HomeMy WebLinkAboutSUB202200020 Correspondence 2022-06-10Albemarle County Service Authority Serving&Conserving March 3, 2022 Townes Site Engineering Attn: Ms. Lyndsy Nugent 9850 Lori Road, Suite 201 Chesterfield, Virginia 23832 Re: North Pointe Subdivision Section 2 Dear Lyndsy: We have reviewed the plans entitled "North Pointe Subdivision Section 2 Road Plans" dated January 25, 2022. The following comments need to be addressed: Sheet C-1 1. Provide water and sewer data sheets. Provided with submittal. 2. Sheet C-713 is out of order in the printed version. Sheet order has been fixed 3. Improve on fire hydrant spacing and fire coverage for all lots. Additional fire hydrant has been provided 4. Review matchlines on plans and profiles for callout accuracy. Matchlines sheets numbers have been revised 5. Show sanitary sewer lateral locations for each lot. Laterals have been provided for each lot 6. Remove the following sheets from the ACSA Submittal: C-7N, C-70. Sheets have been removed for ACSA submittal 7. Final dedication of North Pointe Subdivision Section 1 required prior to final approval. Understood 8. This submittal contains very limited information related to the proposed force main system. The following items are required for ACSA's consideration: Design information has been provided with submittal. A meeting has been set up to discuss other projects and a presentation of how the system will work. a. Coordination of a demo/presentation from E/One to ACSA staff. b. Design from manufacture including pipe material and diameter, connection details and required pump information. The ACSA will not be the owner of the individual grinder pumps. c. Provide contact information for other municipalities that have these types of systems in operation. Sheet C-3 1. Label existing manhole E59 as North Pointe-16-1. Manhole E59 has been renamed NorthPointe-16-1 on both plan and profile 2. Provide a fire hydrant at the intersection of Cliffstone Boulevard and Cliffview Court. Lots on Cliffview Court do not have adequate fire protection (Lots 155- 158). Fire hydrant has been provided at Cliffstone Blvd & Cliffview Ct (road was mislabeled on plans) 3. Water main along Cliffview Court can be 4-inch diameter since it's only serving 4 lots. Show gate valve and blow -off at the end of this cul-de-sac. Waterline along Cliffview Ct has been reduced to 4" and GV, Blowoff, Plug have been provided at the end of the line. 4. Consider reducing water main diameter along Riparian Court (Lots 113-117) and avoid duplicating road names. Show gate valve and blow -off at the end of this cul-de-sac. Waterline along Riparian Ct has been reduced to 4" and GV, Blowoff, Plug have been provided at the end of the line. 5. Only two valves required at the intersections with Riparian Court since this isn't a looped system. Delete the southern valve at each tee. The southern valves have been removed, as requested 6. Relocate water meter for Lot 117 to the opposite side of the lot. Water meter has been relocated, as requested 7. Provide water meter for Lot 118. Water meter has been provided 8. Relocate water meter for Lot 159 to Riparian Court to reduce service line length. Water meter has been relocated, as requested 9. Provide justification for sanitary sewer over to MH 25. Sewer laterals could be extended across the road. Manhole 25 has been removed and lots are serviced via laterals, as suggested Sheet C-3A 1. Label existing manhole E58 as North Pointe-15-4. Manhole E58 has been renamed NorthPointe-15-4 on both plan and profile 2. Relocate water meter for Lot 1 to the opposite side of the lot. Water meter has been relocated, as requested 3. Provide water meters for Lots 9 and 10. Water meters have been provided 4. Show gate valve and blow -off at the southern end of Steep Rock Place. GV, Blowoff, Plug have been provided at the end of the line. 5. Place water meters for Lots 13 and 14 at their shared property line. Water meters have been relocated, as requested 6. Relocate water meter for Lot 87 to the opposite end of the lot. Water meter has been relocated, as requested 7. Review need for Future Apartments label on Lot 91. Label has been removed 8. Provide water meter for Lot 80. Water meter has been provided 9. Relocate water meter for Lot 76 to the opposite end of the lot. Water meter has been relocated, as requested 10.Shift water main along Retreat Loop further out into the roadway to avoid crossing under curb and gutter. The water line has been adjusted to avoid crossing under the C&G 11. Provide justification for parallel sanitary sewer mains along Lewis & Clark Drive. The sanitary sewer has been revised to avoid having parallel sanitary sewer mains. 12.Shift MH 11 downstream to the opposite side of Lot 104. Lots 80 and 105 can connect to the sanitary sewer along Lewis & Clark Drive. This run of sanitary sewer has been removed and lots are being service via the sewer line across Steep Rock Place Sheet C-3B 1. Provide water meters for Lots 29 and 61. Water meters have been provided 2. Relocate water meter for Lot 45 to the opposite end of the lot. Water meter has been relocated, as requested. 3. Shift water main along Retreat Loop further out into the roadway to avoid crossing under curb and gutter. The water line has been adjusted to avoid crossing under the C&G 4. Reduce water main diameter along Steep Rock Place beyond the last fire hydrant. Water main has been reduced to 6" past steep rock court and a fire hydrant has been provided at the end of steep rock place. 5. Reduce water main diameter to 4-inch after fire hydrant on Steep Rock Court. The waterline has been reduced to 4", as requested Sheet C-3C 1. Reduce water main diameter along Headland Court (Lots 123-128). Show gate valve and blow -off at the end of this cul-de-sac. Shift water main to the opposite side of the roadway further from the storm sewer. Water line has been relocated to opposite side of the road, reduced to 4", GV, Blowoff, Plug have been provided at the end of the line. 2. Reduce water main diameter along Cliffstone Boulevard beyond the last fire hydrant. Show gate valve and blow -off at the end of this cul-de-sac. Water line has been reduced to 6" beyond list FH, GV, Blowoff, Plug have been provided at the end of the line. 3. Only two valves required at the intersection with Headland Court since this isn't a looped system. Southern gate valve has been removed along Cliffstone Blvd. Sheet C-7 1. Lower storm sewer crossing along Lewis & Clark Drive to allow water main to cross above storm. Storm sewer has been lowered to allow waterline to cross above it. Sheet C-7A 1. Lower storm sewer crossings along Cliffstone Boulevard to allow water main to cross above storm. Storm sewer has been lowered to allow waterline to cross above it. Sheet C-7B 1. Lower storm sewer crossings to allow water main to cross above storm sewer. Storm sewer has been lowered to allow waterline to cross above it. Sheet C-7C Lower storm sewer crossings along Steep Rock Place to allow water main to cross above storm. Storm sewer has been lowered to allow waterline to cross above it. Sheet C-7E 1. Lower storm sewer crossing along Retreat Loop to allow water main to cross above storm. Storm sewer has been lowered to allow waterline to cross above it. Sheet C-7K 1. Minimum allowable slope for sanitary sewer mains is 0.50%. Revise profiles accordingly. Sanitary sewer has been revised to the minimum slope of 0.50%. A 0.1 drop is being provided per discussion via phone call on 06/01/2022 2. Sewer between MH's 1 and 3 shall be ductile iron. Sewer has been changed to D.I pipe, as requested. 3. Add note requiring contractor to confirm slope between MH's meets minimum required slope before continuing upstream. Slope has been revised to meet county minimum slope requirements. Note has been added, as requested. 4. Provide stationing for MH's 17 and 18. Stationing has been provided 5. Show water main crossing between MH's 6 and 8. If water main crosses below sanitary sewer, sewer pipe must be ductile iron and a minimum of 18- inches of vertical separation must be provided. Water crossing is provided and sewer has been changed to D.I. due to waterline crossing underneath the sanitary sewer 6. Show water main crossing between MH's 8 and 8. If water main crosses below sanitary sewer, sewer pipe must be ductile iron and a minimum of 18- inches of vertical separation must be provided. This run of sanitary sewer has been removed. 7. Show water main crossing downstream of MH 19. Water crossing is provided Sheet C-7L 1. Minimum allowable slope for sanitary sewer mains is 0.50%. Revise profiles accordingly. Sanitary sewer has been revised to the minimum slope of 0.50%. A 0.1 drop is being provided per discussion via phone call on 06/01/2022 2. Show water main crossing between MH's 13 and 14. This run of sewer has been removed. 3. Sewer between MH's 2 and 14 shall be ductile iron. This run of sewer has been removed. 4. Show water main crossing between MH's 12 and 13. This run of sewer has been removed. 5. Eliminate duplicate sewer profile between MH's 6 and 8. This also shows up on Sheet C-71K. Duplicate manholes have been removed from profile, as requested 6. Sewer between MH's 23 and 25 can likely be eliminated and replaced with private sewer laterals. This run of sewer has been removed. Sheet C-7M — Sheet has been removed and profiles relocated to Sheet 7L 1. Provide stationing for MH's. Stationing has been provided 2. Show water main crossing between MH's 22 and 26. This run of sewer has been removed 3. Sewer downstream of MH 22 shall be ductile iron. Sewer has been changed to D.I., as requested. If you have any questions concerning this review, feel free to call at (434) 977- 4511. Ext. 114. Sincerely, Jeremy M. Lynn Jeremy M. Lynn, RE Senior Civil Engineer JML:dmg 050601 NorthPointeSection2Ur030322