HomeMy WebLinkAboutSDP201400003 Correspondence 2014-01-14 Ellie Ray
From: Ellie Ray
Sent: Wednesday, May 28, 2014 9:53 AM
To: 'Craig Kotarski'
Subject: FW: Agnor Hurt
See below. You can submit signature sets at your convenience.
Thanks,
Ellie Carter Ray, PL4
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Alex Morrison [mailto:amorrisoraserviceauthority.orq]
Sent: Wednesday, May 28, 2014 8:10 AM
To: Ellie Ray
Subject: Agnor Hurt
Ellie,
I am working on the approval documentation for the above project. I do not anticipate any further revisions.You can
request signature sets from the applicant at this time, if you are only waiting on my review.Thank you.
Alexander J. Morrison, EIT
Civil Engineer
Albemarle County Service Authority
168 Spotnap Road
Charlottesville,Virginia 22911
(0)434-977-4511 Ext. 116
(F)434-979-0698
Like the ACSA on Facebook at www.facebook.com/acsaconnect
Ellie Ray
From: Ellie Ray
Sent: Tuesday, May 27, 2014 4:19 PM
To: 'Craig Kotarski'
Subject: RE: SDP-2014-00003 Agnor-Hurt Elementary School Major Amendment
Yes,four is correct.
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Craig Kotarski [mailto:Craig.Kotarskk timmons.com]
Sent: Tuesday, May 27, 2014 3:35 PM
To: Ellie Ray
Subject: RE: SDP-2014-00003 Agnor-Hurt Elementary School Major Amendment
Ellie,
I've asked Alex over at ACSA to send you something saying the drawings are good to go.
Once he does that how many copies do you need for signature? I want to say its 4, but thought I would double check.
Thanks.
Craig Kotarski, P.E., LEED AP
Project Manager
TIMMONS GROUP I www.timmons.com
919 2nd Street S.E. I Charlottesville, VA 22902
Office: 434.327.1688 I Fax: 434.295.8317
Mobile: 434.964.7148 I craig.kotarski@timmons.com
Your Vision Achieved Through Ours
To send me files greater than 20MB click here.
From: Ellie Ray [mailto:era Ealbemarle.or•]
Sent: Thursday, May 22, 2014 1:13 AM
To: Craig Kotarski
Subject: FW: SDP-2014-00003 Agnor-Hurt Eleme' ary School Major Amendment
Please find VDOT comments attached. •y :id he can review for these change on the signature copies. So, at this
point, we're waiting on ACSA and then sig re copies with Troy's requested changes can be submitted.
Thanks,
Ellie Carter Ray, P.A
Senior Planner
Albemarie County Communt
pr;: L w4.29:..5E32 x.
1
Ellie Ray
From: Ellie Ray
Sent: Thursday, May 22, 2014 11:13 AM
To: 'Craig Kotarski'
Subject: FW: SDP-2014-00003 Agnor-Hurt Elementary School Major Amendment
Attachments: SDP-2014-0003 Agnor-Hurt Elementary School Review Comments-5-21-14.pdf
Please find VDOT comments attached. Troy said he can review for these change on the signature copies. So, at this
point,we're waiting on ACSA and then signature copies with Troy's requested changes can be submitted.
Thanks,
Ellie Carter Ray,PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Austin, Nathran. (VDOT) [mailto:Nathran.Austin(a>vdot.virginia.gov]
Sent:Thursday, May 22, 2014 7:43 AM
To: Ellie Ray
Subject: SDP-2014-00003 Agnor-Hurt Elementary School Major Amendment
Troy Austin, P.E.
Area Land Use Engineer
Virginia Department of Transportation
Land Development—South
Culpeper District
P.O. Box 1017
Troy,VA 22974
Phone: (434) 589-5871
Fax: (434) 589-3967
Aso-
Ellie Ray
From: Ellie Ray
Sent: Wednesday, May 21, 2014 9:27 AM
To: 'Craig Kotarski'
Subject: RE: Agnor Hurt
Attachments: RE: Agnor Hurt
Craig,
See the attached email. I wouldn't submit copies for signature until you get tentative approvals from both ACSA and
VDOT.
Ellie Carter Ray,PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Craig Kotarski [mailto:Craig.KotarskiCa�timmons.com]
Sent:Tuesday, May 20, 2014 8:13 AM
To: Ellie Ray
Subject: Agnor Hurt
Ellie,
Are there any outstanding comments for Agnor Hurt(besides ACSA)? We'd like to get copies for signature into you all,
but I wanted to double check with you.
Best,
Craig
Craig Kotarski, P.E., LEED AP
Project Manager
TIMMONS GROUP I www.timmons.com
919 2nd Street S.E. I Charlottesville, VA 22902
Office: 434.327.1688 I Fax: 434.295.8317
Mobile: 434.964.7148 I craig.kotarski atimmons.com
Your Vision Achieved Through Ours
To send me files greater than 20MB click here.
Ellie Ray
From: Ellie Ray
Sent: Thursday, May 15, 2014 2:48 PM
To: 'Craig Kotarski'
Subject: RE: Agnor Hurt
Craig,
I have completed my review of the revisions and my previous comments have been addressed. We are still awaiting
approval from ACSA and VDOT. The WPO plan will need final approval as well before the site plan can be signed. Once
all approvals are in place,you will need to submit four copies(including all `slip in' sheet(s) noted below)for signature.
When the signature copies are submitted, Intake processes them and sends an email to all reviewing agencies notifying
them that the plans are ready for signature and giving them 10 business days in come in and sign the plans. Once the
plans are signed, I will notify you that one signed plan is ready to be picked up (two go to zoning and one stays in the
file). I'll pass along anything I receive from ACSA or VDOT as soon as I receive it.
Thanks,
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Craig Kotarski [mailto:Craig.Kotarskatimmons.com]
Sent: Monday, May 12 14 10:04 AM
To: Ellie Ray
Subject: Agnor Hurt
Ellie,
I am checking in with regards to Agnor Hurt to see if you have any questions or additional comments? I also have a
message in to Troy at VDOT and Frank who is covering the engineering. Alex has sent me some minor items from ACSA
that he said we could slip sheet in.
Thanks for your help on this.
Best,
Craig
Craig Kotarski, P.E., LEED AP
Project Manager
TIMMONS GROUP I www.timmon .com
919 2nd Street S.E. I Charlottesvill , VA 22902
Office: 434.327.1688 I Fax: 434.295.8317
Mobile: 434.964.7148 I craig.kotarski @timmons.com
Your Vision Achieved Through Our
To send me files greater than 20MB click e .
Ellie Ray
From: Ellie Ray
Sent: Monday, May 12, 2014 10:11 AM
To: 'Craig Kotarski'
Subject: RE: Agnor Hurt
My internal due date is the 19th...I am totally swamped, so I hope to be able to get to it by then, but it will just depend
on how things go. Once my review is complete, I'll let you know.
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Craig Kotarski [mailto:Craig.Kotarskatimmons.com]
Sent: Monday, May 12, 2014 10:04 AM
To: Ellie Ray
Subject: Agnor Hurt
Ellie,
I am checking in with regards to Agnor Hurt to see if you have any questions or additional comments? I also have a
message in to Troy at VDOT and Frank who is covering the engineering. Alex has sent me some minor items from ACSA
that he said we could slip sheet in.
Thanks for your help on this.
Best,
Craig
Craig Kotarski, P.E., LEED AP
Project Manager
TIMMONS GROUP I www.timmons.com
919 2nd Street S.E. I Charlottesville, VA 22902
Office: 434.327.1688 I Fax: 434.295.8317
Mobile: 434.964.7148 I craig.kotarski(ciltimmons.com
Your Vision Achieved Through Ours
To send me files greater than 20MB click here.
1
• . %
TIMMONS GROUP
YOUR VISION ACHIEVED THROUGH OURS.
April 28, 2014
Ellie Carter Ray
Senior Planner
County of Albemarle Community Development
401 McIntire Road
North Wing
Charlottesville,Va. 22902-4596
RE: SDP201400003 Agnor-Hurt Elementary School-Major Amendment- Comment
Response Letter
Dear Ms. Ray: N
0
m
N -
We have reviewed all of your comments from April 9th, 2014 and made the necessary revisions. a 23
Please find our responses to the individual comments below:
N
y M
Application Information:
I) (32.5.2(a)] This property is zoned R-6 and, therefore, technically doesn't have parking
setbacks;please remove this information from the "site data". Additionally, this property has v
two fronts;one on Berkmar and one on Woodburn. Because there are two fronts, all of the W
other property lines are sides (fronts and backs don't intersect). Please show the setbacks on
the layout plan and label them correctly. -no m
Setbacks have been revised.
Revl: Comment addressed. °'
2) [32.5.2(a)] Provide the names of the owners, zoning district, tax map and parcel number, and
o
present uses of all abutting parcels. E
Information has been provided. E
Rev I: Comment addressed.
3) [32.5.2(b)] List the number of parking spaces removed and the number proposed. Verify the
total number of spaces provided; "site data"indicates 118, but the landscape plan states 128.
The total number of pre and post spaces have been verified and listed on Sheet -
C 1.0. 118 parking spaces are provided. The landscape plan has been revised.
Rev.1: Comment addressed.
v
4) (32.5.2(d)]A critical slope waiver was requested to disturb 0.55 acres of man-made slopes in
excess of 25%. However, a Zoning Text Amendment (ZTA) is currently underway that, if
il
approved, would designate the slopes on this property as "managed". The ZTA, as proposed,
a.
would allow for the disturbance of"managed"critical slopes for many permitted uses as long as
certain design standards are met, and would make this waiver unnecessary. The ZTA will be o
y
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
Iviwo April 30,2014
Page 2 of 8
heard by the Board of Supervisors on Wednesday March 56. If the ZTA is not approved, the
waiver request will be processed while revisions to the site plan are underway.
The slopes are now considered "managed" and have been noted as such on the
plan.
Rev. 1: Comment addressed.
5) (32.5.2M Provide the pavement width for Woodburn Road.
Width has been provided on Sheet C2.0.
Rev. 1: Comment addressed.
6) (32.5.2(l)] Provide the pavement width for both entrances and their associated accessways.
Widths have been provided. See Sheet CO.I and Sheet C4.0.
Rev. I: Comment addressed.
7) (32.5.2(j,k,l)] Verify that the location(s) of all existing or proposed utilities and utility
easements including water, sewer, drainage, telephone, cable, electric and gas are shown on the
plan.
Locations have been verified.
Rev. I: Comment addressed.
8) (32.5.2(m)]Show the distance to the centerline of the nearest existing street intersection from
the proposed ingress and egress locations.
Distance has been shown for existing and proposed entrance see Sheet CO.I.
Rev. 1: Comment addressed.
9) (32.6.2(e)5] Provide a legend showing all symbols and abbreviations used on the plan.
A legend has been provided on Sheet C I.I.
Rev. 1: Comment addressed.
10) (32.6.2(g)]All water and sewer facilities to be dedicated to public use and the easements for
those facilities and shall be identified by a statement that the facilities are to be dedicated to
the Albemarle County Service Authority.
The waterline easement has been identified.
Rev. I: Comment addressed.
I I) (32.6.2(i)]Dimension all travelways.
Travelways have been dimensioned see Sheet C4.0.
Rev. 1: Comment addressed.
12) (32.6.2(i)]Show the location of any loading space(s) and provide dimensions.
The entrance to the loading dock on the east side of the building will serve as a
loading space.
Rev. 1: Comment addressed.
I 3) (32.6.2(i)] Provide the location of any signs.
Signs locations have been provided on Sheet C4.1.
Rev. I: Comment addressed.
14) (.32.6.2(i)] Indicate the type of surfacing for all paved or gravel areas.
Surfacing type has been indicated with hatches on Sheet C4.0 that match details
on Sheet C I.I.
R\1 03\3443 I-Agnor_Hurt\Docs\2-Design\Letters
N„t„. ,orse April 30,2014
Page 3 of 8
Rev. I: Comment addressed. However, the hatching patterns used to designate
different surfacing types are very hard to distinguish on the copies submitted for
review.
The hatching has been updated.
5) 132.6.2(i)] Label the angle of any non-perpendicular parking spaces.
The angle of non-perpendicular spaces has been labeled.The only non-
perpendicular spaces are the bus parking spaces and the angle of these has been
labeled.
Rev. 1: Comment addressed.
16) (32.6.2(i) &4.12.15 (f)] Each end of the 10 parking space row on the eastern side of the
parking lot should be protected by raised traffic islands instead of painted stripes.
Raised curb islands have been added.
Rev. I: Comment addressed.
17) (32.6.2(j)&32.7.9.4(b)]Existing trees maybe preserved in lieu of planting new plant materials
in order to satisfy the landscaping and screening requirements of section 32.7.9 or to meet
conditions of approval, subject to the agent's approval. It appears that some of the Landscape
Plan should show the trees to be preserved, the limits of clearing, the location and type of
protective fencing,grade changes requiring tree wells or walls, and trenching or tunneling
proposed beyond the limits of clearing. In addition, the applicant shall sign a conservation
checklist approved by the agent to insure that the specified trees will be protected during
construction. Except as otherwise expressly approved by the agent in a particular case,such
checklist shall conform to specifications contained in the Virginia Erosion and Sediment Control
Handbook, pp/II-284 through 111-297, and as hereafter amended. This checklist must be
signed, dated, and added to the landscape plan sheet.
The landscape plan (L I.0) has been updated to show the trees to be preserved,
the limits of clearing,the location and type of protective fencing, grade changes
requiring tree wells or walls, and trenching or tunneling proposed beyond the
limits of clearing. The `Conservation Checklist' has been added to the landscape
notes and details Sheet (L2.0).
Rev. I: Comment not fully addressed. The majority of the required tree canopy
is provided through preservation of existing trees along the perimeter of the
property. The tree protection measures for these trees are only shown on the
Sheet C3.I, not the landscape plan. Frequently E&S plans are pulled from the
site plan set at the request of Engineering; make sure Sheet C3.I remains with
the site plan set or add an additional landscape sheet showing tree protection for
all trees remaining on the site. Additionally, the conservation checklist must be
completed, signed and dated.
Sheet L I.0 includes reference to Sheet C3.2 for Tree Protection Layout and
Sheet C3.0 for Tree Protection Detail. The Conservation Checklist has been
completed and signed.
18) (32.6.2(j)&32.7.9.6(b)] The 5%landscaped area required shall be planted with a mixture of
shade trees and shrubs and shall include one (I) large or medium shade tree per ten (10)
parking spaces or portion thereof if five (5) spaces or more. As noted above, clarify how many
total parking spaces are proposed. Additionally, it appears that one Betula nigra is proposed
within a striped paved area;please revise.
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
.,,,,o April 30,2014
Page 4 of 8
118 parking spaces are proposed. The requirements chart on L I.0 has been
updated to reflect the 5% landscape area for 118 parking spaces. The Betula
nigra within the paved area has been relocated.
Rev. 1: Comment not fully addressed. The parking lot tree note indicates that
11.8 (12)trees are required, and only I 0 are provided. However, the Landscape
Plan shows many more trees than 10 are proposed. Revise the note to indicate
that at least the minimum required number is provided. Please also revise the
size of the proposed trees to indicate the minimum caliper instead of height. The
minimum requirement for parking lot trees is 1 1/2" — 13/4" caliper.
The proposed trees tabulation has been updated accordingly. All tree sizes have
been adjusted to I '/z"— 13/4" caliper.
19) 132.6.2(j)&32.7.9.8] The tree canopy requirement for this site is 10%;please provide
information to verify that this requirement is being met. If existing trees are to be used to
satisfy this requirement, provide the information requested above regarding preserving existing
trees in lieu of planting new plant material. Please also provide the tree canopy information for
all proposed plantings.
The landscape plan (L 1.0) has been updated to show the trees to be preserved,
the limits of clearing,the location and type of protective fencing,grade changes
requiring tree wells or walls,and trenching or tunneling proposed beyond the
limits of clearing. The `Conservation Checklist' has been added to the landscape
notes and details Sheet (L2.0). The plant schedule on L 1.0 has been updated to
provide the tree canopy information for all proposed plantings.
Rev. 1: Comment not fully addressed. See comment#I7 above. Additionally,
use numbers from the County's "Approved Plant Canopy Calculations" to
indicate the canopy provided by the proposed plantings.
(http://www.albemarle.org/upload/images/forms center/departments/Community
Development/forms/applications/Approved Plant Canopy Calculations 02-05-
03.pdf)
The tree canopy requirement tabulation has been updated accordingly.
20) (32.6.2(k)&4.17]Is any outdoor lighting proposed> If so, all lighting(including building
mounted fixtures) must be shown on a lighting plan that includes a photometric plan, luminaire
schedule and cut sheets for each proposed fixture.
A lighting plan has been included.
Rev. I: Comment not fully addressed; a lighting plan has now been added to the
application, see lighting comments below.
Acknowledged.
21) (Comment] This amendment cannot be approved until VDOT completes their review and grants
their approval;comments will be forwarded upon receipt. Engineering, Fire/Rescue,ACSA,
inspections, and E9 I I comments have been provided.
Acknowledged.
Rev. 1: Comment addressed. This amendment cannot be approved until VDOT,
Engineering, Fire/Rescue, and ACSA complete their review and grant their
approval; comments will be forwarded upon receipt.
The VDOT, Engineering,and ACSA comments have been received and
addressed.
R:\103\3443 I-Agngnor_Hurt\Docs\2-Design\Letters
*.r' ..+ April 30,2014
Page 5 of 8
22) (32.6.2(k)&4.17]Show the proposed lighting locations on the layout and landscape sheets to
verify that no site conflicts exist.
The proposed lighting is now shown on Sheet C4.0 and L 1.0.
23) [32.6.2(k) &4.17]Lighting spillover exceeds 0.5 footcandle along the Woodburn Road right-of-
way, and possibly along the northern property line in one small area;revise the lighting to
reduce the spillover to 0.5 footcandle or less (4.17.4(b)I).
Moved poles to reduce spillover to less than 0.5 FC along Woodburn Road.
24) (32.6.2(k) &4.17]Albemarle County requires that the LLF(maintenance factor)be 1.0;revise
the photometric plan to use the proper LLF.
Revised calculations with LLF set to 1.0.
25) (32.6.2(k) &4.17]Provide the following standard lighting note on the lighting plan: Each
outdoor luminaire equipped with a lamp that emits 3,000 or more initial lumens shall be a full
cutoff luminaire and shall be arranged or shielded to reflect light away from adjoining residential
districts and away from adjacent roads. The spillover of lighting from luminaires onto public
roads and property in residential or rural areas zoning districts shall not exceed one-half
footcandle.
Added note as indicated to plans.
WPO Plan Review(Frank Pohl):
I) Sheets C3.I and C3.2—Adjust CWD off f o f paved court and onto grassed area.
The clean water diversion has been moved off the paved court.
2) Sheets C3.I and C3.2-Adjust CWD on the north side of the parcel so that the clean water is
not routed to the sediment basin.
The clean water diversion has been updated to ensure that clean water is not
being routed through the sediment basin.
3) Sheets C3.1 and C3.2—Add fabric to uphill side of slope drain.
Fabric has been added to the uphill side of the slope drain.
4) Sheets C3.I and C5.I —Verify that riprap outlet at STR 400 was sized correctly(velocity).
The riprap outlet is sized correctly.
5) Sheet C3.2—Add inlet protection to inlet located in small parking lot on north side of building.
Inlet protection has been added to STR 108.
6) Sheet C6.1 — "pre"should be "post"at bottom of upper pond drainage area table.
"Pre" has been changed to"Post".
7) Sheet C6.2-Forgot to mention this one, and it is minor, but in scheduled, "Rim Length"should
be "Rim Elev".
Rim length has been updated to Rim Elev.
8) Sheet C6.3—Add pipe 213 crossing to STR 116-Bayfilter#2 profile.
The profile has been updated.
9) Sheet C7.0—Minor but extend arrows.
The arrows have been extended.
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
Nifty, No, April 30,2014
Page 6 of 8
Stormwater Management (Glenn Brooks):
I) I could not find verification of water quality treatment for the new entrance and bus loop area.
Water quality treatment information is provided on Sheet C6.1.
2) Better explanation needs to be provided for the area/volume curve used in the routings. It
appears as though the modeling for the stone field voids and the arches may be counting some
portion of storage areas double, which erroneously helps results.
Design has been changed.
3) I did not find anything regarding MS-19, and we know this is a problem area with the channel
and grate inlet next to Berkmar.
Design has been changed. Flow and volume into channel will not be increased.
Additional flow and volume has been redirected to existing ponds.
4) The storage chamber system is not recommended for a county maintained infrastructure.
Plastic chambers under a heavily loaded bus loop may have structural problems in the long term.
The system is very difficult to inspect and clean out, and as proposed, has no reasonable access.
It is recommended that a surface pond, or reinforced concrete storage chamber system be
considered, and not placed directly under the bus route.
Storage chamber has been removed and stormwater design has been changed.
Review Comments (Max Greene):
I) Curb and gutter should be added to the parking area that drains across the proposed fill over
the existing swale on the North side of the site.
Curb and gutter have been added.
2) Sight distance details (C7.0) should be clearly labeled as new entrance onto Woodburn Road.
Site distance profile labels have been updated.
3) VDOT approval is required for new entrance onto Woodburn Road.
Acknowledged.
Fire and Rescue (Robbie Gilmer):
I) 20 foot lane designed for student drop-off and pick-up needs to have signs "No Parking/
Student Drop-off and Pick-up Only".
Signs have been added. See Sheet C4.I.
2) The inside Radii on the drive lane designed for student drop-off and pick-up needs to be no less
than 25 ft.
Radii has been revised to 25'.
3) Bus parking lot needs to have the area near the building marked as "Fire Lane No Parking".
Fire lane marking has been added. See Sheet C4.I.
R:\103\3443 I-Agnor_H urt\Docs\2-Design\Letters
w .ome April 30,2014
Page 7 of 8
ACSA (Alex Morrison):
General Notes:
I) Add ACSA Water and Sewer General Conditions.
The ACSA Water and Sewer General Conditions are shown on Sheet C I.2.
Sheet 4.0:
I) Show existing 6"water main from the existing meter to the fire hydrant assembly at the end of
the water main (the water main that extends to the North between "Play Are W/Equipment"
and"(3) Frame Sheds."
The existing main is now shown.
2) Call out existing water main as "6"DIP."
The existing main is now called out as 6" DIP.
3) Update connection to 6"x 6"tapping sleeve and valve, followed by a 90 degree bend(see
sketch I on Sheet 4.0).
The tie in to the existing line has been updated per sketch I.
4) Call out cut and cap after tapping sleeve and valve (see sketch I on Sheet 4.0).
The existing line is now shown as being cut and capped.
5) Add gate valve on fire line to end ACSA ownership (see sketch 2 on Sheet 4.0).
The gate valve has been added.
6) Update water meter service line configuration,per sketch 2 on Sheet 4.0.
The water meter service line configuration has been updated per sketch 2.
7) Add additional proposed ACSA water easement near the proposed water meter, as shown.
The easement has been updated.
8) Call out all bends, fittings,gate valves, etc.
All water structures have now been called out.
9) Add sequence of construction to Sheet 4.0 (see below).
The sequence of construction has been added to Sheet C4.0. However,the final
step in the sequence has been updated to say"Remove existing water main
which is now out of service". It is necessary to remove the line as opposed to
abandoning it in place because the line runs under the proposed building
footprint.
Sheet L 1.0:
1) Show proposed FHA.
The FHA is now shown on Sheet L I.0.
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
Niere — April 30,2014
Page 8 of 8
VDOT(Troy Austin):
I) The sight line and sight distance to the right should be shown on the plan view.
The Site lines/distances to the right,and left are now shown on Sheet CO.I.
2) The entrance detail provided is for a Private Subdivision Road Entrance. The entrance should be
designed based on the Commercial Entrance Design Along Highways with Shoulders standard as
found in Appendix F of the Road Design Manual.
The detail has been updated; it's shown on Sheet C I.2.
We have attached (10)full size of the revised plans and (2)copies of the calculations,and
narratives for your review. If you have any questions or comments, please feel free to give me
a call at 434.327.1688.
Sincerely,
CAockA41 /j1/4.........0.
Craig Kotarski, PE
Project Manager
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
Ellie Ray
From: Ellie Ray
Sent: Thursday, April 17, 2014 10:59 AM
To: 'Craig Kotarski'; Montle Breeden; 'MKavanaugh @shwgroup.com'
Cc: Max Greene
Subject: RE: AGNOR-HURT Addtns& Renovs: Site Plan Approval and Impact on Issuance of Building
Permit
Just wanted to mention that engineering comments are still in the works. There shouldn't be any major issues, but
you'll want to get their comments before you resubmit.
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Craig Kotarski [mailto:Craig.Kotarski @timmons.com]
Sent:Thursday, April 17, 2014 9:05 AM
To: Montie Breeden; 'MKavanaugh @shwgroup.com'
Cc: Ellie Ray
Subject: RE: AGNOR-HURT Addtns &Renovs: Site Plan Approval and Impact on Issuance of Building Permit
Montle,
We've received comments from or discussed the outstanding reviews with everyone at this point. There is nothing that
I see that should cause any trouble. We should have all review responses by tomorrow and will have everything turned
back to the County by the end of the following week. I would anticipate approval will come from that submission,which
would allow 6+weeks before mid June for plans to be signed and such for subsequent permit issuance.
Craig Kotarski, P.E., LEED AP
Project Manager
TIMMONS GROUP I www.timmons.com
919 2nd Street S.E. I Charlottesville, VA 22902
Office: 434.327.1688 I Fax: 434.295.8317
Mobile: 434.964.7148 I craig.kotarski@timmons.com
Your Vision Achieved Through Ours
To send me files greater than 20MB click here.
From: Montie Breeden [mailto:mbreeden2@albemarle.orq]
Sent: Thursday, April 17, 2014 8:56 AM
To: 'MKavanaugh @shwgroup.com'; Craig Kotarski
Cc: Ellie Ray
Subject: RE: AGNOR-HURT Addtns &Renovs: Site Plan Approval and Impact on Issuance of Building Permit
Matthew/Craig:
In case you didn't know, I cannot secure a building permit until the site plan submission is fully accepted by all reviewing
agencies and COMMUNITY DEVELOPMENT has designated the project "aro-oved".
This will be an l5SJE. ius: before the mid-JUN timeframe when the G,. rh,or. untie, contract by;here will make
application.
1
'..ro r r
Given the nature of the remaining VDOT issues (site line/site distance&entrance detail as per Commercial Entrance
guidelines) and the ACSA issue (water line), it is unclear how long this will delay their final acceptances.
As I'm sure you know, any additional revisions to the drawings will have to be included in the review sets (to ensure they
are accurate). I've copied Ellie (our plan reviewer/ coordinator with COMMUNITY DEVELOPMENT) so perhaps she can
offer insight on the logistics of updating the current copies of the submittal.
I realize resolution is currently underway and my hope is that final site plan approval can be garnered sometime in the
coming week(s);well before the time we seek the building permit.
Please let me know is you think this will be a problem.
Thanks,
Montie
From: Montie Breeden
Sent: Wednesday, April 16, 2014 5:07 PM
To: Alex Morrison
Cc: 'MKavanaugh @shwgroup.com'; 'Craig Kotarski'; Frank Pohl
Subject: RE: AGNOR-HURT Addtns &Renovs: Site Plan Review by ACSA
Alex:
Thanks for the update!
I just received word from the A/E that they are looking into changes to the water line work(to area "C" ) so that if would
afford the least disruption to service. Craig should be following up with you on that(as I don't yet know all the particular
details).
Montie
From: Alex Morrison [mailto:amorrison@serviceauthority.orq]
Sent: Wednesday, April 16, 2014 4:43 PM
To: Montie Breeden
Subject: RE: AGNOR-HURT Addtns &Renovs: Site Plan Review by ACSA
Montie,
The plans are currently under construction review.This is a separate process from the county. Once the plans are
approved for construction and approval e-mail is sent to the county for CountyView. I let Craig know earlier that I have
the plans scheduled for final review at our plan review meeting on Friday. Once the meeting is over I will distribute
comments.
I did ask Craig to follow up on one question I had which will affect the sequence of construction. How long can the
school be without water? If a cut and tie in is used then the school would be without water for 3+days. If this is
unacceptable there is an alternative sequence that would put the school out of water for only a few hours. Please
advise.
Thanks.
Alexander J. Morrison, Eli
2
Civil Engineer
New ,gwe
Albemarle County Service Authority
168 Spotnap Road
Charlottesville,Virginia 22911
(0)434-977-4511 Ext. 116
(F)434-979-0698
From: Montie Breeden [mailto:mbreeden2@ albemarle.orq]
Sent: Wednesday, April 16, 2014 3:15 PM
To: Alex Morrison
Subject: AGNOR-HURT Addtns &Renovs: Site Plan Review by ACSA
Alex:
Sorry for the belated follow-up but several weeks ago I dropped off site plan (re-submittal)drawings for the AGNOR-
HURT project at your office on Pantops.
Usually Ellie Ray, in COMMUNITY DEVELOPMENT, coordinates dispersal of the review documents and I offered to help
her out since the department is short-staffed.
I'm just checking in to see where you, or your colleagues, stand on your re-review -- I consulted CountyView but could
only find limited information on the current review application (likely due to my lack of experience successfully logging
onto the database).
Thanks in advance for your reply!
Montie
Montie R. Breeden,AIA
Senior Project Manager
Office of Facilities Development
County of Albemarle
401 McIntire Road, Room 228
Charlottesville,Virginia 22902-4596
T (434)872-4501 ext. 9 3423
F (434) 972-4091
C (434) 566-6014
mbreeden2 @albemarle.org
3
wow .,,.,,,,
Ellie Ray
From: Ellie Ray
Sent: Tuesday, April 15, 2014 3:48 PM
To: 'Craig Kotarski'
Subject: SDP-2014-0003 Agnor-Hurt Elementary School
Fire rescue has also provided comments on the latest revision...they have no objection.
Still waiting on Engineering and ACSA.
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
Planning Division
401 McIntire Road, North Wing
Charlottesville,Virginia 22902
ph: 434.296.5832 x. 3432
fax: 434.972.4126
1
Ellie Ray
From: Ellie Ray
Sent: Wednesday, April 09, 2014 5:43 PM
To: 'Craig Kotarski'
Subject: SDP201400003 Agnor-Hurt Elementary- Major Amendment
Attachments: CDP2_sdp_ECR_Agnor-Hurt Elementary.pdf
Craig,
Please find attached my comments for revisions to the above referenced application. I will send along the other
reviewer comments as soon as I receive them.
Thank you,
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
Planning Division
401 McIntire Road, North Wing
Charlottesville,Virginia 22902
ph: 434.296.5832 x. 3432
fax: 434.972.4126
1
• . ,
TIMMONS GROUP
YOUR VISION ACHIEVED THROUGH OURS
March 27, 2014
Ellie Carter Ray
Senior Planner
County of Albemarle Community Development
401 McIntire Road
North Wing
Charlottesville,Va. 22902-4596
RE: SDP201400003 Agnor-Hurt Elementary School—Major Amendment - Comment
Response Letter
Dear Ms. Ray: ,,,
0
N -
We have reviewed all of your comments from March 4th, 2014 and made the necessary revisions. Q co
Please find our responses to the individual comments below: tea,-
N o
en
N M
Application Information: o
I) (32.5.2(a)] This property is zoned R-6 and, therefore, technically doesn't have parking
setbacks;please remove this information from the "site data". Additionally, this property has U v
two fronts;one on Berkmar and one on Woodburn. Because there are two fronts, all of the N
other property lines are sides (fronts and backs don't intersect). Please show the setbacks on c;; o
the layout plan and label them correctly. N ei
Setbacks have been revised. o`
2) (32.5.2(a)]Provide the names of the owners,zoning district, tax map and parcel number, and o
present uses of all abutting parcels.
Information has been provided. o
a
•3) (32.5.2(b)] List the number of parking spaces removed and the number proposed. Verify the v 3
X
total number of spaces provided; "site data"indicates 118, but the landscape plan states 128.
The total number of pre and post spaces have been verified and listed on Sheet
C 1.0. 118 parking spaces are provided. The landscape plan has been revised.
4) 132.5.2(d)]A critical slope waiver was requested to disturb 0.55 acres of man-made slopes in
excess of 25%. However, a Zoning Text Amendment (ZTA) is currently underway that, if
approved, would designate the slopes on this property as "managed". The ZTA, as proposed,
would allow for the disturbance of"managed"critical slopes for many permitted uses as long as
certain design standards are met, and would make this waiver unnecessary. The ZTA will be
heard by the Board of Supervisors on Wednesday March 5`h. If the ZTA is not approved, the
waiver request will be processed while revisions to the site plan are underway.
The slopes are now considered "managed" and have been noted as such on the
plan.
R:\103\3443 I-AgnorHurt\Docs\2-Design\Letters
March 27,2014
Page 2 of 6
5) [32.5.2(I)]Provide the pavement width for Woodburn Road.
Width has been provided on Sheet C2.0.
6) (32.5.2(1)]Provide the pavement width for both entrances and their associated accessways.
Widths have been provided. See Sheet CO.1 and Sheet C4.0.
7) (32.5.2(bk,l)] Verify that the location(s) of all existing or proposed utilities and utility
easements including water, sewer, drainage, telephone, cable, electric and gas are shown on the
plan.
Locations have been verified.
8) (32.5.2(m)]Show the distance to the centerline of the nearest existing street intersection from
the proposed ingress and egress locations.
Distance has been shown for existing and proposed entrance see Sheet CO.I.
9) (32.6.2(e)5]Provide a legend showing all symbols and abbreviations used on the plan.
A legend has been provided on Sheet C 1.1.
10) 132.6.2(g)]All water and sewer facilities to be dedicated to public use and the easements for
those facilities and shall be identified by a statement that the facilities are to be dedicated to
the Albemarle County Service Authority.
The waterline easement has been identified.
1 1) 132.6.2(i)] Dimension all travelways.
Travelways have been dimensioned see Sheet C4.0.
12) (32.6.2(i)]Show the location of any loading space(s) and provide dimensions.
The entrance to the loading dock on the east side of the building will serve as a
loading space.
I 3) 132.6.2(i)]Provide the location of any signs.
Signs locations have been provided on Sheet C4.I.
14) [32.6.2(i)] Indicate the type of surfacing for all paved or gravel areas.
Surfacing type has been indicated with hatches on Sheet C4.0 that match details
on Sheet Cl.I.
15) (32.6.2(i)]Label the angle of any non-perpendicular parking spaces.
The angle of non-perpendicular spaces has been labeled.The only non-
perpendicular spaces are the bus parking spaces and the angle of these has been
labeled.
16) 132.6.2(i) &4.12.15 (f)]Each end of the 10 parking space row on the eastern side of the
parking lot should be protected by raised traffic islands instead of painted stripes.
Raised curb islands have been added.
17) (32.6.2(j)&32.7.9.4(b)] Existing trees may be preserved in lieu of planting new plant materials
in order to satisfy the landscaping and screening requirements of section 32.7.9 or to meet
conditions of approval, subject to the agent's approval. It appears that some of the Landscape
Plan should show the trees to be preserved, the limits of clearing, the location and type of
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
A■■,w .ose March 27,2014
•• Page 3 of 6
protective fencing,grade changes requiring tree wells or walls, and trenching or tunneling
proposed beyond the limits of clearing. In addition, the applicant shall sign a conservation
checklist approved by the agent to insure that the specified trees will be protected during
construction. Except as otherwise expressly approved by the agent in a particular case, such
checklist shall conform to specifications contained in the Virginia Erosion and Sediment Control
Handbook, pp 111-284 through 111-297, and as hereafter amended. This checklist must be
signed, dated, and added to the landscape plan sheet.
The landscape plan (L1.0)has been updated to show the trees to be preserved,
the limits of clearing,the location and type of protective fencing,grade changes
requiring tree wells or walls,and trenching or tunneling proposed beyond the
limits of clearing. The 'Conservation Checklist' has been added to the landscape
notes and details Sheet (L2.0).
18) 132.6.26)&32.7.9.6(b)] The 5%landscaped area required shall be planted with a mixture of
shade trees and shrubs and shall include one (I) large or medium shade tree per ten (10)
parking spaces or portion thereof if five (5) spaces or more. As noted above, clarify how many
total parking spaces are proposed. Additionally, it appears that one Betula nigra is proposed
within a striped paved area;please revise.
118 parking spaces are proposed. The requirements chart on L I.0 has been
updated to reflect the 5% landscape area for 118 parking spaces. The Betula
nigra within the paved area has been relocated.
19) (32.6.2(j)&32.7.9.8] The tree canopy requirement for this site is 10%;please provide
information to verify that this requirement is being met. If existing trees are to be used to
satisfy this requirement, provide the information requested above regarding preserving existing
trees in lieu of planting new plant material. Please also provide the tree canopy information for
all proposed plantings.
The landscape plan (L I.0) has been updated to show the trees to be preserved,
the limits of clearing,the location and type of protective fencing, grade changes
requiring tree wells or walls,and trenching or tunneling proposed beyond the
limits of clearing. The 'Conservation Checklist' has been added to the landscape
notes and details Sheet (L2.0). The plant schedule on L I.0 has been updated to
provide the tree canopy information for all proposed plantings.
20) (32.6.2(k)&4.17] Is any outdoor lighting proposed> If so, all lighting(including building
mounted fixtures) must be shown on a lighting plan that includes a photometric plan, luminaire
schedule and cut sheets for each proposed fixture.
A lighting plan has been included.
21) [Comment] This amendment cannot be approved until VDOT completes their review and grants
their approval;comments will be forwarded upon receipt. Engineering, Fire/Rescue,ACSA,
inspections, and E911 comments have been provided.
Acknowledged.
WPO Plan Review(Max Greene & Frank Pohl):
I) Please submit a request for a modified inlet protection for the files.
Request has been submitted.
2) Please state on the plans the date of topography. If topo is more than I year old, then please
note on plan that topo was visually field verified by Engineer and date of verification.
Date has been stated on Sheet C1.0.
R:\103\3443 I-Agnor_H urt\Docs\2-Design\Letters
„,,oe March 27,2014
Page 4 of 6
3) Please locate at least I bench mark on the plans that will be utilized throughout the duration of
the site work.
A benchmark has been added see Sheet C2.0.
4) Inlet protection shown is for toe of slope installation due to lack of emergency overflow and can
cause erosion problems when installed in other location. Please show inlet protections suited for
each application.
Inlet details have been coordinated see Sheet C3.0.
5) Please place a note next to the sediment trap "Sediment control structure removals shall be
approved in writing from WPO inspector.”
Note has been added see Sheet C3.I.
6) Cleanwater diversion appears to dump a large area of drainage into back of building with no
outlet. Please explain how stormwater is to be handled at the outlet of the Cleanwater
Diversion.
Design has been revised see Sheet C3.I.
7) Cleanwater diversion near Woodburn Road is within the proposed grading and will need to be
moved back if water is to remain clean.
Grading has been revised.
8) Cleanwater diversion will require a lining to prevent erosion of the berm.
Lining has been added.
9) Cleanwater diversion across critical slope will require a lot of grading to install. Please show
grading required to install Cleanwater diversion in conformance with Std. &Spec 3.17—
Stormwater conveyance Channel.
Clean water diversions have been relocated to avoid critical slopes.
10) Please clarify drainage path from sediment basin and detention facility.
Drainage area is shown with a dashed line and divisions see Sheet C3.I.
I I) Inlet protection along Woodburn Road appears too shallow and may cause the stormwater to
overflow down the slope into the Cleanwater diversion. Please show detail of how this will be
constructed.
A detail for culvert inlet protection has been added see Sheet C3.0.
12) Mountable berm appears to be draining in the wrong direction.
The angle of the berm has been adjusted to ensure positive drainage.
13) Several inlet protections maybe exceeding the I acre drainage area limit. Please show
corresponding drainage areas for each sediment control structure including roof drains. (Inlets
draining to sediment basin with overland relief flows into basin are exempt from I acre rule.)
All existing and proposed roof drains are routed underground. Inlet protection
drainage areas have been shown see Sheet C3.I and C3.2.
14) Please show inlet protection on the existing inlet in the parking lot on the South side of the site.
This may not be required unless the WPO inspector requires it.
R:\103\3443 I-Agnor_Hurt\Docs\2-Design\Letters
"Now .,Noe March 27,2014
• Page 5 of 6
Inlet protection has been added.
15) Please show curb and gutter along I I space parking area to reduce erosion on new slope.
Curb and gutter has been added.
16) Diversion into basin from building does not appear to be a stable proposal and could blow-out in
a storm event. Please clarify the construction and stability of the diversion across the existing
swale area. Please consider extending basin over existing swale.
Design has been revised see Sheet C3.I.
17) Please show Albemarle County detail for temporary paved construction entrance on the plans.
Detail has been added see Sheet C3.0.
Stormwater Management (Glenn Brooks):
I) I could not find verification of water quality treatment for the new entrance and bus loop area.
Water quality treatment information is provided on Sheet C6.I.
2) Better explanation needs to be provided for the area/volume curve used in the routings. It
appears as though the modeling for the stone field voids and the arches may be counting some
portion of storage areas double, which erroneously helps results.
Design has been changed.
3) I did not find anything regarding MS-19, and we know this is a problem area with the channel
and grate inlet next to Berkmar.
Design has been changed. Flow and volume into channel will not be increased.
Additional flow and volume has been redirected to existing ponds.
4) The storage chamber system is not recommended for a county maintained infrastructure.
Plastic chambers under a heavily loaded bus loop may have structural problems in the long term.
The system is very difficult to inspect and clean out, and as proposed, has no reasonable access.
It is recommended that a surface pond, or reinforced concrete storage chamber system be
considered, and not placed directly under the bus route.
Storage chamber has been removed and stormwater design has been changed.
Review Comments (Max Greene):
I) Curb and gutter should be added to the parking area that drains across the proposed fill over
the existing swale on the North side of the site.
Curb and gutter have been added.
2) Sight distance details (C7.0) should be clearly labeled as new entrance onto Woodburn Road.
Site distance profile labels have been updated.
3) VDOT approval is required for new entrance onto Woodburn Road.
Acknowledged.
Fire and Rescue (Robbie Gilmer):
I) 20 foot lane designed for student drop-off and pick-up needs to have signs "No Parking/
Student Drop-off and Pick-up Only".
Signs have been added. See Sheet C4.I.
R:\103\3443 I-AgnorHurt\Docs\2-Design\Letters
%Pe ,O,: March 27,2014
Page 6 of 6
2) The inside Radii on the drive lane designed for student drop-offand f'and pick-up needs to be no less
than 25 ft.
Radii has been revised to 25'.
3) Bus parking lot needs to have the area near the building marked as "Fire Lane No Parking".
Fire lane marking has been added. See Sheet C4.I.
ACSA (Alex Morrison):
I) Need 3 copies of the construction plan submitted to Jeremy Lynn, PE.
Acknowledged.
2) Need water data sheet submitted to Jeremy Lynn, PE.
Acknowledged.
3) Need existing building fixture counts submitted to Jeremy Lynn, PE.
Acknowledged.
4) Need Proposed additional fixture counts submitted to Jeremy Lynn, PE.
Acknowledged.
VDOT(Troy Austin):
1) The proposed entrance onto Woodburn Road will need to be designed and constructed in
accordance with VDOT commercial entrance standards. The appropriate detail should be
added to the plans and the entrance should be dimensioned accordingly.
Entrance has been revised to comply with VDOT commercial entrance standards
and detail has been added. See Sheet C1.2.
2) The sight distance shown on the plans for the proposed entrance onto Woodburn Road does not
meet the minimum sight distance requirements. This entrance cannot be approved unless it
meets the minimum requirements.
Design has been revised and the 390' site distance requirement is now met. See
Sheet C7.0.
We have attached (8)full size of the revised plans and (2) copies of the calculations, and
narratives for your review. If you have any questions or comments, please feel free to give me
a call at 434.327.1688.
Sincerely,
/ •
Craig Kotarski, PE
Project Manager
R:\103\3443 I-ggnorHurt\Docs\2-Design\Letters
Ellie Ray
From: Montle Breeden
Sent: Wednesday, March 19, 2014 4:02 PM
To: Ellie Ray
Subject: RE: AGNOR-HURT Addnts & Renovs: Site Plan Review(initial and re-submission)
Ellie:
Thanks!
I learned this morning TIMMONS is trying to make re-submittal by next WED(26th) -- I'm trying to get the school
division to finalize some design decisions to ensure our A/E can make that date.
Montle
From: Ellie Ray
Sent: Wednesday, March 19, 2014 9:38 AM
To: Montie Breeden
Cc: 'Craig Kotarski'; Rosalyn Schmitt; MWaguespack @shwgroup.com
Subject: RE: AGNOR-HURT Addnts &Renovs: Site Plan Review (initial and re-submission)
This all sounds good to me. I will try my best to remember to let you know once the revision copies are submitted.
You've probably seen this, but here is the map showing managed and preserved slopes for this area:
http://www.albemarle.org/upload/images/forms center/departments/Community Development/forms/critical slopes
/critical slopes preserved managed N1 2.pdf
Ellie Carter Ray, PLA
Senior Planner
Albemarle County Community Development
ph: 434.296.5832 x. 3432
From: Montie Breeden
Sent: Tuesday, March 18, 2014 4:47 PM
To: Ellie Ray
Cc: 'Craig Kotarski'; Rosalyn Schmitt; MWaguespack @shwgroup.com
Subject: AGNOR-HURT Addnts &Renovs: Site Plan Review (initial and re-submission)
Ellie:
I am writing to:
1. inform you of the pending re-submission of the site plan (that addresses the initial round of review comments) --
perhaps Craig can provide us with an anticipated date; and
2.to ask that you immediately alert me when that re-submission lands on your desk as I would like to offer to walk the
other copies to VDOT, Fire Marshal;,ACSA, etc. as we need to complete the re-review as quickly as possible.
I am in the process of securing copies of the critical slope maps,that indicate areas of managed slopes,and forwarding
them to the civil engineer so that they can be indicated on the site plan (because we anticipate final approval around the
time frame this information must be documented on the plans).
1
Let me know if this is acceptable. '`war °'r"
Thank You!
Montie
Montie R. Breeden,AIA
Senior Project Manager
Office of Facilities Development
County of Albemarle
401 McIntire Road, Room 228
Charlottesville,Virginia 22902-4596
T (434)872-4501 ext.9 3423
F (434) 972-4091
C (434) 566-6014
mbreeden2Palbemarle.org