HomeMy WebLinkAboutWPO200400087 Calculations 2004-10-06 LONGACRE FARM
Albemarle County,Virginia
STORMWATER/BIO-FILTER CALCULATION NARRATIVE
October 6,2004
NP ENGINEERING
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
LONGACRE FARM SUBDIVISION
STORMWATER/BIO-FILTER CALCULATIONS
INTENT:
Perform calculations for the capacity of the bio-filter,size/design the stone weir at the bio-filter and the ditch
lining from the bio-filter to the existing stream.
HYDRAULICS:
Pre-Development
Given:Area is currently pasture(C=0.3)
Area Number C Area(ac) CA BS l,rrite--
� S(cPJ1� .E
1 0.300 3.700 1.110 N 1�"-'�", 1'`t _
Weighted Totals: 0.300 ,3e706 1)(24fOlt LE rtD t11J G tik/
0,33 Po s t.Tb1— `Ec�iA-t_
Time of concentration=5 min
Period Intensity Peak Flow ` 1 � v- vc- ' -r- M.c
(years) (in/hr) (cfs)
2 5.40 5.99 _
5 6.35 7.05 10 �✓�. Z '�
10 7.10 7.88
25 8.00 8.88 y re. 1,4.7
50 8.90 9.88
100 9.60 10.66
Post Development
Given: Total drainage area to bio-filter=3.7 ac
Total impervious area= 17,167.77 sf
Total impervious area draining to bio-filter=9,077.98 sf=0.21 ac.
Area Number C Area(ac) CA
1 0.300 0.210 0.063
2 0.900 3.490 3.141
Weighted Totals: 0.866 3.700 3.204
Time of concentration=5 min
Period Intensity Peak Flow
(years) (in/hr) (cfs)
2 5.40 17.30
5 6.35 20.35
10 7.10 22.75
25 8.00 25.63
50 8.90 28.52
100 9.60 30.76
NP ENGINEERING 1
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
DESIGN BIO-FILTER AND CHECK FOR CAPACITY
DESIGN INTENT:
Design the bio-filter capacity based on a surface area of 2.5%times the total impervious area.In addition,
check the volume of the No-filter to handle the first'/2 inch of runoff from impervious areas.
Total impervious area= 17,167.77 sf (see Drainage map)
Calculated surface area required for the bio-filter= 17,167.77 x.025=429.19 sf
Surface Area provided=475.8 sf
Total impervious area draining to bio-filter=9,077.98 sf (see Drainage map)
Required volume of bio-filter= 1/2"x 9,077.98 sf=378.25 cf= 14 cy
Depth of water in basin= 1'
Storage volume provided in bio-filter= 1'x 475.8 sf=478.5 cf= 17.72 cy > 14 cy(volume okay)
CONCLUSION:
The size of the bio-filter(@ 475.8 sf)satisfies the 2.5%rule for sizing and has sufficient capacity to handle the
first'/2 inch of runoff from the impervious area draining to the structure.
DESIGN OF STONE WEIR AT BIO-FILTER
DESIGN INTENT:
Design the stone weir to handle the 10-year post-development storm.
Per the above hydraulic calculations,size the stone weir to handle a minimum of 22.75 cfs.
DESIGN ASSUMPTIONS:
Weir is trapezoidal with the following characteristics:
Top Width=9'
Bottom Width=4.5'
Side Slope=2.25:1 (per VESCH Table 5-15—minimum side slope=2:1)
Depth= 1'
Cross Sectional Area=6.75 sq.ft.
Hydraulic Radius=0.7162
Manning's Coefficient(based on d50) =0.0352
Slope(assume 1%) _.01
Based on Mannings Equation and Continuity Equation,the capacity of this weir is 22.87 cfs,which is greater
than the 10-year storm requirement of 22.75 cfs.
CONCLUSION:
FINAL DESIGN:
Weir is trapezoidal with the following characteristics:
Top Width=9'
Bottom Width=4.5'
Side Slope=2.25:1
Depth= 1'
NP ENGINEERING 2
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
DESIGN OF THE DITCH LINING BELOW BIO-FILTER TO STREAM
DESIGN INTENT:
Design the ditch to convey 10-year peak storm and resist erosion from the 2 year peak storm velocity.
Per the above hydraulic calculations, T -
Qio=22.75 cfs
Q2= 17.30 cfs c t D. 3
Verify ditch can convey the 10-year peak storm:
V = U• is
Assume a V-ditch with the following characteristics:
6'top width
1'deep
3:1 side slopes(per VESCH Table 5-15—minimum side slope=3:1)
Grass lined(n=.05)with EC2
Slope of proposed ditch follows existing contours @ 0.23 ft/ft
Cross sectional Area=3.0 sf f .. 1S Hydraulic Radius=0.474 o,
Vdesign= 8.69 ft/sec " �o ' e-.4 3
/� Qd =AxV=3.0 x 8.69=26.07 cfs>Qio=22.75 cfs (Capacity okay)
/
eLSs Verify resistance to erosion for the 2-year peak velocity LZ= �• �G
1\s,j , Q2= 17.30 cfs
V
;s V2=Q2/A= 17.30/3.0=5.77 ft/sec therefore use EC-3 T (V ,,=4.0-7.0 ft/sec) Z ^ 7. t?
CONCLUSION: '1-1 C to s
FINAL DESIGN:
V-ditch with the following characteristics:
Top Width=6'
Depth= 1'
Side Slope=3:1
Grass Lined with EC-3 Tgp '
,ir-a• •
NP ENGINEERING 3
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
LONGACRE FARM
Albemarle County,Virginia
STORMWATER/BIO-FILTER CALCULATION NARRATIVE
October 6,2004
NP ENGINEERING
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
LONGACRE FARM SUBDIVISION
STORMWATER/BIO-FILTER CALCULATIONS
IN PENT:
Perform calculations for the capacity of the bio-filter,size/design the stone weir at the bio-filter and the ditch
lining from the bio-filter to the existing stream.
HYDRAULICS:
Pre-Development
Given:Area is currently pasture(C =0.3)
Area Number C Area(ac) CA
1 0.300 3.700 1.110 ✓
Weighted Totals: 0.300 3.700 1.110 /
Time of concentration=5 min
Period Intensity Peak Flow
(years) (in/hr) (cfs)
2 5.40 5.99.f
5 6.35 7.05 ✓
10 7.10 7.88
25 8.00 8.88
50 8.90 9.88
100 9.60 10.66 ✓
Post Development
Given: Total drainage area to bio-filter= 3.7 ac
Total impervious area= 17,167.77 sf
Total impervious area draining to bio-filter=9,077.98 sf=0.21 ac.
Area Number C Area(ac) CA
1 0.300 0.210 0.063 .(1) U0 c 0A i
2 0.900 3.490 3.141 . 3o 3,(11 : I, 0 I-
Weighted Totals; 0.866'' 3.700' 3.204 1 f' 33
Time of concentration= 5 min
Period Intensity Peak Flow
(years) (in/hr) (cfs)
2 5.40 17.30✓ G,G'�
5 6.35 20.35✓ 7,ct.r
10 7.10 22.75✓ 8.1
25 8.00 25.63 Y.8 q
50 8.90 28.52 1(.06
100 9.60 30.76✓' 'BI"
NP ENGINEERING 1
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
DESIGN BIO-FILTER AND CHECK FOR CAPACITY
DESIGN IN TENT:
Design the bio-filter capacity based on a surface area of 2.5%times the total impervious area.In addition,
check the volume of the bio-filter to handle the first'/z inch of runoff from impervious areas.
Total impervious area= 17,167.77 sf (see Drainage map)
Calculated surface area required for the bio-filter= 17,167.77 x.025=429.19 sf
Surface Area provided=475.8 sf
Total impervious area draining to bio-filter=9,077.98 sf (see Drainage map)
Required volume of bio-filter= 1"x 9,077.98 sf=378.25 cf= 14 cy
. {
Depth of water in basin= 1' 11.Gv1-61.
Storage volume provided in bio-filter= 1'x 475.8 sf=478.5 cf= 17.72 cy > 14 cy(volume okay)
CONCLUSION:
The size of the bio-filter(@ 475.8 sf)satisfies the 2.5%rule for sizing and has sufficient capacity to handle the
first 1/2 inch of runoff from the impervious area draining to the structure.
DESIGN OF STONE WEIR AT BIO-FILTER
DESIGN INTENT:
Design the stone weir to handle the 10-year post-development storm.
Per the above hydraulic calculations,size the stone weir to handle a minimum of 22.75 cfs.
DESIGN ASSUMPTIONS:
Weir is trapezoidal with the following characteristics:
Top Width=9'
Bottom Width=4.5'
Side Slope=2.25:1 (per VESCH Table 5-15—minimum side slope=2:1)
Depth= 1'
Cross Sectional Area=6.75 sq. ft.
Hydraulic Radius=0.7162
Manning's Coefficient(based on d50) =0.0352
Slope(assume 1%) = .01
Based on Mannings Equation and Continuity Equation,the capacity of this weir is 22.87 cfs,which is greater
than the 10-year storm requirement of 22.75 cfs.
CONCLUSION:
FINAL DESIGN:
Weir is trapezoidal with the following characteristics:
Top Width=9'
Bottom Width=4.5'
Side Slope=2.25:1
Depth= 1'
NP ENGINEERING 2
1850 BROWNS GAP TURNPIKE • CHARLOTTESVILLE, VA 22901
phone:434-823-1228•Fax:434-823-9746
DESIGN OF THE DITCH LINING BELOW BIO-FILTER TO STREAM
DESIGN IN 1'hNT:
Design the ditch to convey 10-year peak storm and resist erosion from the 2 year peak storm velocity.
Per the above hydraulic calculations,
Qio= 22.75 cfs
Q2= 17.30 cfs
Verify ditch can convey the 10-year peak storm:
Assume a V-ditch with the following characteristics:
6'top width
1'deep
3:1 side slopes(per VESCH Table 5-15—minimum side slope=3:1)
Grass lined(n=.05)with EC2
Slope of proposed ditch follows existing contours @ 0.23 ft/ft
Cross sectional Area=3.0 sf
Hydraulic Radius=0.474
Vdesig,= 8.69 ft/sec
Qdesign=AxV=3.0 x 8.69=26.07 cfs>Qio=22.75 cfs (Capacity okay)
Verify resistance to erosion for the 2-year peak velocity
Q2= 17.30 cfs
V2=Q2/A= 17.30/3.0=5.77 ft/sec therefore use EC-3 Type A Lining(Vmpv=4.0-7.0 ft/sec)
CONCLUSION:
FINAL DESIGN:
V-ditch with the following characteristics:
Top Width=6'
Depth= 1'
Side Slope=3:1
Grass Lined with EC-3 Type A
NP ENGINEERING 3