Subject: Site Review Meeting Comments April 16, 2009 site review meeting
Dear Mr. Brooks:
Below are VDOT's comments on the Site Plans for the April 16'h, 2009 Site Review Committee
Meeting:
SDP - 2009 -00016 North Fork Regional Pump Station — Preliminary (Gerald Gatobu)
1. There are proffers by both the North Fork Research Park and Northpoint to add an
additional southbound lane to route 29 at the location where this plan proposes a gravity
sewer. No plans have been reviewed for the widening of the road but efforts need to be
made to avoid conflicts. If widening takes place to the outside of Route 29, a 12 foot lane
and a 13 foot shoulder will be added. Utility structures must be placed outside of these
lanes and shoulders. Proposed structures 27 and 28 appear to be conflicting. It is
recommended that if the line must be placed within the VDOT Right of Way, it is located
in the outer 3 to 5 feet of the Right of Way in accordance with VDOT's Land Use Permit
Manual, 24VAC 30- 150 -1310.
2. Final plans will need to include a pavement design and entrance profile. A detail for the
pavement widening will be required and a design for the break in the guardrail needs to
be shown on the plan.
SDP - 2009 -00017 Humnen Fertility Diagnostics —minor (Gerald Gatobu)
Final plan needs to include design and drainage details for the pipe proposed within the
existing Route 1146 Right of Way.
SDP - 2009 -00018 Blue Ridge Shopping Center — Major (Elizabeth Marotta)
An easement is needed from the existing DI on Route 250 to the first structure off the
ROW around the 24 inch pipe.
WE KEEP VIRGINIA MOVING
SDP - 2009 -00019 Lacy Mechanical Inc. — Major (Elizabeth Marotta)
No comments
SDP - 2009 -00020 Tabor Presbyterian Church Addition - Prelim (Summer Frederick)
1. The number of seats in the addition and the ITE trip generation numbers need to be
shown on the plan.
2. Sight distances need to be shown on the existing and proposed entrances in accordance
with the Minimum Standards of Entrances to State Highways 24VAC 30 -71 -130.
3. The proposed one way entrance needs to be dimensioned as shown in 24VAC -30 -71 -160
of The Minimum Standards of Entrances to State Highways Commercial/Private
Entrance Design Illustrations. The minimum width is 14 feet and the minimum radii are
12.5 feet. The selected dimensions of the entrance need to accommodate the design
vehicle and should be increased accordingly. One way signs will also need to be shown
on the plan. Recommended dimensions for curb returns can be found in Appendix F of
the VDOT Road Design Manual.
4. The two existing entrances need to be evaluated and upgraded to the current standards if
found to be substandard in accordance with the requirements of section 24VAC- 30 -71-
140.
5. Tabor Street is paved with surface course asphalt. The entrances into the site must be of
the same material as the road back to the ROW line or the easement line as indicated in
24VAC 30 -71 -80 of The Minimum Standards of Entrances to State Highways.
6. Profiles for entrances need to be shown as a CG -11 standard.
7. Entrance pipes should be a minimum of 15 inches in diameter for all entrances. In order
to approve the use of 12 inch pipes, a hydraulic analysis will need to be submitted
showing the 12 inch pipe will not cause water to overtop the road in significant storm
events as described in VDOT's Drainage Manual section 8.3.3.1.
SDP - 2009 -00022 Preddv Creek Park Imurovements - Preliminary (Summer Frederick
1. The connection to Route 810 needs to show a profile in accordance with the CG -11
standard.
2. Erosion control stone should be placed at each end of the proposed pipe.
3. Sight distances need to be shown at the proposed entrance in accordance with the
requirements of The Minimum Standards of Entrances to State Highways, 24VAC 30 -71-
130.
SDP - 2009 -00022 Preddv Creek Park Imurovements - Preliminary (Summer Frederick
1. The connection to Route 641 needs to show a profile in accordance with the CG -11
standard.
2. Erosion control stone should be placed at the oulet end of the proposed pipe.
3. Sight distances need to be shown at the proposed entrance in accordance with the
requirements of The Minimum Standards of Entrances to State Highways, 24VAC 30 -71-
130.
SUB - 2009 -00049 Free Bridle Subdivision —Final (Patrick Lawrence)
Access easements should be provided from Olympia Drive to TMP78 -9A, Residue TMP -
78-57B and TMP 78 -10A through the proposed lots E, F and Residue of TMP -78 -11 for
WE KEEP VIRGINIA MOVING
future access of these properties and allow Access Management Regulations spacing
standards on route 250.
SUB - 2009 -00047 Johnson Property -Final (Gerald Gatobu)
No comments
Please request the applicants provide a written description of revisions with re- submissions. If you
have any questions or comments, please contact me prior to sharing these comments with the
applicants.