Project: SDP-2005-00111,Carriage Gate Apartments,Minor Amendment
Plan preparer: Mr. Timothy Miller,PE,Rivanna Engineering PLC (fax 434.984.8863)
Owner or rep.: Mr. Rich Carter, Carnage Gate,LLC (fax:434.296.3510)
Date received: 03 January 2006
Date of Comment: 02 February 2006
Reviewer: Mark Chambers
A.Final site plan comments:
1. We found the inlet computations for ST-3 are incorrect;however,a subsequent check shows the inlet is
within specs. Engineering recommends approval of the minor amendment.
File:E1_fsp_ADS_05-111 Carnage Gate Apartments
40F A
t&r: 1 I 1 I ki
gr
County of Albemarle.
Department of Community Development
Memorandum "WO y
To: Yadira Amarante
From: David Pennock, Principal Planner
Division: Zoning and Current Development
Date: November 18, 2005
Subject: SDP-2005-111: Carriage Gate Apartments—Minor Site Plan Amendment
The Albemarle County Division of Zoning and Community Development: Current Development Review has
reviewed the minor site plan amendment referenced above. Please address the following comments: [Each
comment is preceded by the applicable reference]
Site Plan Comments
1. [Sec. 32.7.9.5] Because of the change in grade in the proposed location of the tree re-located from str-2,
please provide a detail for a method of protection—i.e. a staking plan, tree well, or other device.
2. [4.12.19(b)] A concrete apron must be provided to extend at least 8 feet beyond the front of the
relocated dumpster.
Please contact David Pennock at 296-5832 ext. 3432 if you have any questions.
•
oof AL
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,Room 227
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
Project: SDP-2005-00111,Carriage Gate Apartments,Minor Amendment
Plan preparer: Mr.Timothy Miller,PE,Rivanna Engineering PLC(fax 434.984.8863)
Owner or rep.: Mr. Rich Carter,Carriage Gate,LLC (fax:434.296.3510)
Date received: 21 October 2005 (plan rev. date 15 October 2005)
Date of Comment: 09 November 2005
Engineer: Allan Schuck
The minor amendment to the final site plan for Carriage Gate Apartments,received on 25 October 2005,
has been reviewed. The engineering review for current development does not recommend approval until
the following items area adequately addressed:
A. Final site plan comments:
1. Inlet locations should be coordinated with the location of building entrances and pedestrian travel
paths to minimize inconvenience and nuisances to the public. [DM, 505G.5] The location of STR-
2A is a nuisance to the public with its location in front of the stairs. This inlet needs to be
relocated from this location so it is not a nuisance to the public. (Please refer to below picture.)
111C
•
2. The new concrete dumpster placed between Buildings 'B' and'C' is not built correctly. The
concrete pad shall extend beyond the front of each dumpster so that the front wheels of a truck
servicing the dumpster will rest on concrete, but in no case shall the length of a concrete pad be
less than eight(8)feet beyond the front of the dumpster. [18-4.12.19b] The existing pavement in
front of the dumpster is rutting. No concrete pad currently exists in front of the dumpster. The
dumpster itself is on a concrete pad,but that pad stops at the existing curb. Please show the
correct dumpster pad design for both dumpster locations on the amendment and fix the existing
problems at dumpster. (Please refer to below picture.)
e
f j _
..
•
•
Ego
.ri
3. Structure 2A is not built correctly. The site drainage does not flow into this structure as the
original design. Therefore, the drainage does not flow into the SWM facility. This inlet structure
needs to be relocated and rebuilt to capture the drainage and get the drainage to the SWM facility.
�-._ „ n fir
_ _
/1M
-111
Ise
TI . 7
4. The new design with the island and proposed contour and spot elevation grades does not allow the
drainage to flow into STR-4. Therefore,the drainage will not get to the SWM facility. Please
revise proposed drainage patterns shown on the minor amendment. [17-312C& 17-315A]
Concentrated flow will not be allowed to cross the traffic lanes of the site plan. It appears the
concentrated flows from this area will cross the travel lanes at several locations. It appears that an
additional drop inlet is needed along the western parking lot to address both of these concerns.
[18-32.5.6k]
5. The parking alignment shown on the minor amendment is not the same as in the field. The
handicap spaces are field located at Building `B'. The amendment shows the handicap spaces in
front of Building`C'.
6. CG-12 also exists in front of Building 'B' as well as Building `C'. Please show correctly on plans.
File:El_fsp_ADS_05-111 Carriage Gate Apartments