HomeMy WebLinkAboutWPO201400065 Correspondence 2014-08-04John Anderson
From: Chris Mulligan [CMulligan @roudabush.com]
Sent: Tuesday, October 07, 2014 11:17 AM
To: John Anderson
Subject: RE: OLA
Attachments: 1 YEAR PRE Summary.pdf; HydroCAD Summary.pdf; OLA- swm.pdf;
VRRM_ReDev Compliance Spreadsheet—v2.8-2013-3 infil.xlsm
John,
See attached support and let me know if this will work for you.
Also attached is the full size representation of the documentation for the plan set.
121 clltme AaMoaff
914 Monticello Road
Charlottesville, Virginia 22902
(804 ) 437 -2788 (cell)
From: John Anderson [ mailto :landerson2 @albemarle.org]
Sent: Monday, October 06, 2014 5:11 PM
To: Chris Mulligan
Cc: Glenn Brooks
Subject: RE: OLA
Chris,
9VAC25- 870 -66 reference 24 -hr storm events, and 9VAC25- 870 -72 states TR -55 should be used for analysis, that a VSMP
authority may allow the Modified Rational Method, but ACCD does not allow it. I hope it's possible to piece together an
analysis using TR -55, since we do not accept MRM. We'll talk tomorrow - thanks for your time and help today.
From: Chris Mulligan [ mailto:CMulligan @roudabush.com]
Sent: Monday, October 06, 2014 3:59 PM
To: John Anderson
Subject: OLA
The other issue appears to be the use of the SCS method for such small areas.
The use of the modified rational method is much more appropriate for smaller drainage areas( <20 acres). This is also
outlined in the manual.
I am going to look at it more from this approach to see if it is in fact more realistic, and will get back with you.
C9iwis /L%a /oaf
914 Monticello Road
Charlottesville, Virginia 22902
(804) 437 -2788 (cell)
Digs, Inc. PROPOSAL
P.O. Box 31
II Charlottesville,VA 22902 Page: 1 of 5
(434)978-4435-office
(434)978-3703-fax Date: 3-5-14
Rev.: 6-17-14
Rev.: 7-25-14
Proposal Submitted To: Work To Be Performed At
Abrahamse&Company OLA Chapel Addition
l.
Categories Quantity Unit Cost Quote
■
Mobilization 1 LS $2,750.00 $2,750.00
Layout 1 LS $3,500.00 $3,500.00
Clearing 1 LS $600.00 $600.00
Demo/Disposal 1 LS $2,440.00 $2,440.00
Construction Entrance 1 LS $2,700.00 $2,700.00
Silt Fence 1 LS $2,460.00 $2,460.00
Diversion Dike 1 LS $700.00 $700.00
Inlet Protection . 1 LS $600.00 $600.00
Sediment Trap 1 LS $4,365.00 $4,365.00 k
Strip/Replace Topsoil 1 LS $7,500.00 $7,500.00
Gut/Fill/Import 1 LS $94,990.00 $94,990.00
(, Grading 1 LS $4,045.00 $4,045.00
--Patoidation-Bran- 1 LS --$81-85+:96
--$878561.08---Storm Sewer
1
ill
LS $14,150.00 $14,150.00
Infiltration Pits 1 LS $6,050.00 $6,050.00
CG-2 1 LS $2,205.00 $2,205.00
Sidewalk 1 LS $4,480.00 $4,480.00
Steps with Cheek Wall 3E-- 1 LS $20,635.00 7 - $20,635.00
Fire Lane Stone 1 LS $2,975.00 $2,975.00
Subtotal $185,995.00
All material is guaranteed to be as specified,and the above work to be performed in accordance with the drawings and specifications submitted for above
work and completed in a substantial workmanlike manner for the sum of Dollars($ 185,995.00)with payments to be made as
follows: Net 10 Days.1.5%fmo after 30 days.In addition,the undersigned agrees to pay DIGS,Inc.all costs of collection including attorneys fees.
This proposal may be withdrawn from us if not accepted within 15 days.
Any alteration or deviation from above specifications involving extra costs,wilt be executed only upon written orders,and will become an extra charge over
and above the estimate.All agreements contingent upon strikes,accidents,or delays beyond our control.Owner to carry tire,tornado,and other necessary 1
insurance upon above work.Workmen's Compensation and Public Liability Insurance on above work taken out by DIGS,Inc.
1
s
Respectfully Submitted: Brook R.Wood �f
Per: Digs,Inc.
1
Acceptance of Proposal
The above prices,specifications and conditions are satisfactory and are hereby accepted.
{ You are authorized to do the work as specified. Payment will be made as outlined above,
Please sign acceptance of proposal and return one copy.
li
It
Date: Signature:
il
R
Ij
Digs, Inc, PROPOSAL
P.O. Box 31
Charlottesville,VA 22902
Page: 2 of 5
(434)978-4435-office
(434)978-3703-fax Date: 3-5-14
Rev.: 6-17-14
Rev.: 7-25-14
Proposal Submitted To: Work To Be Performed At:
Abrahamse&Company OLA Chapel Addition
Categories Quantity Unit Cost Quote
Subtotal $185,995.00
Paving/Roadway Stone 1 LS $27,300.00 $27,300.00
Paint Striping/Wheel Stops 1 LS $1,650.00 $1,650.00
Temporary Seeding 1 LS $2,600.00 $2,600.00
Project Management 1 LS $8,705.00 $8,705.00
TOTAL $226,250.00
A 2. 17 `few
GpI
All material is guaranteed to be as specified,and the above work to be performed in accordance with the drawings and specifications submitted for above
work and completed in a substantial workmanlike manner for the sum of Dollars($ 185,995.00)with payments to be made as
follows: Net 10 Days.1.5%fmo after 30 days.In addition,the undersigned agrees to pay DIGS,Inc.all costs of collection including attorneys fees.
This proposal may be withdrawn from us if not accepted within 15 days.
Any alteration or deviation from above specifications involving extra costs,will be executed only upon written orders,and will become an extra charge over
and above the estimate.All agreements contingent upon strikes,accidents,or decays beyond our control.Owner to carry fire,tornado,and other necessary
insurance upon above work,Workmen's Compensation and Public Liability Insurance on above work taken out by DIGS,inc.
Respectfully Submitted: Brook R.Wood
Per: Digs,Inc.
Acceptance of Proposal
The above prices,specifications and conditions are satisfactory and are hereby accepted.
You are authorized to do the work as specified. Payment will be made as outlined above.
Please sign acceptance of proposal and return one copy:
Date: Signature:
•
Nese
John Anderson
From: Chris Mulligan [CMulligan @roudabush.com]
Sent: Tuesday, October 07, 2014 12:10 PM
To: John Anderson
Subject: FW: OLA
Attachments: Our Lady of AngeIs332.pdf
I'd forgotten to attach the soil infiltration tests done by Steve Gooch.
e4eif/+f
914 Monticello Road
Charlottesville,Virginia 22902
(804) 437-2788(cell)
From:John Anderson [mailto:ianderson2Ctalbemarle.org]
Sent:Tuesday, October 07, 2014 11:18 AM
To:Chris Mulligan
Subject: RE: OLA
Thanks, Chris
From: Chris Mulligan [mailto:CMulligan(aroudabush.com]
Sent: Tuesday, October 07, 2014 11:17 AM
To: John Anderson
Subject: RE: OLA
John,
See attached support and let me know if this will work for you.
Also attached is the full size representation of the documentation for the plan set.
c, e,(fa f
914 Monticello Road
Charlottesville, Virginia 22902
(804) 437-2788 (cell)
From:John Anderson [mailto:ianderson2@albemarle.org]
Sent: Monday, October 06, 2014 5:11 PM
To:Chris Mulligan
Cc:Glenn Brooks
Subject: RE: OLA
Chris,
9VAC25-870-66 reference 24-hr storm events, and 9VAC25-870-72 states TR-55 should be used for analysis,that a VSMP
authority may allow the Modified Rational Method, but ACCD does not allow it. I hope it's possible to piece together an
analysis using TR-55, since we do not accept MRM. We'll talk tomorrow-thanks for your time and help today.
From: Chris Mulligan [mailto:CMullig @roudabush.com]
Sent: Monday, October 06, 2014 3:59 PM
To: John Anderson
Subject: OLA
The other issue appears to be the use of the SCS method for such small areas.
The use of the modified rational method is much more appropriate for smaller drainage areas(<20 acres). This is also
outlined in the manual.
I am going to look at it more from this approach to see if it is in fact more realistic,and will get back with you.
ask.
/f4
914 Monticello Road
Charlottesville, Virginia 22902
(804)437-2788 (cell)
2
( 1 97!{020€
FAX(4 34)2 6-S22O
UUDABUSH,GALE&ASSOC.,INC aa INPf OWABUSI"I,COM
A PRO,'ESS;c ,%.4J.-CORPO'1V
" 9t4 NIONTACELLOItCAO
CHARLor-esv!LLE.VIRGINIA 22902
August 20, 2014
Mr. Glenn Brooks, P.E.
County Engineer
Albemarle County
RE: Our Lady of the Angels Monastery
Dear Mr. Brooks,
Thank you for your prompt review and response to the VSMP application for Our Lady of
the Angels Monastery. I have reviewed your comments and offer the following.
I have attached a copy of the check submitted by Shank and Gray with the submittal
package for the Site Plan and WPO Plan. It is Check No. 6006 for$1350. I believe the
reference number you included in your comment was from Old Trail.
I have attached two copies of the WPO/Erosion and Sediment Control Plans for your
review.
Stormwater management is being provided within the redevelopment area. One method of
stormwater management used on this project is infiltration pits, which are shown on Sheet
4 of the Site Plan and detailed on Sheet 4 of the WPO Plan. The other technique used is
sheet flow to open space. We are aware of DEQ's requirements of utilizing open spaces as
a stormwater management treatment area. A long-term management plan and necessary
legal covenants will be prepared and submitted prior to Site Plan/WPO Plan approval.
A site specific Pollution Prevention and Spill Prevention Plan has been prepared that
identifies the locations of fueling areas, wash out areas and sanitation facilities. I am
attaching two copies for your review.
The SWPP/PPP document has been updated to more accurately reflect site conditions and
construction activities for the project. The Pollution Prevention Certification has be signed
and included with this resubmittal package.
I believe the attached information and noted revisions satisfy your comments. Please do
not hesitate to contact me if you have any questions or comments.
Regards,
Chris Mulligan
SDP 201400035 Our Lady of the Angels Monastery
Response to Max Green's Comments
1) WPO Plans,Application and Fee are required for disturbances over 10,000 square feet
The WPO Plans include the Erosion and Sediment Control Plan and the Stormwater Management
Plan.
• Erosion Control Plan
o Construction Entrance
o Silt Fence
o Diversion Dike
o Tree Protection
o Sediment Trap (which will be converted after construction is finished to a Biofilter)
• Stormwater Management Plan
o Utilized VaRRM spreadsheet to determine requirements
o Infiltration pits provided
2) Limits of Disturbance do not appear to encompass all proposed work.
Limits of disturbance line adjusted... and included in the erosion and sediment control plan.
3) Date and Source of topographic information:All topography should be at least visually field
verified by the designer within the last year[18-32.6.6, 14-302, Policy for date] Noted.
4) The proposed work is on Parcel 0200-00-00-040A1. Noted.
5) Retaining wall labeled with a maximum height(Walls require building permits according to
Building Official policy). Cheek walls are proposed to protect steps. <3'
6) Safety railing shown for retaining walls over 4' high(building permit may be more strict) [Policy]
Cheek walls are proposed only to protect dirt from steps.
7) Guardrail with VDOT designations shown for retaining walls next to parking or travelways [18-
32.7.2]
The plan is to raise and resurface an existing graveled entrance. The slopes are being reduced to
less than 16%, and the access shall be paved. A small-flat-shoulder has been introduced along the
entrance, but guardrail is not planned.
8) Show Critical Slopes on plan.
There are no critical slopes within the Steep Slopes Overlay District (created by the BOS on March 5,
2014). The steep slopes from the as-built topography onsite are shaded as stabilization areas on the
Erosion Control Plans.
9) Access Road appears to exceed 10%slope requirements for access aisles [18-4.12.17]
We request a waiver to this standard to allow a maximum grade of 15%. See letter under separate
cover. Per 4.12.17 "The county engineer may increase the maximum grade, upon a finding that no
reasonable design alternative would reduce or alleviate the need and that the increase in grade
would be in the best interest of public health, safety and welfare.The developer must request the
waiver in writing and provide all information necessary to justify that no reasonable design
alternative exists."