charlottesville,VA. Behind the Target store
(3) Consultants Shimp Engineering, P.C.
(4) Sources
(5) Design Population
(6) Hydraulic Capacity
(7) Pipe Material Ductile Iron
(8) Pipe Diameter (Inches) Length (Feet)
4" 55
6" 271
8" 346
10"
12"
(9) Fire Hydrant Assemblies 1 (Number)
(10) Valves: (A) Gate 3 (Number)
(B) Air Relief (Number)
(11) Fittings: (A) Cross (Number)
(B) Tee 2 (Number)
(C) 90° Ell 3 (Number)
(D) 45° Bend (Number)
(E) 221/22 Bend 1 (Number)
(F) Reducer (Number)
(G) Blow-off
Assemblies (Number)
(12) Minimum pressure at critical water meter (20 psi required)
Authority Provide:
Booster Station
Storage Reservoir
A-1
SEWER DATA SHEET
Date 11/27/2017
(1) Project Name Hollymead Town Center Hotel
(2) Project Location Timberwood Blvd Charlottsville,VA. Behind the Target store.
(3) Consultants Shimp Engineering,P.C.
(4) Waste Treatment Facility
(5) Design Population (Number)
(6) Connections 2 (Number)
(7) Industrial Waste
(8) Pipe Material SDR-26
(9) Pipe Diameter (Inches) Length (Feet)
6" 57
8" 334
10"
12"
15"
18"
21"
24"
TOTAL FEET 391
(10) Manholes: (A) Standard 4 (Number)
(B) Drop (Number)
(11) (A) Siphons & Pump Stations (Number)
(B) Force Main (Size-Length) (Feet)
Authority Provide:
Drainage Basin
Sub Drainage Basin
A-2
S ri .1?,
PROJ rnnI
CIVILECT EHNGINEERINGAGEMENT
`� LAND PLANNING
ENGINEERINGa
November 6, 2017
Adam Moore,
Virginia Department of Transportation
1601 Orange Road
Culpeper,VA 22701
Regarding: SDP 201700046 HTC Hotel—Comfort Inn—Initial Site Plan
Dear Mr. Moore,
Thank you for your review of the final site plan for HTC Hotel. We have reviewed and revised the plan per
your most recent comments dated November 6, 2017. See below for detailed responses to each of your
comments.
1. Provide entrance geometry. Note that the minimum radius for a commercial entrance without a separate truck
feet
Provided
2. Provide a one-way sign in the median on Timberwood Dvd across from the hotel entrance.
Provided
3. The final site plan must show conformance with the VDOT Road Design Manual Appendices B(1)and F,as wt
applicable standards, regulations or other requirements
Acknowledged
If you have any questions or concerns about these revisions please feel free to call me at (434) 227-5140 ext. 3
or email Justin Shimp at justin@shimp-engineering.com and we can discuss any questions that you may have in
further detail.
Best Regards,
Peter Russell
Shimp Engineering, P.C.
Page 1 of 1
PROTECT MANAGEMENT
CIVIL ENGINEERING
LAND PLANNING
ENGINEERINGa
November 6, 2017
Robbie Gilmer,
County of Albemarle
Department of Community Development
401 McIntire Road, North Wing
Charlottesville,VA 22902
Regarding: SDP 201700046 HTC Hotel—Comfort Inn—Initial Site Plan
Dear Mr. Gilmer,
Thank you for your review of the final site plan for HTC Hotel. We have reviewed and revised the plan per
your most recent comments dated November 6, 2017.See below for detailed responses to each of your
comments.
1. Please show the FDC location on the site plan.
Provided
If you have any questions or concerns about these revisions please feel free to call me at(434) 227-5140 ext. 5
or email Peter Russell at peter(Wshimp-engineering.com and we can discuss any questions that you may have in
further detail.
Best Regards,
Peter Russell
Shimp Engineering, P.C.
Page 1 of 1
PROJECT MANAGEMENT
sHimpl CIVIL ENGINEERING
LAND PLANNING
ENGI N EERI NGa
November 6, 2017
Victoria Fort,
County of Albemarle
Department of Community Development
401 McIntire Road, North Wing
Charlottesville,VA 22902
Regarding: SDP 201700046 HTC Hotel—Comfort Inn—Initial Site Plan
Dear Ms. Fort,
Thank you for your review of the final site plan for HTC Hotel. We have reviewed and revised the plan per
your most recent comments dated November 6, 2017.See below for detailed responses to each of your
comments.
1. RWSA will require a capacity certification prior to final site plan approval
Acknowledged. Will submit when timeline permits and if certification is required from water
usage/fixture count.
If you have any questions or concerns about these revisions please feel free to call me at(434) 227-5140 ext. 5
or email Peter Russell at peter@shimp-engineering.com and we can discuss any questions that you may have in
further detail.
Best Regards,
Peter Russell
Shimp Engineering, P.C.