Project: Kingdom Hall of the Jehovah's Witness [SDP201000046,
WP0201000034]
Plan preparer: William Moore [wmoore @balzer.cc]
Owner or rep.: East Congregation of Jehovah's Witnesses; Morgan Davis ETAL TRS
Plan received date: 15 June 2010
Rev. 1: 20 July 2010
Date of comments: 1 July 2010
Rev. 1: 27 July 2010
Reviewer: John P. Diez — Current Development - Engineering Technician
A. Final site plan (SDP201000046)
1. .'lease provide the application number of the previously approved site plan that this plan is
amending.
(Rev. 1) Comment has been addressed.
2. All proposed slopes steeper than 3:1 must have low maintenance (not grass) ground cover
specified on the plan.
(Rev. 1) Comment has been addressed.
3. All entrances must have VDOT designations (PE -1, CG -9a, etc.)
(Rev. 1) Comment has been addressed.
4. VDOT approval must be obtained for any plan affecting right -of -way.
(Rev. 1) Comment has not been addressed.
5. Please clarify arrow stripping in the parking area.
(Rev. 1) Comment has been addressed.
B. Stormwater Management Plan (WP0201000034).
6. Please provide a completed copy of the standard stormwater maintenance agreement and fee for
recordation for any stormwater management facilities.
(Rev. 1) Comment has been acknowledged.
7. Please label STR #3 and #4 on the profile.
(Rev. 1) Comment has been addressed.
8. Please replace the sidewalk turn -down with a CG -2 and shift 6" out to allow the minimum 5'
width of sidewalk.
(Rev. 1) Comment has been addressed.
9. Please show all utility crossings on the profiles.
(Rev. 1) Comment has been addressed.
10. Minimum pipe sizes into and out of the facility must be 15" diameter for maintenance.
(Rev. 1) Comment has been addressed.
11. It appears that the some of the runoff in post - development is now flowing to a SWM facility. The
run -off from DA #2 must be captured for stormwater management treatment.
(Rev. 1) Comment has been addressed.
Engineering Review Comments
Page 2 of 2
12. With the added impervious from DA #2, please revise the size for the biofilter. If the facility is to
treat 50% removal rate, then the first 0.5" of runoff is to be treated. Please size the biofilter using
the 2.5% of the total impervious area. In addition:
- Please provide 2.5' of sand /soil media.
- The floor of the biofilter must be flat (0% slope)
- Please provide 1' — 1.5' of stone drain in geotech fabric under media, with 6" perforated
pipe to daylight.
- Please provide 1' ponding depth.
Please refer to the SWMH Section 3.11A and 5 -6.1 and the Design Standards Manual for specs.
and details.
(Rev. 1) Comment has been addressed.
C. Erosion Control Plan (WPO201000034)
13. Please provide a stockpile location.
(Rev. 1) Comment has been addressed.
14. Please provide a staging and parking area.
(Rev. 1) Comment has been addressed.
15. Please show on the detail or plan that the wet storage side slope is 1:1 or flatter.
(Rev. 1) Comment has been addressed.
16. Please extend the diversion dike towards the northeast side of the proposed building.
(Rev. 1) Comment has been addressed.
17. Please provide a construction entrance prior to #6 of the construction sequence. Protection must be
provided for all stages of construction.
(Rev. 1) Comment has been addressed.
The Erosion & Sediment Control and Stormwater Management Plans (WPO201000024)
submitted 20 July 2010 have received Engineering Review and meet Albemarle County minimum
checklist items for approval. Please submit 5 paper copies of the Plan to Current Development
Engineering.
The E &SC bond amount is $13,600. The SWM bond amount is $17,700. The forms and
instructions to post the Water Protection Ordinance Bond can be found on the Community
Development Department Web site on www.albemarle.oig.
A completed copy of the Standard Stormwater Maintenance Agreement and fee for recordation for
the stormwater facilities is required prior to final approval. [17-304E] The forms and instructions
can be found on the Community Development Department Web site on www.albemarle.or ,-.
You may contact Ana Kilmer (Albemarle County Department of Community Development) at ext.
3246 for further information on bonding procedures and Maintenance Agreements.
Once the E &SC bond and the SWM bond have been posted, you may contact the Department of
Community Development to arrange a pre - construction meeting with a County Erosion &
Sediment Control Inspector. Should the County Inspector find the limits of disturbance increased
or the need for additional control measures required to protect the site, additional fees will be
required.