HomeMy WebLinkAboutSDP201300005 Review Comments 2013-01-22 (3) Ellie Ray
From: Michelle Roberge
Sent: Tuesday, May 07, 2013 10:23 AM
To: Ellie Ray
Subject: Planning Application Review for SDP201300005 Hollymead Substation-Minor.
The Review for the following application has been completed:
Application Number=SDP201300005
Reviewer= Michelle Roberge
Review Status = No Objection
Completed Date =05/07/2013
1
',.r
�.�pFAAL�k
!till lll�1111197'
!Ole'
IRGINZP
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,North Wing
Charlottesville,Virginia 22902-4596
Phone(434) 296-5832 Fax(434) 972-4126
February 14, 2013
Charlene Harper, P.E., LEED AP
Geosyntec Consultants
2727 Enterprise Parkway, Suite 103
Richmond,VA 23294
RE: SDP201300005 Hollymead Substation—Minor Amendment
Dear Charlene:
Your minor amendment has been reviewed. In order for the minor amendment to be approved the
following revisions are required:
1. [32.5.2(a)] Provide the name of the owner on the Cover Sheet. Please also add R-15 to the
Zoning note, a portion of this parcel is zoned R-1 and a portion is zoned R-15.
2. [32.5.2(a)] Please verify the accuracy of the boundary lines. The lines shown (within proximity of
the proposed work)appear much closer than those shown in GIS.
3. [32.5.2(a)] Provide the source of survey and topography.
4. [32.5.2(d)] Show areas of the site where existing slopes are critical slopes.
5. [4.2.6(c)] The Agent has determined that this use is exempt from the building site requirements
of section 4.2.2. The applicable exemption section reads as follows, "A lot, structure, or
improvement may be exempt from the requirements of section 4.2 as provided herein:
...(c)Accessways, public utility lines and appurtenances, storm water management facilities, and
any other public facilities necessary to allow the use of the parcel shall not be required to be
located within a building site and shall not be subject to the requirements of this section 4.2.2,
provided that the applicant demonstrates that no reasonable alternative location or alignment
exists. The county engineer shall require that protective and restorative measures be installed
and maintained as deemed necessary to insure that the development will be consistent with the
intent of section 4.2 of this chapter." Engineering comment#1 may be disregarded, but the
reviewing engineer can require additional protective or restorative measures as noted above.
6. [32.6.1(a)] Site Plans, and any amendments to a plan, must be prepared, sealed, signed and
dated by an architect, professional engineer, land surveyor, or certified landscape architect, each
of whom shall be licensed to practice in the Commonwealth of Virginia. Please seal, sign and
date each page of the plan set.
7. [32.6.2(j)] The landscape plan sheet should show any proposed tree removal.
8. [32.6.2(j) &32.7.9.4(b)] Existing trees may be preserved in lieu of planting new plant materials in
order to satisfy the landscaping and screening requirements of section 32.7.9. The landscape
plan should show the trees to be preserved, the limits of clearing,the location and type of
protective fencing, ,rrde changes requiring tree wells or walls, aritTerenching or tunneling
proposed beyond the limits of clearing. The applicant shall sign a conservation checklist
approved by the agent to ensure that the specified trees will be protected during construction.
Except as otherwise expressly approved by the agent in a particular case, the checklist shall
conform to the specifications in the Virginia Erosion and Sediment Control Handbook, pages III-
393 through III-413, and as hereafter amended. This checklist should be scanned and added to
the Landscape Plan Sheet.
9. [32.6.2(j) &32.7.9.7] Screening that meets the requirements of 32.7.9.7(d) is required (minimum
20' depth). It appears that existing vegetation meets this requirement; please verify. If this is
correct,the addition of the above-noted conservation plan and checklist will satisfy this comment.
10. [32.6.2(j) &32.7.9.8] Tree canopy that meets the requirements of 32.7.9.8(a)(1) is required
(minimum 10% of parcel). It appears that existing vegetation meets this requirement; please
verify. If this is correct,the addition of the above-noted conservation plan and checklist will
satisfy this comment.
11. [32.6.2(k) &4.17] Please clarify if any new outdoor lighting is proposed. If new fixtures are
proposed, a lighting plan must be submitted that meets the requirements of section 4.17.
12. [Comment] This site plan amendment cannot be approved until VDOT completes their review
and grants their approval; comments will be forwarded upon receipt. Zoning, Fire/Rescue,
inspections, and ACSA have completed their reviews and each has no objection. Engineering
comments have been provided.
Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The
Code is kept up to date by the County Attorney's office. The Code may found on the County Attorney's
website which may be found under"Departments and Services"at Albemarle.org.
In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit
a revised final site plan to address all of the requirements within six (6) months after the date of this letter
the application shall be deemed to have been voluntarily withdrawn by the developer.
If you have any questions about the comments please feel free to contact me.
Sincerely,
&th_ 6. 26uo
Ellie Carter Ray, CLA
Senior Planner
Planning Division
At,y45.
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,Room 227
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
Project: Hollymead Substation Expansion-Minor Amendment to SDP-1984-60
Plan preparer: Geosyntec Consultants [fax 804-767-2182]
Owner or rep.: Virginia Electric&Power CO
Plan received date: 22 Jan 2013
Date of comments: 11 Feb 2013
Reviewer: Michelle Roberge
A. Site Development Plan(SDP201300005)
1. It appears there is one critical slope located south of site that will be be slightly disturbed during
the construction of the additional gravel area. It also appears that the runoff for the entire site will
be routed into a stormsewer with the outflow concentrated near the critical slope area. The
applicant requesting the waiver shall file a written request explaining how the waiver, if granted,
would address the rapid and/or large-scale movement of soil and rock, excessive stormwater run-
off, siltation of natural and man-made bodies of water, loss of aesthetic resources, and, in the event
of septic system failure,a greater travel distance of septic effluent(collectively referred to as the
"public health, safety, and welfare factors")that might otherwise result from the disturbance of
critical slopes. [Section 4.2.5]
2. Please show the drainage easements within the property boundary.
3. The property drains into a lake managed by the Forest Lakes Community. Per Section 17.314 and
section 17.315,water quality and quantity will need to be addressed. A WPO application can be
filled out for the stormwater management and erosion and sediment control review. The load
reduction calculation spreadsheet can be found on our website,
www.albemarle.org/deptforms.asp?department=cdd. The file name is Plan Review BMP Removal
Rate Computations.
4. Please show the the VDOT Flared End Section ES-I for the outlet pipe.
5. The area between the proposed grate inlets will start ponding.Please revise to prevent ponding.
6. Please provide the detail of the 1' wide wall located south of site.
7. On sheets 5 and 9 for post development,please do not show the grate inlet and pipe to be
removed.
8. Please revise E2 to be a 24"RCP outlet pipe.
9. The site will eventually drain into(2)— 12"DIP before entering the pond. Please replace pipes
with a 24"RCP. This will require permission from the Forest Lakes Community Association, Inc.
Please provide.
Sincerely,
tor
I,
I
Michelle Roberge
County Engineer
Review Comments
Project Name: Hollymead Substation - Minor Minor Amendment
Date Completed: Friday, January 25, 2013
Reviewer: Jay Schlothauer
Department/Division/Agency: Inspections
Reviews
Comments:
Review Status: No Objection
Review Comments
Project Name: Hollymead Substation - Minor Minor Amendment
Date Completed: Monday, February 04, 2013
Reviewer: Robbie Gilmer
Department/Division/Agency: Fire Rescue
Reviews
Comments:
Based on SDP 1/22/13
No Objection or comments
Review Status: No Objection
Review Comments
Project Name: Hollymead Substation -Minor Minor Amendment
Date Completed: Thursday, February 07, 2013
Reviewer: Alexander Morrison
Department/Division/Agency: ACSA
Reviews
Comments:
Review Status: No Objection