Loading...
HomeMy WebLinkAboutSDP200800059 Review Comments Major Amendment, Final Site Plan 2008-08-12ALg�,�� �'IRGINZ� COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road Charlottesville, Virginia 22902 -4596 Phone (434) 296 -5832 Fax (434) 972 -4126 Project: SDP - 2008 - 00059, Oliva and Son Major Site Plan Amendment Plan preparer: Mr. Tim Miller, PE (fax 434.979.1681) Owner or rep.: Richard A Oliva and Sons (fax unknown) Date received: (Rev. 2) 6 August 2008 (plan signed 5 August 2008) (Rev. 1) 28 May 2008 7 April 2008 (plan dated 3 April 2008) Date of Comment: (Rev. 2) 12 August 2008 (Rev. 1) 10 June 2008 2 May 2008 Engineer: Phil Custer The major site plan amendment for the Olivia and Sons has been reviewed. Because the application is a major amendment to an existing site plan, the following comments are final site plan comments. A. SDP - 2008 -00059 ,i . h vv r u plan for this property will need to be approved before the site plan can be. No information regarding the water protection plan for the proposed addition has been provided. Detention appears to be provided for the industrial park through the use of a facility adjacent to the FedEx facility. However, the building addition will increase the discharge from the site into the downstream system. The applicant must either perform an analysis of the downstream storm sewer network, or provide onsite detention. Stormwater quality will also need to be considered in the WPO plan. (Rev. 1) A WPO plan has been received for water quality measures but not for erosion and sediment control. The applicant claims that land disturbances will be under 10,000sf and will not require an ESC plan. Comments regarding the WPO plan will appear in a separate letter. (Rev. 2) Comment has been addressed. 2. Please show all existing utility lines on the plan. (Rev. 1) Comment not addressed. I do not see where the underground electric line is located. (Rev. 2) Comment has been addressed. 3. Sight distance needs to be shown from the parking lot entrance onto Five Springs Road. It appears it may be necessary to adjust the grading on site to obtain adequate sight distance looking to the north. A vertical profile of the sight line may be required. (Rev. 1) The required sight distance for this entrance is 10 x the speed limit of the road, not 100ft. After a closer inspection, it does not appear that adequate sight distance is present at this entrance. But since no improvements will be made to the existing entrance and parking areas, correcting the sight distance issue will not be required with this plan. [DM] 4. It appears a dumpster or trash compactor is needed for the site. Please provide one on the plan. (Rev. 1) The dumpster pad must be placed so that water does not run through, but away from, the pad. The proposed location would also limit the available sight distance for the entrance as well. [18- 4.12.19.b] (Rev. 2) Comment has not been addressed. The ordinance requires 8ft of the concrete pad in front of the dumpsters. CG -6 curb is not designed to withstand the loads of a garbage truck. 5. (Rev., )mment has been addressed. File: E2_pmj_PBC_08 -00059 Oliva and Sons