HomeMy WebLinkAboutSDP200800135 Review Comments Major Amendment, Preliminary Plan 2008-10-07Albemarle County
Service Authority
Serving ♦ Conserving —
TO: Megan Yaniglos
FROM: Gary Whelan, Civil Engineer
DATE: September 25, 2008
RE: Site Plan Technical Review for: BB & T Bank (Crozet) - Major
SDP200800135
TM 56 -110
The below checked items apply to this site.
X 1. This site plan is within the Authority's jurisdictional area for:
X A. Water and sewer
B. Water only
C. Water only to existing structure
D. Limited service
X 2. A 12 inch water line is located approximately 85' distant.
3. Fire flow from, nearest public hydrant, located distant from this site plan, is
Gpm + at 20 psi residual.
X 4. An 8 inch sewer line is located approximately 100' distant.
5. An Industrial Waste Ordinance survey form must be completed.
X 6. No improvements or obstructions shall be placed within existing or future
easements.
7. and plans are currently under review.
8. and plans have been received and approved.
X 9. No plans are required.
10. Final and plans are required for our review and approval prior to
granting tentative approval.
11. Final site plan may /may not be signed.
12. RWSA approval for water and /or sewer connections.
13. City of Charlottesville approval for sewer.
Comments: Backflow prevention is required. Provide a plumbing fixture count and
projected flows. DEQ will need the flow numbers to certify the pump station size.
The site plan does not show or incorrectly shows:
meter locations water line size
waterline locations sewer line size
sewer line locations expected wastewater flows
easements expected water demands