HomeMy WebLinkAboutSDP202100056 Correspondence 2022-05-16/A® SEH Building a Better World for All of Us® May 16, 2022 Andy Reitelbach Senior Planner Planning Services Division Albemarle County 401 McIntire Road Charlottesville, VA 22902 Dear Mr. Reitelbach: RE: SDP2021-00056 Airport Road Pump Station Project Final Site Plan Review Response Letter Rivanna Water & Sewer Authority SEH No. RIVAN 153082 14.00 We received your August 12, 2021 letter with review comments on our final site plan submittal SDP2021- 00056 for the RWSA's Airport Road Pump Station. On behalf of the Rivanna Water & Sewer Authority of Albemarle County, Virginia, we have prepared this letter in response to your comments. Our letter is formatted to list your inquiry/comment in regular or bold font followed by our response in italics font. Enclosed following this letter you will find the following documents: Enclosure A: Updated Final Site Plan Drawings Signed 5/12/2022 Enclosure B: Parking Space Review Email Enclosure C: ARB Certificate of Appropriateness 1. [32.5.2(a)] Identify on the cover sheet that this plan is a "final site plan." Also, provide the application number on the cover sheet of the plan — SDP2021-00056. Response: The cover sheet has been updated to reflect that this is a "final site plan". The application number has been added to the cover sheet 2. [32.5.2(a)] The signature line for the Health Department can be removed from the approval box on the cover sheet. This site is within the jurisdictional area of the Albemarle County Service Authority (ACSA). Response: Virginia Department of Health has been removed from the approval box on the coversheet. 3. [32.5.2(a)] On the cover sheet, provide an address for the property owner. Response: The address for the property owner has been added to the cover sheet. 4. [32.5.2(b)] Clarify why the proposed impervious area identified on the cover sheet is less than the sum of the building footprint, generator enclosure, and paved parking/vehicular circulation Engineers I Architects I Planners I Scientists Short Elliott Hendrickson Inc., 3535 Vadnais Center Drive, St. Paul, MN 55110-5196 SEH is 100 % employee -owned I sehinc.com 1 651.490.2000 1 800.325.2055 1 888.908.8166 fax SDP2021-00056 Airport Road Pump Station — Final Site Plan Review Comments Letter Page 2 area. Response: This is a typo and has been updated on the cover sheet. 5. [32.5.2(c)] As it appears that the ground storage tanks are to be built at a later time, either remove them from this plan, or provide phase lines/information on the plan identifying the limits of the future phase(s). Response: The dashed lines depicting the anticipated location of the future tanks have been removed from the plan sheets and replaced with the following note "SPACE FOR ANTICIPATED FUTURE GROUND STORAGE TANKS". 6. [32.5.2(i)] Provide the state route number for Berkmar Drive on the site plan layout sheet (sheet C09). Response: The state route number for Berkmar Drive has been added to Sheet C09. [32.5.20); 32.5.2(k)] An easement plat will be required for all stormwater management facility, drainage, and access easements. This easement plat will need to be reviewed, approved, and recorded prior to the approval of the final site plan. Response: The stormwater management facility easement has been recorded. The easement is shown on Sheets C09 and C15 with the deed book and page numbers listed. 8. [32.5.2(n); 4.17] Outdoor lighting. a. The light loss factor (LLF) on the photometric plan (sheet DE1) must be 1.00. Revise the luminaire schedule with an LLF of 1.00. Response: Sheet DE1 has been revised and updated with a light loss factor of 1.00. b. Revise the photometric plan calculations to reflect an LLF of 1.00. Response: Sheet DE1 has been revised and updated with a light loss factor of 1.00. 9. [32.5.2(p); 32.7.9] Landscape plan. a. The Conservation Plan checklist on the landscaping plan sheet will need to be completed, signed, and dated by the property owner prior to approval of the final site plan. Response: The landscaping plan has been signed and dated by the property owner. b. It is suggested that the label for the proposed undisturbed buffer along the southwestern property line be revised to separate the 20' undisturbed buffer at the rear of the property from a "variable width" undisturbed buffer closer to the proposed Berkmar Drive right-of-way, to accommodate the proposed clearing and replanting that will occur in that area. Response: The "20.0' UNDISTURBED LANDSCAPE BUFFER" was kept on the plans. This gives the onsite representative of the Owner and Engineer more control in minimizing tree removal. c. In the landscaping schedule, provide the number of Virginia Pines that are proposed to be planted. In addition, provide the caliper of the proposed trees, and the expected height of the trees at ten years maturity after planting. Response: The landscaping schedule has been updated to reflect this information. SDP2021-00056 Airport Road Pump Station — Final Site Plan Review Comments Letter Page 3 The original comments from the review and action letter for SDP2020-00060 are in gray font. Follow- up comments from the review of the final site plan, SDP2021-0056, are in bolded black font. Please address these follow-up comments as well. 1. [32.5.2(b)] Include the generator and its enclosures in the list of proposed uses on the cover sheet of the plan Also, provide the square footage and height of the generator enclosure on the cover sheet and on the layout plan. Clarify the structure that is enclosing the generator and portable pump. Are they enclosed within the building, or is a fence surrounding these elements? Response: The generator has been added to a list of uses on the cover sheet. The generator is covered by an extension of the pump station roof, so the height is the same as the building. There are no walls or fence surrounding the generator, it is open on all sides. A fence will be provided around the perimeter of the site. 2. [32.5.2(b); 4.12.7] As the proposed use is an unscheduled use in regard to the Parking requirements, Section 4.12, submit a letter to the Zoning Administrator with a request for the proposed number of parking spaces. This request must include justification for why the proposed number of parking spaces is expected to provide sufficient parking capacity for the proposed use. The number of parking spaces required for this use will ultimately be determined by the Zoning Administrator. This comment has not been addressed. Submit a letter addressed to the Zoning Administrator with justification for the proposed number of parking spaces to be provided. The ultimate determination on the required number of parking spaces will be made by the Zoning Administrator. Response: A letter requesting review of the parking spaces was submitted to the County on September 21, 2021. No official response has been received at this time. An email from Mr. Reitelbach stating the number of proposed parking spaces is sufficient is enclosed following this letter. 3. [32.5.20); 32.5.2(1)] Identify all existing sewer and drainage facilities, as well as all existing and proposed utilities. a. An approved easement plat will be needed for the proposed utilities and stormwater facilities. Once recorded, the deed book and page number(s) for the new easements will need to be noted on the plan before final approval can be granted. This comment must still be addressed. Response: The stormwater management facility easement has been recorded. The easement is shown on Sheets C09 and C15 with the deed book and page numbers listed. 4. [32.5.2(k)] Proposed sewer and drainage facilities. Depict these facilities and their dimensions. If necessary, an approved and recorded easement plat will be required prior to approval of a final site plan and/or final subdivision plat. (This comment and the comment above are standard comments for all site plans, and staff recognizes that they may not apply to this project in the same way as most other projects since this site plan is for an RWSA facility.) This comment must still be addressed. Response: There is no sewer associated with the project. Stormwater facilities have been updated as per conversations with J. Anderson. SDP2021-00056 Airport Road Pump Station — Final Site Plan Review Comments Letter Page 4 5. [4.1] Provide a note on the cover sheet identifying whether this property is located within the ACSA jurisdictional area. This comment has not been addressed. Response: This comment has been addressed. Comments from Other Reviewing Departments. Divisions. and Aaencies Albemarle County Architectural Review Board (ARB) - Khris Taggart, ktaggart(5_albemarle.org Note: The Certificate of Appropriateness from the Albemarle County Architectural Review Board is enclosed following this letter. No details have been provided on the appearance of the ground storage tanks. If the ground storage tanks are proposed with this submittal, provide details on the architectural designs of the ground storage tanks, including a color sample. If details on the appearance of the ground storage tanks are unavailable at this stage, revise the site plan to remove all references to the ground storage tanks. Response: As per email correspondence with K. Taggart, the dashed lines depicting the anticipated locations of future tanks have been removed from the plan sheets and replaced with the following note "SPACE FOR ANTICIPATED FUTURE GROUND STORAGE TANKS'. See comment #1 regarding notes/references to ground storage tanks. If details on the appearance of the ground storage tanks are unavailable at this stage, revise the site plan to remove all references to the ground storagetanks. Response: As per email correspondence with K. Taggart, the dashed lines depicting the anticipated locations of future tanks have been removed from the plan sheets and replaced with the following note "SPACE FOR ANTICIPATED FUTURE GROUND STORAGE TANKS'. 3. The standard mechanical equipment note is not included in the site plan. Revise the plan to include the standard mechanical equipment note: " Visibility of all mechanical equipment from the Entrance Corridor shall be eliminated." Response: This note has been added to Sheet A200 The LLF of the proposed fixtures is less than 1.0. Revise the photometric plan using an LLF of 1.0 for all fixtures. Response: Sheet DE1 has been revised and updated with a light loss factor of 1.00. No details on the view of the ground storage tanks from Airport Rd. have been provided. If the ground storage tanks are to be proposed and reviewed with this submittal, provide site sections that show the view of the site, including the storage tanks from the Airport Rd. frontage. Response: As per email correspondence with K. Taggart, the dashed lines depicting the anticipated locations of future tanks have been removed from the plan sheets and replaced with the following note "SPACE FOR ANTICIPATED FUTURE GROUND STORAGE TANKS.. Albemarle County Engineering Services (Engineer) - John Anderson, landerson2(c@albemarle.org Requested changes; see the attached checklist and comment memo. Response: Responses to the comment memo are below: 1. Recommend revise plan title to include ref. to SDP202100056. Response: This has been added to the title sheet. SDP2021-00056 Airport Road Pump Station — Final Site Plan Review Comments Letter Page 5 2. Revise T01 to include reference to related plan, WP0202100035. Response: This reference has been added. 3. Revise sheet list, T01, to remove ESC-SWM-PPP (WPO plan -related) sheets from the final site plan. Response: The sheet list and the sheets included in the resubmittal have been updated to address this comment. 4. Revise T01 topography note to confirm existing topography has been at least visually verified within the last 12 months [See Final Site Plan checklist for plan reviewers, p. 1, Existing conditions plan view information; 2nd item —ref. attached]. Response: This note has been added. 5. Coordinate final site plan design with VDOT. VDOT has near -term plans to extend Berkmar Drive Ext. to Airport Drive. Ensure that the final site plan proposed grade (final contours) are consistent with roadway extension. At present, they are not. Proposed grade suggests relatively abrupt rise into the site, with gradual fall, west to east, across the site. Ref. sheet C12, Grading Plan. If grade is to be flatter, consistent with future Berkmar Drive Ext. roadway, then grades must be lowered across the site. Retaining walls may be required between proposed development and parcel to immediate north in order to eliminate 4'-5' grade rise at entrance to RWSA pump station. Retaining walls are a common remedy for addressing grade issues. Retaining wall ht. > 4-ft. requires a sealed geotechnical retaining wall design. Please coordinate directly with VDOT on Berkmar Drive Ext. (future) design, and accommodate reasonably -predictable VDOT Berkmar Drive Ext. future design needs. Note: Virtually all sheets of the FSP show and label Anticipated VDOT Grading Easement (Typ.), yet the FSP proposes grades that conflict with Berkmar Drive Ext. future grading. Please revise FSP consistent with anticipated VDOT Grading Easement. Response: We are aware of the future extension of Berkmar Drive. The Owner and Engineer have coordinated with VDOT to the best extent possible. The plans for the permanent site access drive have been coordinated with preliminary drawings in an effort to minimize future conflicts. Please remove sheet C09 bioretention basin specific design elements (footprint with label is fine), as well as sheets C10, C11, C13, C16, DC03 from the site plan since ESC measures and SWM facilities are not approved with a site plan, but with a WPO plan. WPO plan review is pending (WP0202100035). Response: These sheets have been removed from the set and the Sheet List on T01 has been updated. C12: Provide final disposition of runoff along south side of site access; specifically: provide channel lining design and velocity/capacity calculations for runoff in ditch -line between contours 623 and 615. Proposed grade routes runoff to a bend in site access, at which point runoff appears to sheet across site access without routing to any SWM capture or conveyance system. Include a new Drainage Plan sheet that shows storm runoff collection and conveyance. Response: Stormwater facilities have been updated as per conversations with J. Anderson and are shown in the resubmittal of the WPO plan. 8. With WPO Plan, account specifically for increased sheet flow from impervious parking and site access (reasonably anticipated to occur) along south side of development, given close proximity SDP2021-00056 Airport Road Pump Station — Final Site Plan Review Comments Letter Page 6 to property line. Response: Stormwater facilities have been updated as per conversations with J. Anderson and are shown in the resubmittal of the WPO plan. C15: Engineering defers to Planning Division as to whether proposed grading within 20.0' undisturbed landscape buffer qualifies as undisturbed. C08, Existing Conditions, accurately describes existing condition as'existing wooded area mix of deciduous and evergreen trees.' The site is 100% mature canopy mix. If mature mix of deciduous and evergreen trees is removed, replacements will not attain maturity for decades. Engineering defers to Planning, but if site grade is lowered, generally, it may be not only feasible but relatively easy to preserve 20.0' undisturbed landscape buffers along parcel boundaries, for the entire development. Engineering encourages design to preserve an undisturbed landscape buffer to the maximum extent practical. Retaining walls may aid in addressing this and other review comments. Response: This was not noted in the comments from the Planning Division. The minor grading and replanting in the 20-foot buffer was designed in an effort to maintain as much of the mature canopy as possible and is believed to be preferable to planting vegetative screening through a double staggered row of evergreen trees planted 15-feet on center, as described in 32.7.9.7.e. Albemarle County Information Services (E911) - Elise Kiewra, ekiewra(d?albemarle.org No objections at this time. Response — Noted. Albemarle County Building Inspections - Betty Slough, bsloughno.albemarle.org Add the following note to the general notes page: Buildings or structures built before January 1, 1985 must have an asbestos survey performed in order to apply for a demolition permit. Asbestos removal permits are required if positive for such from Albemarle County and VDOLI. Contact VDOLI for their additional requirements and permits for demolition projects at 540-562-3580 x1 31. Response: This is green field construction and there is no structure demolition as a part of this project. There is only miscellaneous trash/debris removal. To avoid confusion with the Contractor, at this time, the note has not been added. Albemarle County Transportation Planning - Daniel Butch, dbutch(c@albemarle.org No objections at this time. Response — Noted. Albemarle County Department of Fire -Rescue - Howard Lagomarsino, hlagomarsino(&albemarle.org No objections at this time. Response — Noted. Albemarle County Service Authority (ACSA) - Richard Nelson, rnelson(c@serviceauthority.org No objections at this time. Response — Noted. Virginia Department of Transportation (VDOT) -Adam Moore, Adam.Moore(r_vdot.virginia.gov No objections at this time; see the attached memo. Response: The contractor will apply for and hold the land use permit for this work. SDP2021-00056 Airport Road Pump Station — Final Site Plan Review Comments Letter Page 7 Closure We would like to thank you for your comments and trust that our responses and attachments are sufficient to address your concerns. If you wish to discuss the project or have any additional questions, please do not hesitate to contact me by phone at 507.440.7485 or bweiss@sehinc.com. Sincerely, Brad Weiss, P.E. Project Engineer Enclosures: Enclosure A: Updated Final Site Plan Drawings Signed 5/12/2022 Enclosure B: Parking Space Review Email Enclosure C: ARB Certificate of Appropriateness ENCLOSURE A FINAL SITE PLAN DRAWINGS RIVANNA WATER &SEWER AUTHORITY SITE DATA OWNER: PROPERTYSIZE: PROPERTYADDRESS: PROPERTY INFO: PARCELID: ZONING: COUNTY: STATE: MAGISTERIAL DISTRICT: OVERLAY DISTRICTS: DISTRICT WATERSHED: AIRPORT ROAD PUMP STATION ALBEMARLE COUNTY, VIRGINIA 695 MOORES CREEK LANE CHARLOTIESYIUE,VA22902 LGUACRES N/A TAX MAP 32MUA2 DB 4912 PG 328 03200TOTIOD1A2 RURALARFAS ALBEMARLE VIRGINIA RIO DISTRICT ENTRANCE CORRIDOR -AIRPORT IMPACT POWELLCREEK-THIS SITE 15 NOT LOCATED WUHINA WATER SUPPLY WATERSHED IURISDICNONALAREA ALBEMARLE COUNTY SERVICE AUTHORITY ENGINEER: SHORTELUOTHENDRICKSON 3535 VADNAIS CENTER DRIVE ST. PAUL, MN 55110 SURVEYOR: SHORTELUOTHENDRICKSON 3535 VADNAIS CENTER DRIVE ST. PAUL, MN 55110 DATUM: HORIZ: NAD-83 VERT: NAD-88 PROPOSED USES 1) POTABLE WATER PUMP STATION. 2) COVERED GENERATOR FOR EMERGENCY PUMP SEX MINIMUM SETBACK REQUIREMENTS: 25' FRONTSETBACK 25' SIDE SETBACK 35' PEAR SETBACK HEIGHT OF PROPOSED STRUCTURES: PROPOSED PUMP STATION AND GENERATOR ENCLOSURE: 23'-W PROPOSED BUILDING FOOTPRINT: PROPOSED GENERATOR ENCLOSURE: TOTAL PROPOSED IMPERVIOUS AREA: TOTAL SITE FOOTPRINT: OVERALL PROJECT LIMITS OF DISTURBANCE: PAVED PARKING/VEHICU AR CIRCULATION: EXISTING TREE CANOPY: EXISTINGTREETYPE: PROPOSED TREE CANOPY: 1209 SF (0.028 AQ 70 SF (0.01] AQ 0.18 AC 0,214 SF(1.60 AQ 1.20 AC 0.12 4 1.54 AC (%%) MIX OF DECIDUOUS & EVERGREEN 0.51 AC (32%) EXISFING TOPOGRAPHY PER SEE! SURVEY DONE NOVEMBER 2019 EXISFING TOPOGRAPHY HAS BEEN VISUALLY VERIFIED WITHIN THE U\ST 12 MONTHS. FINAL SITE PLAN SDP 2021 =00056 REFERENCE PLAN: WPO 202100035 y4� Po a`"Yiyps F2' VQ P i [IurleneAuMft tr l fi ai�wn A 5 C a r PROJECT LOCATION C(ENO OF BERKMA* DR) N wvanna ,�w� d � Ta y � f Hol"a4 APPROVALS DATE DEPARTMENT OF COMMUNITY DEVELOPMENT PLANNING/ZONING ENGINEER INSPECTIONS ARB DEPARTMENT OF FIRE RESCUE ALBEMARLE COUNTY SERVICE AUTHORITY VIRGINIA DEPARTMENT OF TRANSPORTATION SITE PLAN SHEET LIST SHEET NUMBER SHEET TITLE T01 COVER COB EXISTING CONDITIONS AND DEMOLITION PLAN C09 SITE PLAN C10 EROSION CONTROL PLAN C11 POLLUTION PREVENTION PLAN C12 PUMP BUILDING AREA GRADING PLAN C13 BASIN AREA GRADING PLAN C14 UTILITY PLAN C15 LANDSCAPE PLAN C16 RIVANNA WSA GENERAL NOTES DC01 PUMP STATION SPECIFIC DETAILS DCO2 WATER MAIN DETAILS DC03 EROSION CONTROL DETAILS DC04 FENCE DETAILS DE1 PUMP STATION- SITE PHOTOMETRICS DE2 PUMP STATION - SITE FIXTURE CUT SHEETS X�EALTH Op G.,'L /J-7 �- -OIONAL Env 8 DATA PROFOSEDZONING: RURALARENSDISTRICT HAL RIO DISTRICT PROPOSED USE: PUBLIC WATER FACILRY ED: POWELL CREEK DISTRICTS: ENTRANCE CORRHOR-AIRPORT IMPACT DISTRICT SQUARE FOOTAGE: PROPOSED WATER PUMP STATION -1,2MBE COVERED GENERATOR PAD -709$F 250' MINIMUM FRONTAGE ALONG EXISTING PUBDC ROAD 150' MINIMUM FRONTAGE ALONG INTERNAL PUBDC ROAD OR PRIVATE ROAD 75' FRONT SETBACK 25'$IDESETBACK 35' REAR SETBACK TRACK$HONM IS 76 FROM EXISTING PROPERTY DNE EXISTING BERKMAR DR RIGHT-OF-WAY. PROPOSED AST 75 FROM THE ANTICIPATED VOOT RIGHT-OF-WAY BERKMAR DR. j � IIIIII IIIIj�II // I 1 1 1 1 111111111 I / I II IIII IIIII II III / I I I I IIIIIIIIIIIII i \ IIIIIIII IIIII III / I I I III III11111111 / \\ I IIIIIIIIII II. / \ I I I I I 111 1 11 1 1 ANTICIPATEDVDOT 1 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 RIGHT-OF-WAY T' '\ \ \ 1 IIIIIIIIII I I ' 1T\ o!I j111111 Il IIII11111111I i 1$m ge�lllllll llljl 111 j IIIm mNllllllllll II / Illl�m8amlll It Ivmg•I1111 II / / II III ��II��m�r 111111111 / / / III I III IIim�irlll / / II IIIIIIIIII IRWnmlOml m ti and V II IIIIIII IIIIII Iq�I IIIII IIIII IIIIIIIII 0 I II1111111111111111 \/ / -- 111j1 j 111111111111111111 \ ,_ \ \ I IIIIIIIIIIIIIIIIII \ \ IIIj111111111111111 1 \ IIIII II IIIII I I I I II1 I \\ I11 111III 1I 11 1 I j1111111111111II 1 I I \ /l/ /////IIIIIIIII I I \i 324 r l I \\\ MICROAIRE HOLDING \ COMPANY LLC \ (D.B. 5240,PO. 1]0) I \ /ZONING: UGHTINDUSTRVI \\�'�/ I HYDRANT TOP NUT \\ \,EL=616.83 I1�11j 11 II\�\� IIII\: 1111 III IIIIIIII 1\ \ \ III \\ \\\ I I I I NOTES: CONTRACTOR$HALL REMOVE ALL TRASH AND DEBRIS FOUND ON SITE AS PART OF NgRK. I I ALL TRASH AND DEBRIS SHALL BE PROPERLY DISPOSED OF IN ACCORDANCE WTH STATE, / \ \ \ \ 1 I COUNTY AND LOCAL REGULATIONS. 3241A3 I I I DAVID P. TURNER & THE I I I I 11 MARKET PLACE OF VIRGINIA LC I I I I I I I 1 \ \\ \\ \ \\ \ 1 (D.B. 4151, PG. 310) I I 1 I 1 ZONING: RURALAREAS I 1 I 0 m 10 kN / \ _ I -I- \ \ I -�- LEASE AREA CROWN COMMUNICATION INC \ 1 / / (D.B. 4151, PG. 310 \ } = 1 1 \ ZONING: RURAL AREAS \ REMOVE EXISTING I TRASH/DEBRIS I II I CONTROL POINT V A V 1 1 NAIL 1 A \V A 1V A IV A N3935942.0420 �/ / E 11500310.4600 41 g \ \ \ \ ANTICIPATED VOOT GRADING / / / / / I \\ / / 1 ,i EL=608,53� 4 V I A A EASEMENT (TYP) / / x 1 I / j I A AV II STORAGE MANAGEMENT I LLC 1 1 YI l I Q/I 1 / �1 11 A (D.B. 1921, PG. 423) 'ZONING: HIGHWAY COMMERCIAL vI 1 I AV A / EXISTING I I / l Ij 1 \ 1 A A l I I I l I 1 I I v A I CELL TOWER I. 1 / / I 1 1 CONTROL POINT CONTROL POINT m I / / 1 I j 1 1 I NAIL NAIL / ro \ I N 39358]T]030 I N 3936050]T4D / I \ u m I I I I E 11500340.2300 1 E 11500044.150D \ 32J1A2 I I 1 I EL-599.30 1 EL=625.58/ \ \\\\ /' 1 / / j RIVANNAWATER ANDSEWER I I I I I I I I I AUTHORITY I \ CONTROL POINT // / / I I (D.B. 4912, PG. 328) m 1 I I I NAIL r _ I/ / I CONTROL POINT 1 I I I \\ / _J_____ __f I ZONING: RURALEAS 1 1 I I m IN 3935996 9300 / / / / / NAIL I 1 I I 1 E 11500080.2200 jl T— / j/ l I l 1 11 1 1 j l I N 3935880.3250 1 I I \\ EL=626.20 �I 1 I / / I I I I 1 m I EL-605.11 1 1 1 I I I I E 11500294.3600 / / / I I I I 1 I 1 \ /- / I/ I / / /CONTROL POINT I / / / I I I I g 1 / I / NAIL / // / N ____/ �.O / E11500220.5100613.14 I 1 1 I � 1 j / CLEAR GRUBBING LIMITS (TYP)�A APPROX. AREA= 48,000 SF EXISTING WOODED AREA / I MIX OF DECIDUOUS& / I _ Q\3 EVERGREEN TREES / 1 1 / \ \\ II I 1 I 1 \ \ I I 1 1 1 1 I CONTROL POINT / NAIL EL=621.31 O I / / / / /' / jI ADDITIONAL GRDBBIFO REQUDIN _ / / / / / \ I FOR GRADING � / / / / / /� / // ADDITIONAL GRUBBING REQUIRED 111I I I l I I / / / / m I F REOLIATE PER LANDSCAPE PLAN _ / / / / / / / / / FOR GRADING O _ / / // / 32J1R / / REFOLIATE PER LANDSCAPE PLAN IIII I I I I /TRUST; / / 1 \ / r / / I I I 1 I� 1 I 1 32J1RPOST // / CHAR ESFFICE"HUR &SHIR EV -�/ i / l I /l// /i�i'ii �// I / / / /� I / POST OFFICE LAND TRUST: I 1 1 \ \ \\ / / / / / / //// / / / // / I I i FISHER TRUSTEES — - /� �' S i �'_ % / / / / / CHARLES ER HURT & SHIRLEV (D.B. 1661, PG. 116) ------ ���// FISHER TRUSTEES 'ZONING MIXED COMMERCIALPMENT - �i'i i� ///%/ I ZONING:LANNED DEVELOPMENT '/ice '/ice -�_/ / / --__ MIXED COMMERCIAL I // N 0 ¢ O r Z <O > . e_ W Z z O y O O F LLe Q � Q 3 < ¢ ¢ i z m ¢ Q rc 0 R �6 gm3 N m z u F o O o w u 3 8 ��anoo 0 Q N Z Oz a z a OOz O mrCDF C N 2 j �aFO wmxww �aw0 SHEET C08 SITE DATA EXISTINGPROPOSED ZONING: RURALARFASDISTRICT MAGISTERIAL RIO DISTRICT EXISUNGPROPOSED USE: PUBLIC WATER FAGLRY WATERSHED: POWELL CREEK OVERLAYDISTRICT$: ENTRANCE CORRIDOR -AIRPORT IMPACT DISTRICT BUILDING SQUARE FOOTAGE PROPOSED WATER PUMPSTATION -LZM BE COVERED GENERATOR PAD -]BB SF SETBACK$: 250' MINIMUM FRONTAGE ALONG EXISTING PUBLC ROAD 150' MINIMUM FRONTAGE ALONG INTERNAL PUBLIC ROAD OR PRIVATE ROAD 75' FRONT SETBACK 25'$IDESETBACK 35' REAR SETBACK FRONT SETBACK NOTE: FRONT SELBACK$HONM IS 75' FROM EXISTING PROPERTY ONE RUNNING ROUGHLY PARALLEL TO EXISTING BERKMAN DR RIGHT-OF-WAY. PROPOSED SUMNG IS ALSO SET BACK AT LEAST 75 FROM THE ANTICIPATED VDOT RIGHT-OF-WAY FOR BERKMAN DR. ANTICIPATED VDOT � I I \ I FT GRADING \ IY LCEUTO�ER I I — ]5' FRONT SETBACK FROM EXISTING -� PROPERLY LINE / W �75' 3 / 2F / r/I I I I I I I I I I \ �6 I \ SPACE FOR I % ANTICIPATED FUTURE \ I I GROUND STORAGE \ TANKS P i I (TYP) \ I I \ TRANSFORMER 4 I I I I 30.3 TO PROPERTY ONE IX ' a I D ' I CONCRETE LEVEL SPREADER q j (SEE SHEET C13 FOR I RESTORATION DETAILS) LIMITS GENERATOR - III illV STORMWATER MANAGEMENT FACILITY EASEMENT �I Er •• �� •••� • • ••.. (I Q axe �, • •Y• •• •t• • •.• • • • ••.i�. 32-041A2 STORMWATER MANAGEMENT FACILITY ACCESS EASEMENT DB 5637 PG 328 SETBACK LINE (TYP) J A A ! CONSTRUCTION LIMITS(TYP) UN N a O Z U ag Q 25 00 > rc d W Z 2 rc O H O G K Q Q Q Q i Z m Q Q a O Z cNa �dw wfF yam SHEET C09 0 I I I I I 1 I I I 1 I 1 I I I I I I I I I , / / 1 EXISTING CELL TOW X�x III ANTICIPATED VDOT GRADING \ \ EASEMENT (IYP) / I lI 1 / I ANTICIPATED VDOT \ RIGHT-OF-WAY I \\ I I � PROPOSED CHAIN LINK (TYP) INSTALL FENCE ALONG FINAL CLEARING LIMITS SEE SHEET DC05 FOR FENCE DETAILS I \ I I \ I \ \ PROPOSED CLEAR & GRUBBING LIMITS (TYP) \ SEE SHEET COS FOR CLEAR &GRUBBING DETAILS \---------------- 1 - --y 15 OP 0 --1--�— A` GRADE SWALE TO DIRECT DRAINAGEAROUND BUILDING / PAINTED "NO PARKING" P / I 1 I I I I I I p I I I i / I / I / I / I / I I I I I / I / I / I 1 / I / I / I / I / I / I / I � r I I I 1 I I 1 I u le a I I a I Po,; ;roe 3 Ili a l I Z ) I i OOftO(1CFf1 OI 11.IO a I Wa /r STATION BUILDING -1,209 SF GENERATOR PAD - 769 SF FF EL = 624.5 eYgyi L�Y// O / v / / Y o O w -w w 25 00 o ,7; j---j r '25� - %<\ \\ � PROPOSED ASPHALT (TYP) GRADE SWALE TO DIRECT \ \ SEE SHEET DC01 FOR DETAILS DRAINAGE OFF DRIVE AND jl1 AV I�� TOWARD BERKMAR DR PROPOSED WATER MAIN (TYP) \\ \\ SEE SHEET C14 FOR DETAILS A 1 PROPOSED LANDSCAPING SEE SHEET C15 FOR DETAILS PROPOSED 20'SWING GATE \ I SEE SHEET DC05 FOR FENCE DETAILScA CONNECT PROPOSED ACCESS DRIVE TO END OF -- EXISTING BERKMAR DR / l / / I 1 I I -_--- y > I I 1 I I I 1 1 1 I I 1 I 1 1 I I I / 3 1 \ \ I \ \ 1 \ 1 1 \ 1 I \ I \ � I 1 I I j I l I I / 1 1 / I l I 1 / 1 / i m m I l I 1 / BASIN ACCESS DRIVE NOTES. I l I 1. CONTRACTOR TO GRADE IS'WIDEAR I l I AND INSTALL 10' GRAVEL DRIVE IN I / I CENTER OF GRADED AREA 2. INSTALL PER GRAVEL ACCESS DRIVE SPECIFICATIONS. �S ANTICIPATED GRADING LIMITS OR DRIVE INSTALLATION SHOWN. HOWEVER, ADDITIONAL GRADING MAY REQUIRED WHEN EXTENDING DRIVE ENTIRE DISTANCE TO BASIN. 4. IF ADDITIONAL GRADING IS REQUIRED, CONTRACTOR TO INSTALL ANY ADDITIONAL EROSION CONTROL / MEASURES PER VDOT SPECIFICATIONS. / 5. PROPOSED GRAVEL DRIVE SLOPE / SHOWN AT 1516%i. EXISTING $LOPES/ THIS AREA VARY FROM 1420%i / / ILS / / /I L/SEER II IG LF / R L ACC SS DRI /GRAVEL ACCESS DRIVEl / l lA.iO EXISTING SPOT= ELEVATION (TYP) I 1 1 I I I I I I I 1 1 1 I I 1 11 1 I 1 I I I 1 I 1 11 \ S O CQ � L Z O J 0 W w O CL z r a a 0 r Z w < �_ a 00 > rc d W Z 2 K y O Q y O w rc Q Q a a i z m ¢ a a 0 z < 0 0 3 8 SHM C12 I IT ANTICIPATED VDOT GRADING EASEMENT (I YP) 0 X EXISTINGCELL TOWER X- ROTATETEEUPTOWARD BEND ® 5 5'f ANG1E 1 D STA=d5RH.W, 15 )TL 1 I 18"IE=816d8 1 8'IE= 616.W -'-----__--__ 3 LF B" DIP > i� ___ VALVE BOX TA=4DAT STA=d51616], 1212E 18Y16'REOUCER ______ AIR RELEASE _8'IE=618.83 16'PLUG STA=M A•4N5]251501'L IE•Bfl.Bd VALVEA$$EMBLY X.F-3 LF 8'OIP®5.5]%'-- - IE•NN, > I- I STA•45+XLW.15.W3L 8 �°BEND IE•81523- ROTATE BEND WNM TOWARD > MBLY - TEE @ W. ANGLE 51F 18' OIP 1 W/6" GATE VALVE & B STA=05t61.87, B.OB' L- I i STA=4HBB. W, 30.O:T L" 8-IE =618d6 18"GATE VA_ _BOX IE=61268 8'BY BEND STA • M 55.82, 181W L I ROTATE BEND WNM TOWARD / IE.ItUt X TEE WANGLE V }3 LT 16" DIP 00.0096 I ifl TFF Ntl M1'RFNNG.EN 5TA=A5a616], 539' L I 89E=01BW 310± LF TO BERKMAR DR/ LAUREL PARK LN INTERSECTION STA=4N55.B2, 1563' L E=611J9 31F 18' Dll STA= STA-4 (X50. 1504E IE=6125] 18' DIP 45400 LF L _-•STA•d51516],005'LJ 8E=815.Bd 26'TEEEEREDUCER _ ROTATETEE UUP TGWARO XC- TA=dA-4I8°4 ANGLE X S2W16],006' - _--=81586PF'NE' y 8'IE= 1- 8�.5 51F 26'OIP 45Nb.67, DUN' L 24"IE=61584 4 LF N" UIP- � 1 � 2d'OIP� DIP 5lF N"DIP- I N"GAUEV5LV I �31F N"BB°BEND STA•4 71.6], 0.06'L- 1 j I STA•45a66.88. 6.84'R N'IE.815.84 241EF 6 5.8IP _ 21.1TTEE 1 STA=d5N8A$ O.OT IT 1 M"IE=615,54 1TIE=610.17 3 o I 6U`24'DIP I 2d"x iT TEE I $ I 5TA=0.5UOT I 24.:E-615Sl 2d'IE=6156 I I I 1 I I I 1 I iTIE=618.11 I 1 I I I K i I <¢ C I I L I Lu m I I I I U I I I I U jI 10 0 10 20 I I -le 5 ket I I UTILITY CONSTRUCTION NOTES: I 1. CONTRACTOR $HALL VERIFY CONNECTION LOCATIONS TO EXISTING E UTILITIES PRIOR TO CONSTRUCTION. 18 RIP 2. ALL PIPES SHALL HAVE SMIN. COVER. STA-4 70D151WAVIL I 3. PROPOSED BUILDING ROOF DRAINS _ t8'IE-6i6.8t __ I I SHALL DAYLIGHT ONTO GRADE. X ----- I 4. CONTRACTOR $HALL OBTAIN ALL I 311=18' DIP REQUIRED CONSTRUCTION PERMITS 16-CONNECTION - PRIOR TO CONSTRUCTION. AT BUILDING J �STA=45N331.%01'L 10"D.I P. $URGE RELIEF 18"IE=61661 LINE TO SUCTION MIN U II Id', CONNECT TO TRENCHEASRBUILDING DAYLIGHT TO GRADE AS REO'DEO'O C �.. a I SPACE FOR ANTICIPATED II 3 I Z 'I r FUTUREGROUND J I o /a wa 1 STORAGE TANKS J, ,f 6"$TORZ FITTING FOR 18"GATEVALVEB BOX J I BYPA$$ PUMP SUCTION n TA-45185.58,15.07.E - x--,__x ypxl CONNECTION 5 DIP LF 18"DIP 20 LF 8" 18"B8°BEND � LID 1 i' AND GRADE BREAK 8 BEND STA=d5N0.1], 1507.E 89E ••°818.58 (3)10' CONNECTION AT BUILDING STA=4518d 27, d5t80.5], a I p e 45°96.91, 45196.42 12-IE-816 1] ®I 131E 1T OIP V fyl � 1]lF 8'OIP 6"$TOR FILLING FOR BYPASS PUMP DISCHARGE 81F N' DIP- Wil'W CCPNNECTION 45°BEND STA=48a02.26. NN''L E=B1B58 8"IE=819.58 VALVE & BOX 18e.27, 45190.57. 45t86.430 2 ]4' L 8'17 24"PLUG K+N.3) A=46+2d.N, 0,MR �� 24"IE:8158M1 `18 LF 4DIP N" GATE V L �-S�TA • CBg8.83. 83, DW 00& L �24"IE•815.G - DIP ���_ f i IE•815.84 M"x iT TEE //24'x i2 TEE STA=45a8U.43.0 WL STA•45t88A3.0.08'L N"PWG LTA- (IRLI34, 8.80'R L N'IE •815.84 r a Z � 0 Q K ¢ Z H 0 O 0 F W N Q Q 3: K Q Q 6 Z m Q Q a 0 a� a CN) w�5 w�F SHEET C14 O PLANTING LEGEND ABBREV BOTANICAL NAME COMMON NAME SIZE ROOT NO. TO BE PLANTED TREE CALIPER ANTICIPATED HEIGHT (AFTER 10 YR) VP PINUS VIRGINIANA VIRGMNN PINE 8'-7' BB,B 27 1'-1.S 14'-1T D L;miverd..aAe (mWMCEeiplim wo-em mx u«a); D LosaemaM rypc ofPdcctlesfcmmr D Gmde cLmges rtquinng tr[e weW mmW; o bmcNne d mmeWa Imyma me limldxrNm;ng. unxPmw lomXcawimpeinldlilma:mnEeigDlclemh mlemryuipmemepnmdv. hs1 Wgin pc g mbc ONO O No pMinB aheB hepwmtil Ihebeemmhioghubemm[puledmdappsosxd by a Camry Iovpccmr. , 3. PrtLdublRHon Code.: �/ �prtsmmicnm�modnwvmmwm meBSeminmdaim the sOlmmmem vhe. , A [p:ipnml DpeFapw ana $ema K. O egee�pmty v uure Kh 6FL sb mL `«'amm�gc ofcovmufim wmv6 mmoainevoY meunabepem:ilwe wimm me miptioee oFvew mbF / mycd. II s.swr Imo Fna smrm.amDelmabv Deiru _ .. Q mete ml .mc ttltrmw mvca. / 4 Rm: em nd pemilW wmau¢100 feet orme anpBm of treeswge roved 1. Tmis MYcv : TMc—=—umU7nftu wlh eWca nuns IN fttl ofine"Pline of bees wbe mvm, t' g oPT o"xml"m lcdmi "feeldepopocedbni,eiogdgM gmlifry du06cp:daclW byf mg. \ / I M Fcvcwg mnB be in Ple«ebe ehaB ge inRwnea mdePPovea M'a CoumY Gspolm Padw8maa8 mcwrncuom. , x 9.Tm WeW: D lmxl mart be misty nimiu me dnplimafxaee to be wed, amm meB a 11lR psoviaedmaecrosuusam aeuDsubmilba \' .i 1 ,nlgmmd / JT 1a. TPm WFW: DWmale,d muel be lP�mxe vamm me aaPBmno-«mtc u,W,.o-cn Pvuemnhe Pxwea:nmewrmm«imaemB mgmhsed' fro epPovel. 1 I I I I � I i 1 I } \ I I 1 I W S $ • �• I I I I I I , � � I ',r ' c S ,� p.. ^� � �7 1 r i • ! Xi i i l i i i, i l i i i l � l 1 I I I I 1 i/ / I / r •gl L i l l, m.B UNd3TRU9E0IAILBN(PE EIIFFER (t4P11 I I I I I I I / f 1 •' 1b.B'( VCPI_+_ _1—F._y3 I_ j_ �� I I � � I � II I l i l 11; ! 1 7 I I I 1 VIRV-7'- E • , I I S-T-BBB \ l• / I I 77 I \ ' c ., -. I I III / I I I I \\ Y TYPICAY1\, + .r. , �� I1 II I \\ \\ 11. TnpaminennaT=nj.: D Wlmtrmsl:mgus<gmmaw,iNomc Bmita xfclemae.Bsbeube aene�rm mxyltm mevmtsorbeesmposuble.TmbeW6lmaese / ! \ f ! / / i I I I I u 1\ I I\ 1 I ImP btt dvllhcroslmm mm uvmemx NnenilD®aerewe mn:mmwylmmMne a,B acaroy rxa«rods. ! - \ I ! I � ! 1 I I I g 11 \ 1 1 , I \ \ \ D Pm1� sin6ekB be me bslaauvmmM Along mcfwl<Imnup. / , /' / \ 13.REM NTree: / D D�immeai.mhM Amiss renlimlim:melmmabeae:m«emeead bya vweP<cielia i / / \ NOTE:IT L4 TBE DliI'ELOPER'SbF.RPONSDIILITYTO CONFERWTpN THE CONTRACMRON TREE CONSERVATION \ 1tfQOD1EMENTR / 5i 12 �a2� r EKISTING E ATIBE CELL TOWER TREE CANOPY: EWiOT�E CANOPY W%(1.51 AC) PROPOSED TREE CANOPY 3294(R51 AC) PRECONSTRUIIONNOTES: \ 1�FZSflEs SHAll BE ESTABLISHED TO MINIMIZE SOIL CONPACTON. MD ROOT SFEM a BRANCH DAMAGE , BMW coNS CT1oN 1 \ 2. PLASTIC FENCING MEETINGTHE REQUIREMENTS OUIUNED IN CHAPTER 3. OF TIE ARGINW EROSION AND SEDIMENT \ CO OLIWIDBOOKTODEFINETIETREEPROTECTONZANE I \ NdDUMITACCEM. �I ]. INSTALLTREEPROTECTIMFENGNGALONGPROPOSEDCHAIN INK FENCE AUGMAENT, FOLLOIMNG CLEARING a GRUBBING ACTMTES, AND ALONG INTERNAL CL NGB GRUBBING / UMTS. 4. PRIOR TO GRAUNG TREE FENCING SHALL BE INSPECTED AND APPROVED BY A COUMY INGPECTOR 2. NOCCNSTRUCTONEONP68W SUPPUESO MEMSSNNL BE ALLOWED IN TREE PROTECTON ZONES, 3. GRADE CHANGES ARWNDTREES BHALL BEAVO DED. IFTHE 4. 1 I/e JI / co _w C3 I 4 1 ' I CIO �� I Q .V11 3 / ANTICIPATED VDI D EASEMENT(TYP) 1 ANTICIPATED VDOT 1 t: '} IV "I� ONI\v 1 I 1 e PREADER \ I 1 r �\ , 1 1 1 I 1 r � 1 � I 1\ I \ I ` 1 I , I 1 SPACE FOR f I I ANTICIPATED FUTURE / I II I I I I I I \ I I I I I I II I II j I 1 I GROUND STORAGEI I I �I I I I I I I 1! TANK(TVPI / I l I } I I I I I j I / 1 ram- EBUFFER(IYP) I r 1 w � / w' 1 isa rP) — �\ —l__ D d I 1 i f J f r 1 1 / I I TD I m.a UNDISTRUBEO LANDSCAPE BUFFER(IVPI l RETENTION BASINS 1 f I I I 1 1 I I 1 SEE SHEET CI3 FOR I I PLANTING DETAILS I 1 1 STORNWATER I MANAGEMENT FACILITY EASEMENT ' DS BUT PG 329 • ! l I 1 1 !I /! '-85 FJLOpo / I I II / Ni LEVEL SFREADER 110 1 1 1 r / � / / / I !I 11 ff'K I If I ♦ I / I / l 1 / l �9' I 1 \ 1 I I 1 S.G IRGSTRUBEO IAIiDBOAPE BUFFER (TYP)' '� // ' • - / '• // 32-041A2- STORMWATER s9 / MANAGEMENT C ESSEASEMENTY I 1 DB 5837 PG 326 I% AllSa-'y i•ItA_/.sl�!\A IA.'(.a �l/C f! I Ilf )''/ r / ; r -S n/' / ; /_ /'!',// / ,ll,.A {,J . \ \ �`tj , \b ` it l yrr f , l I�/ Y' /• 1/ y, T 11' r I I 1 1 I / Ifit 1111 11 7 I I I I r / /,. •" /i i // IIII � /L •'/i 1 l I / / I(I I- I I I I! , /. EXISTING RIGHT OF WAY PERMANENT EASEMENT PROPERTY LINE HORIZONTAL CONTROL POINT BENCHMARK • SURVEY MARKER SOIL BORING SANITARY SEWER AND MANHOLE FM FORCE MAIN AND LIFT STATION SANITARY SEWER SERVICE & CLEANOUT WATER MAIN, HYDRANT, VALVE AND MANHOLE WATER SERVICE AND CURB STOP BOX STORM SEWER, MANHOLE AND CATCH BASIN CULVERT AND APRON ENOWALL GAS MAIN, VALVE, VENT AND METER oHll HANDHOLE BURIED FIBER OPTIC CABLE AND MANHOLE — T-BUR T 0 T BURIED PHONE CABLE, PEDESTAL AND MANHOLE WBUR �c-rvB TE BURIED TV CABLE, PEDESTAL AND MANHOLE OE BURIED ELECTRIC CABLE, PEDESTAL, MANHOLE, TRANSFORMER AND METER OVERHEAD WIRE, POLE AND GUY WIRE ¢ LIGHT POLE TRAFFIC SIGNAL ♦® y STREET NAME SIGN n SIGN (NON STREET NAME) T,rn err RAILROAD TRACKS O6.. DECIDUOUS AND CONIFEROUS TREE Q BUSH/SHRUBAND STUMP (YYY-y y y y 1. EDGE OF WOODED AREA vdFr WEI_AND BUILDING x FENCE (UNIDENTIFIED) BARBED WIRE FENCE xC CHAIN UNK FENCE xB ELECTRIC WIRE FENCE xm WOOD FENCE xww WOVEN WARE FENCE 0 0 0 PLATE BEAM GUARDRAIL ❑ ❑ ❑ CABLE GUARDRAIL op POST/BOLLARD �wwwvv RETAINING WALL PROPOSED 6+00 1 STREET CENTERLINE RIGHT-OF-WAY — PERMANENT EASEMENT TEMPORARY EASEMENT CONSTRUCTION LIMITS — SANITARY SEWER, BULKHEAD AND MANHOLE FM FORCE MAIN j`0 SANITARY SERVICE AND CLEANOUT WATER MAIN, TEE, HYDRANT, BULKHEAD AND VALVE QQ A H i1 WATER VALVE MANHOLE, REDUCER, BEND AND CROSS L H WATER SERVICE AND CURB STOP BOX �C -- STORM SEWER, MANHOLE AND CATCH BASIN CULVERT AND APRON ENDWALL -------------�--- DRAIN TILE —— DITCH /$WALE RIPRAP STREET NAME SIGN 1 SIGN (NON STREET NAME) 1'WVWVYV' RETAININGWALL MISCELLANEOUS PROPOSED ...... WOVEN WIRE FENCE MD WOOD FENCE xB ELECTRIC FENCE xC CHAIN LINK FENCE BARBED WARE FENCE x FENCE ❑ ❑ ❑ GUARDRAIL W-DUCi TV DUCT TV CONDUIT —rvOH —TVOH — OVERHEAD TV T-DUCT PHONE DUCT PHONE CONDUIT — TOR — TOH PHONE OVERHEAD OIL OIL PIPELINE G NATURAL GAS MAIN FOOUCi FIBER OPTIC DUCT FO FIBER OPTIC CONDUIT x x STEAM ':'NVASPACING POST -TO -POST NOTES: TREE PROTECTION FENCE EXISTINGTREE FENCING 4Z E7(S-ING ffc::�cCD:) (c- �:�D DE 3FAOE TO MIRAFI MIRASAFE ORAN APPROVED EQUAL STAPLETO VIERTICAL 2X4ORTIE TO METAL T POSTS. MAINTENANCE REQUIREMENTS: 1. PLACE CONTINUOUS RUN OF FENCE MATERIAL ON BOTH SIDES OF 1. INSPECT WEEKLY AND AFTER EACH RAINFALL PRODUCING 0.5 IMMEDIATE WORK ZONE IN WOODED AREAS AS SHOWN ON THE PLAN$. INCH OR MORE OF RAIN. DO NOT ATTACH FENCE MATERIALS TO TREES. 2. REPAIR OR REPLACE DAMAGED FENCING IMMEDIATELY. 2. TREE PROTECTION FENCING FABRIC TO BE PLACED IN A RADIUS OF A MINIMUM OF 1.5' FROM THE TRUNK OF TRUNK FOR EACH INCH OF DBH (DIAMETER AT BREAST HEIGHT). AREA INSIDE OF FENCING SHOULD BE A 3. REPLACE ANY DAMAGED SIGNAGE IMMEDIATELY AS NEEDED. NO ACCESS, NO ENCROACHMENT ZONE THAT SHALL HAVE NO PARKING OF EQUIPMENT OR STOCKPILING OF SUPPLIES. 4. IF ROOTS ARE DAMAGED, CUT OFF DAMAGE AREAS CLEANLY AND KEEP -EXPOSED ROOTS MOIST BY SPREADING PEAT MOSS, MOIST 3. "MIRASAFE' HIGH STRENGTH POLYMER GEOGRID FABRIC BY MIRAFI TOPSOIL, OR MOIST MULCH. NO PAINT IS NEEDED. CONSTRUCTION PRODUCTS, PENDERGRASS, GEORGIA. 5. FENCING $HALL BE INSTALLED SUCH THAT NO TREE BARK 4. ONE SIGN PER 50' OF TREE PROTECTION FENCING SHALL READ: 'TREE DAMAGE OCCURS. IF SUCH DAMAGE DOES OCCUR, ONLY PROTECTION ARENDO NOT ENTER AREA/PARA PROTECCION DE LOS CERTIFIED ARBORIST SHOULD DO ANY BARK TRACING. NOPAINT ARBOLES/ PROHIBIDO ENTRAR° IS NEEDED. O CQ rc L Z O J 0 W LL w O CL Z r O a 2 Z U S Q Od 3 ' �z w z rc O m O O Q rc U w Q Q < < Q Q D Z m Z Q Q rc 8 � a z a� u g 6 0 0 3 8 SHEET DC01 PLACE 5' CONCRETE "WITNESS" POST IN REMOTE AREAS AS DIRECTED. MARKER LOCATION MAY BE SUBJECT TO HIGHWAY DEPARTMENT APPROVAL. EXISTING GRADE - RESTORE ALL NOTE: HYDRANT MUST BE DISTURBANCE DUE TO INSTALLATION IN -KIND EOUIFPED NTH CHARLOTTES - FNISHED GRADE WLLE MUCH IS WATERTIGHT FRAME & COVER LOCAL DARD STANDARD. THE LOCAL STANDARD. COVER TO SIT FLUSH WITH GRADE RINGS MAY BE REO'D (12" MAX.) LENGTH OF BRANCH VARIES 12"MIN. - fi' MIN 2• TO TO' ^PRESSURE GAGE 15"MA%. 12° MIN (2]01 ASSEMBLY BARFTAW SEE NOTE 3 16"-22" z' BALL vuSE PREVENTER (RPz) 1 ' II ] CU. FT. aLVE SON BO' 10" TALL ARV ASSEMBL II >• II ADJUSTABLE VALVE BOX W/ UD #65 STONE 2" BALL VALVE 2" BRASS PIPE NIPPLE 3 n BINGHAM & TAYLR FIG. NO. 4905 DOG -HOUSE SECTION: BETWEEN CORP STOP SCREW TYPE OR APPROVED a ii ( ) ALL VOIDS TO BE FILLED AND BALL VALVE EDUAL 42"MIN 6" GATE TEE HYDRANT WITH BRICK &GROUT 2" NET CORP STOP VALVE (SEE PLAINS ME. /// NO. 57 STONE TO 16°/24" x 2" BASE CORP LE _ °, POOP SIZE) RRE4QUICSEW 2 BALL VALVES MINF RWSA 16"/24"TAPPING 250E P.S.I. CouCRETE ` I WATER MAIN BABE AND THRUST .� ° MH SUPPORT M.J. GALE VALVE BLOB( AGAINBS \V/ UNDISTURBED STABLE BLOCKING SOIL (TYP QTY - 2) STEEL PILE 6-MIN. RESTRAINED JDNT FlTTNGS WHEN ME SOIL IS DISTURBED R WHEN CAP. M.J., RESTRAINED w/ 2' NPT TAP 18"(TYP) A HYDRANT IS LOCATED IN A MI IN ADDITION TO POURING CONCRETE A SWEL PILE SHALL BE USED AS ADDEBONAL SUPPORT. NEW WADER MAIN EXISTING WADER MAIN TO BE TESTED NOTES: 1. CONCRETE SUPPORT BLOCKING SHALL BE OF WATER LANE SUFFICIENT LENGTH AND WIDTH TO OVERHANG '� P NOTE MANHOLE BY s° AT ANY POINT. --- 2. ARV SHALL HAVE A 1/2' BALL VALVE INSTALLED ON 2500 P.S.I. L SURROUND WEEP HOLES NTH RAVEL AND KEEP FREE R CONCRETE. 2. MAINTAIN A 3 1/2' MIN. WWR MOM ME MAIN TO ME FIRE HYDRANT FLUSHING PORT. BALL VALVE SHALL BE CONCRETE THRUST BLOCK - G 2'x 2' BEARING AREA. 1(FINISHEDN GRADE DITCHES IALL SLOPE AWAY FROM THE FIRE HYDRANT AND ACCESSIBLE FROM MANHOLE LID. - VALVE BOX. 4. ME GATE VALVE IS ALLOWED IN SHOULDER OR BEHIND ME DITCH. 3. CONTRACTOR TO VERIFY MANHOLE SECTION HEIGHT < IT IS NOT ALLOWED IN THE DITR. NOTES: . M. p S FIRE HYDRANTS SHALL BE INSTALLED AT LCCATIWS MORE WEEP BASED UPON TEST PITS. MANHOLE SHALL BE SIZED - < HOLES ARE ABOVE ME PREMIUMS ROUNDWATER ELEVATION. IF 1. NO PERMANENT CMNECnCNS MAY BE MADE TO THE FlNISHEp WATER SYSTEM PRIOR TO THE RMAN SUCH THAT THE TOP OF ARV (WHEN INSTALLED) IS REWIRED TO BE BI NET AREAS, THE WEEP HOLES SHALL BE COMPOISINFECTON OF AND TESTING. PLUGGED AND ME HYDRANT HALL BE PUMPED DRY. 2. WE LAST JOINT MOW BE RESTRAINED R BLOCKED. 12' -15' FROM COVER. NOTE : IN REMOTE AREAS, VALVE BOXES SHALL EXTEND SIX (6) INCHES ABOVE GRADE TYPICAL FIRE HYDRANT ASSEMBLY DETAIL AIR RELEASE MANHOLE DETAIL xenexx Mar B DArz: DRAWING NUMBER : FIG. N'T'B W-4 x,M sEPT2D+s TYPICAL TEMPORARY CONNECTION FOR ORawIrvD NUMBER: TYPICAL GATE VALVE 6 FLUSHING AND TESTING WATER MAINS WATER 13 NITSMOTTOWATER rvolro �`�' SCALE RIVANNA WATER AND SEWER AUTHORITY TDA BBB, Tonle RIVANNA WATER AND SEWER AUTHORITY NOTE: HYDRANT MUST SE EQUIPPED WDTH NATIONAL HOSE THREADS NET) MUEULIERS ORAPPRTYPE TYPICAL FOUNDATION AFIREHTU RAMORAPP EQ UALEQUAL 5' MAX._ __FLUSH BOX LIO I'vALVE Box NITIAL BACKFlLL 4MAX.Q II °- IN6" BEDDING OR B#57ED STONE r PAVEMENT RESTORATION (SEE6HEETDC03) __DEPTH �-SLURRY BACKFlLLFOR ALL BENDS FOR vu6Es OR PLOWABLE FILL TRENCH TO TWO (2) INSULATION LAYERS 6'GATE VALVE WI AC ACCOMMODATE WITH JOINTS STAGGERED NJ RETAINING ANCHOR IF 3" WHERE SHOWN ON PLANS GLANDS REWIRED. T CU, FT W68 STONE ROCKY FOUNDATION MATERIAL UNDER -CUT CONDITIONNG AS 6- WE AND COVER IRED IN M V45' W COMPACTED WS]STONE GRANULAR FILL PLUG J— ^^ 2A IN INITIAL BACKFlLL 4 MIN. 6"45, 3•12 25WP.SA. ° . 1 BEDING 12" 1 OOP MIN T ' 00 TWO(2) INSULATION LAYERS CONCRETE BASE°ANCHOR THE VALVE TO THE HYDRANT MIN. MIN. MIN. 6 SY STONE MIN MIry WITH JOINTS STAGGERED ANDTHRUST WITH2-'THREADED RODS (GALVANIZED OR " DEB OR DDING STAY SECTION I -I SECTION 2-2 WHERE SHOWN ON PLANS 26" WATER MAIN BUCKKAGAINST POURING CONCRETE, UNDISTURBEDCR 4' MIN IN ADDITION TO POURING CONCRETE, ] STONE _ _ COMPACTED A STEEL PILE$HALL BE USED AS AN STABLE SOIL OR ROC ROCK e'S ifa STABLE SOIL STEELPILE AUDmoNAL suPPORT NOTES: to a if a. WATER MAIN INSULATION AND SLURRY BACKFlLL DETAIL WHEN SOIL IS DISTURBED OR MEN A HYDRANT IS LOCATED IN 1. ROCK BE REMOVED TO AMINIMUM OF 6"BELOW THE PIPE AND I2" NCTTOS F A FILL, IN ADDITION TO POURING CONCRETE ASTEEL PILE MINIMUM CLEARANCE TO THE SIDES OF THE PIPE. If a if SHALL BE USED AS AN ADDITIONAL SUPPORT. NOTE. 2. RS/OR W68STONE SHALL BE PLACED AGAINST UNDISTURBED SIDES AND _im 1. SURROUND WEEP HOLES WITH GRAVEL AND KEEP FREE OF CONCRETE. BOTTOM OF TRENCH TO THE SPRINGLINE OF THE PIPE If M n.`� 0 2. MAINTAIN A3'MIN. COVER FROM THE MAIN TO THE HYDRANT(INCLUDING DITCHES) 3. INSTALL POLYETHYLENE ENCASEMENT, TRACER WRE, MARKING TAPE AND S. FINISHED GRACE SHALL SLOPE AWAY FROM THE FLUSH BOX LID CLAY CUTOFFS IN ACCORDANCE WITH THE SPECIFICATIONS.. t. 4. HYURANTS SHALL BE INSTALLED AT LOCATIONS WHERE WEEP HOLES ME MOVE THE PREVAILING 4. THE INRIALBACKFlLLSHALL BE PLACED AND COMPACTED IN W LIFTS. GROUNDWATER ELEVATION. IF REQUIRED TO BE IN WET AREAS, THE WEEP HOLES$HALL BE PLUGGED 5. NO ORGANIC OR FROZEN MATERIAL OR DEBRIS SHALL BE ALLOWED IN THE AND THE HYDRANT SHALL BE PUMPED DRY. TRENCH. Gwew,LMre: 5. LID$HALL READ'RW$A' AND APPROPRIATE MANUFACTURER NAME OR LOGO. 'FIRE HYDRANP$HALL 6. BELL HOLES SHALL BE DUG OUT IN ALL CASES. UH.DFTULI$API CAa>= FTM NOT BE LISTED ON THE LID 6. CONTRACTORSHALL PROVIDE THE OWNER WDTH THREE (3) FLUSH TYPE HYDRANT WRENCHES PRIOR Z SH ALL INITIAL BACKFILLALL BE 2IA MATERIAL PLACED AND COMPACTED IN 6" UHUSTBIOCKSWDPR r SSTURG+DRe vXa W12 w'Oi TO ACCEPTANCE OF PIPELINE. LIFTS. INITIAL BACKFlLL SHALL EXTEND TO PAVEMENT OR TOPSOIL IN `^ T. BOX AND LID SHALL BE VEHICLE RATED. LPNDSCAPEDAREAB 1. USE MINIMUM 2500 PSI CRCRETE 2. CONCRETE FOR THRUST BLOCKS 91ALL NOT BE ALLOWED TO INTERFERE WRI JOINT OR RESMAINT B. SILT STOPS SHALL BE PLACED ALONG TRENCH EVERY400'. HARDWARE. PLASTC SXEETXG MAY SE PITACED OVER PIPE OR FlTTNGS TO PREVENT CONCRETE FROM 9. MAXIMUM PAYMENT TRENCH WIDTH FOR ROCK REMOVAL IS 12" ON EACH SIDE ADHEDIXG TO SURFACES. CONCRETE FOR THRUST BLOCKS SHALL BE PLACED AGAINST UNDISTURBED BURY HYDRANT DETAIL OF HE PIPE PLUS THE PIPE DIAMETER. SOIL' 3. TIE DESIGN FNCINER SHALL BE RE3PCNSIBIE N VERIFY WE TYPE AND SRE OF ALL THRUST RLDRS. NI8 R�xsEPTm1s DUCTILE IRON WATER PIPE INSTALLATION DRAWING xunBER: arEx sEPrm+s DRAwTxc rvuMBER: CONCRETE THRUST BLOCKS MOTTO AND BEDDING WATER 1 WATER 2 MOTTO B MI SCALE RIVANNA WATER AND SEWER AUTHORITY EXAMS: SCALE RIVANNA WATER AND SEWER AUTHORITY T O a x z U S D <o > 0` 3 1 z z 0 O G rc N NO Q Q Q o ° z Ou m a a rc op O m2 �4 ES N a z a� g 0zoom SHEET DCO2 (A L/TNON/A L/LiNT/NG' sarzmrnl f ERNXES B svE° eUPoxs CC1 DMW2 .d. ELEdEd— d —E a, .xd._. x„,.x,P „b ww,_ wm s...., o. .„l'p w.� hdEd iu.mm..r,e i.iEd, [rv,woe ® Vl S wwp P—DDTUM�I[f x.w. �re HLWPQ ."' onalumnum r�om�mm.INa .d m�lai MlpxYfullfumXl[0 n:-ph. 1 ud gfiam.wmrenm x .0 ph.—mvenmmh Od'.—'e: Nnu Idl *1 1-11. ore wm IT LEA 11 ­1 ..I .— �.ew. . "E nld. YNi.. qnm miu:mnw ma: . Oymairgeouwmne,o-esxwmA[Ix.l ym..p.n..mm vm:w 1.,11. E..,..Ed. Rlmmpl.Ifw. ..,m�w,nxlY blhmo,mmw AMmWesYxpa®.a w y,n DMW7 LED Wet Loubm TTrmmm re�xID m ®. : .. _'1 YwlBbppYrtNw pws.w^ �. wpm ® �em'�atiu.wnm� wmyane:v.a mpmpwggmeP w ® m�InIBMG mN�' W.MwoA�rn mryw�gFyuy�wwm�wC m1 uNM womwmma,., ivbxW�.xnI�ipm�'tlw ' ea.omeilpm MrtidIdn',!..t�eDe p9ymMm�mAeaw AaY.YbgN" woamnµuY^ ��'i ® xaWaa.xpmum ,nmprml HLWPC2 w<Xw,A•wllmmnEd a& • Mxv.mnpxL4 z,o+a.x�xmwe..mamx.•xww.. .r.w`..:w.wm. swon9urilmm lYmn.mA�x mmdmepM1-Masup.xudu pmmapm: n 1 mom.. ,•mw"'u �m duu,m., n bmanupY.p pvmxmxlxWMAx,WIf1Y3 ..+�wunnEpuiw:� �ry,eV'[4gAM4xxnAAlmnyXEWtW �4 �I'm,mynWl o:mn�ryepmaxxlrtl ' m"�m°"sn l'°�mn�n°ixAdiY®�n n,m lx.m mm.xYd. Ss d.M"Mw'�'Ym°,°monm m,.� m�.mp,,.. .nm ,mdSL eddd1.I .mYman, m Am px 9mx mMwm,EW Manrve¢um ddd, x lmmrEd, ... n �w,xo.xl�wm� xuro egsryquauiy.vla ysr.apeo...ummn A'lide HLWPQ WIIpYFllfulailk0MAW Ed ONEYf YMWNY Pogl[ XIMR I6p1I5 RNBW1 11'ONmW1f Oxxl W}05�11@W .IAW MV4axN41 npnMpnX�wn vivn X �m"�°w� ., -xlmx. xx.�Xedmww-napm . �I msn+n'an,exumlww �r,xxwx l...Ymm.a xw gmmlyymxy.�w Hwe i,ssr.mymm.wmmn Mn ,ov"o mw, w or ewrmrXr x wmx.mVm E�W ELLEE.x.o.. m,VueVum-s 9.MIx x p.Ayr .4:+mn xuxeem,mgxe.um� mmpmeemxoimmux YtlWM ��onmVp�axam w �WwwM. OW1d.L11Yw W n Mm.v'mswwu„:SX..A mx ,mwmg.m.r,np.amw ����w!aw E W N a s O Q z U � � Q op s Od 3 � C -L H � O F w U W � 3 Q Q W d � m Z Q Q s $HEEE DE2 ENCLOSURE B PARKING SPACE DETERMINATION REVIEW EMAIL Brad Weiss From: Andy Reitelbach <mreitelbach@albemarle.org> Sent: Wednesday, May 4, 2022 5:01 PM To: Brad Weiss; Michelle Simpson Subject: RE: SUB2021-00209, WPO2021-00035 -- RWSA deed of SWM facility easement + plat; items ready for pickup /recordation Good afternoon Brad, No additional information for that request is needed. The four (4) parking spaces that are provided on the plan have been deemed to be sufficient to accommodate the parking for this project. Best regards, Andy Andrew Reitelbach Senior Planner 11 Albemarle County areitelbach@albemarle.ore 434.296.5832 x3261 401 McIntire Road Charlottesville, VA 22902 From: Brad Weiss <bweiss@sehinc.com> Sent: Wednesday, May 4, 2022 5:52 PM To: Andy Reitelbach <mreitelbach@albemarle.org>; Michelle S. Simpson, PE <msimpson@rivanna.org> Subject: RE: SUB2021-00209, WPO2021-00035 -- RWSA deed of SWM facility easement + plat; items ready for pickup /recordation CAUTION: This message originated outside the County of Albemarle email system. DO NOT CLICK on links or open attachments unless you are sure the content is safe. OK, understood. We will send in an updated package to you. I do see that there was a comment regarding the number of parking spaces for the site. We sent in a request for determination but haven't seen a response back yet. Could you please let us know if additional information is needed for that review? Thanks, Brad Weiss, PE (MN, TX, VA, WI) Project Engineer Short Elliot Hendrickson, Inc. 651.318.0349 direct 1507.440.7485 mobile 1651.490.2000 main Building a Better World for All of Us® ENCLOSURE C ARB CERTIFICATE OF APPROPRIATENESS ,S.{.OF AL8 County of Albemarle Community Development Department - Planning November 29, 2021 Brad Weiss SEH Inc. 3535 Vadnais Center Drive St. Paul, MN 55110 Khristopher Taggart - Planner ktaggart@albemarle.ora Telephone: (434) 296-5832 ext. 3278 RE: ARB-2021-68: Airport Road Pump Station Final Site Plan (TMP 03200-00-00-041A2) Dear Applicant, I have reviewed the plans with revision date of October 26, 2021 submitted for the above referenced project. The changes made in these plans address the conditions of approval outlined at the ARB meeting held on October 5, 2020. You may consider this letter your Certificate of Appropriateness. This approval is specifically conditioned on the following: 1. Execution of the design indicated on the final approved plans, attachments, materials, samples, and other submittal items presented. 2. Mechanical equipment shall not be visible from the Entrance Corridor. Please note the following: 1. Any changes in the approved design will require a new application and additional review. 2. Changes made to the site or architectural plans after issuance of a Certificate of Appropriateness can delay the signing of final site plans and the approval of building permits. It is in the applicant's best interest to notify ARB staff of such changes and to initiate the review of amendments to ARB-approved plans to avoid future delays. 3. Certificates of Appropriateness are valid for the same period that the corresponding site plan is valid. If there is no site plan required for the proposed work, the Certificate of Appropriateness is valid for 3 years. Applicants requesting an extension of the period of validity must do so in writing. The letter must be received by the Director of Planning prior to the expiration date. If you have any questions, please do not hesitate to contact me. Sincerely, Khris Taggart — Planner cc: Rivanna Water and Sewer Authority, 695 Moores Creek Lane, Charlottesville, VA 22902 File WWW.ALBEMARLE.ORG 401 McIntire Road, North Wing, I Charlottesville, VA 22902-4579