I have reviewed your recent submittal for the above - referenced project dated February 4, 2008. Outstanding
issues that will need to be further addressed are shown in italics after the original comment from the Action
Letter of July 20, 2007.
The details provided on July 2, 2007 of the outdoor picnic pavilion are acceptable with materials and
colors as stated, with the possible addition of a stone knee wall to match the lower level of the main
building.
If a stone knee wall is intended, revise Sheet 3 Layout and Dimension Plan by adding the note "The
outdoor pavilion will have a stone knee wall matching the lower level of the main building. "
2. Revise the building design in the south (rear) and west (left side) elevations (Sheet EL -1) to eliminate the
appearance of blankness at the second story level using either window arrangement as presented on July 2,
2007 or vertical and horizontal banding as discussed and referenced in the drawing.
Replace the vertical HardiPlank boards, shown dividing the expanse of siding in the upper section of the
South (rear)and West (side) elevations, with a vertical board/molding as wide as the porch cornice line in
the East Elevation is tall. Revise the elevations to show the fascia trim boards wider. The vertical width
(height) of the fascia board should equal half the height of the porch cornice in the east elevation.
3. Revise the building design of the west (left side) elevation (Sheet EL -1), so that the hardiplank siding does
not rest directly on the top of the first story windows. With building materials and design, provide a
transition between the first and second floor levels of the elevation. This redesign should also provide a
more balanced sense of scale and proportion between the hardiplank at the second story level and the
building design above and below.
Revise the West (side) elevation by making the sill band (apron) above the stone wider. The band should
be at least half as high as the porch cornice in the east elevation.
4. Revise the site plan and building elevations to provide the location and method of screening for HVAC
and other equipment, indicating how visibility of the equipment will be eliminated from the EC.
Sheet Ex -1 shows 6 HVAC units in a 2:1 embankment adjacent to the south elevation. The height of these
units in relation to the adjacent retaining wall cannot be determined with the information provided. Two
HVAC units are shown adjacent to the northwest corner of the building. The method of screening for these
units is not shown.
5. Revise Sheet 4 Grading and Utilities Plan and Sheet 5 Landscape and Lighting Plan to show cut and fill
slopes that are rounded (minimum 10' radius) to meet existing conditions.
Revise Sheet 4 Grading and Utilities Plan and Sheet 5 Landscape and Lighting Plan to show cut and fill
slopes that are rounded (minimum 10' radius) to meet existing conditions.
6. Revise Sheet 3 Layout and Dimension Plan, Sheet 4 Grading and Utilities Plan, and Sheet 5 Landscape
and Lighting Plan and provide an erosion and sediment control plan clearly indicating proposed and
existing tree lines (labeled), the limits of construction, the location and method of tree protection fencing
for each tree /tree mass at the outermost limits of the canopy. Include a note on the landscape, grading and
erosion control plans stating the following: The movement of heavy equipment and the storage of all
materials outside the limits of construction are prohibited. No tree removal or grading will occur within
the 75 foot setback adjacent to the Route 250 E. EC.
Revise Sheet 3 Layout and Dimension Plan, Sheet 4 Grading and Utilities Plan, and Sheet 5 Landscape
and Lighting Plan and provide an erosion and sediment control plan clearly indicating proposed and
existing tree lines (labeled), the limits of construction, the location and method of tree protection fencing
for each tree /tree mass at the outermost limits of the canopy. Include a note on the landscape, grading and
erosion control plans stating the following: The movement of heavy equipment and the storage of all
materials outside the limits of construction are prohibited. No tree removal or grading will occur within
the 75 foot setback adjacent to the Route 250 E. EC.
7. Revise Sheet 5 Landscape and Lighting Plan to show 2'/2" caliper trees, 40' on center, of a species
common to the area, based on the County's Recommended Species List, along the eastern perimeter of the
proposed parking lot.
Revise the Plant List on Sheet 5 Landscape Plan to indicate that all medium to large shade trees fulfilling
this requirement are to be 2' /z inch caliper minimum.
8. Provide a lighting photometric plan showing all foot candle values across the site. Values at a right -of -way
line or boundary line adjoining a rural area district shall not exceed the one -half (1/2) foot candle
threshold. Provide alternate pole light fixtures that meet full cutoff requirements. Revise Sheet 5
Landscape and Lighting Plan to indicate the proposed finish, color and location of the Lumascape 461 -2
fixture. Provide information indicating the number of lumens that are emitted by this fixture. If 3,000
lumens or more, provide a full cutoff fixture. Revise the maintenance factor (LLF) in the luminaire
schedule to 1.0. Indicate whether or not decorative lighting is proposed. If it is, show how it addresses all
EC guidelines.
Revise the Lighting Photometric plan to include proposed exterior building lighting. Revise the Luminaire
Schedule to indicate the proposed finish and color of all fixtures. Revise the lighting maintenance factor
(LLF) to 1.0. Indicate whether or not decorative lighting is proposed. If it is, show how it addresses all EC
guidelines.
Please provide:
1. Two copies of revised drawings addressing the aforementioned comment.
2. A memo indicating specifically how the condition has been satisfied. If changes other than those
requested have been made, specifically identify those changes in the memo, also. Clear, specific, and
accurate information will facilitate the review of your submittal.
3. The attached "Revised Application Submittal" form. This form must be returned with your revisions
to ensure proper tracking and distribution.
When staff s review of this information indicates that all conditions of approval have been met, a Certificate of
Appropriateness may be issued. If you have any questions, please do not hesitate to contact me.
Sincerely,
Brent W. Nelson
Landscape Planner
cc: ARB File
COUNTY OF ALBEMARLE
Department of Community Development
REVISED APPLICATION SUBMITTAL
This form must be returned with your revisions to ensure proper tracking and distribution. County staff
has indicated below what they think will be required as a resubmission of revisions. If you need to submit
additional information please explain on this form for the benefit of the intake staff. All plans must be
collated and folded to fit into legal size files, in order to be accepted for submittal.
TO: Brent W. Nelson DATE:
PROJECT NAME: ARB2007 -0044: First Christian Church
Submittal Type Requiring Revisions ( ) indicates submittal Code
County Project Number
# Copies
Erosion & Sediment Control Plan (E &S)
# Copies
Distribute To:
Mitigation Plan (MP)
2
Brent Nelson
Waiver Request (WR)
Stormwater Management Plan (SWMP)
Road Plan (RP)
Private Road Request, with private/ public comparison (PRR)
Private Road Request — Development Area (PRR -DA)
Preliminary Site Plan (PSP)
Final Site Plan (or amendment) (FSP)
Final Plat (FP)
Preliminary Plat (PP)
Easement Plat (EP)
Boundary Adjustment Plat (BAP)
Rezoning Plan (REZ)
Special Use Permit Concept Plan (SP -CP)
Reduced Concept Plan (R -CP)
Proffers (P)
Bond Estimate Request (BER)
Draft Groundwater Management Plan (D -GWMP)
Final Groundwater Management Plan (F -GWMP)
Aquifer Testing Work Plan (ATWP)
Groundwater Assessment Report (GWAR)
Architectural Review Board (ARB)
ARB2007 -00044
Other: Please explain
(For staff use only)
Submittal Code
# Copies
Distribute To:
Submittal Code
# Copies
Distribute To:
ARB
2
Brent Nelson