HomeMy WebLinkAboutARB201200047 Review Comments Miscellaneous Submittal 2012-07-09ARCHITECTURAL REVIEW BOARD STAFF REPORT
Project #/Name
ARB- 2012 -47: Fresh Market
Review Type
Final Review of a Site Development Plan
Parcel Identification
Tax Map 61, Parcel 123
Location
502 Albemarle Square, at the south end of the Albemarle Square Shopping Center, at the northeast corner of the
intersection of Rt. 29 and Rio Road.
Zoned
Planned Development Shopping Center (PDSC), Entrance Corridor (EC)
Owner /Applicant
Rio Associates Limited Partnership /TFF Architects & Planners LLP (Ginna Freyaldenhoven)
Magisterial District
Rio
Proposal
To renovate the Circuit City retail space into a Fresh Market store.
Context and Visibility
The space to be renovated is located at the south end of the Albemarle Square Shopping Center, approximately 500'
from the Route 29 EC and 270' from the Rio Road EC. The site is visible from the Rio Road EC, but visibility of the
walls is somewhat limited by the fact that the building sits considerably lower than the road. This position does allow,
however, for views of the rooftop equipment from Rio Road. Visibility from Route 29 is limited by the buildings that
stand along the EC frontage and the retaining wall that stands on the east side of 29.
ARB Meeting Date
July 16, 2012
Staff Contact
Margaret Maliszewski
PROJECT HISTORY
DATE
APPLICATION/REVIEW TYPE
RESULT
April 2, 2012
ARB- 2012 -25 Preliminary review
The ARB provided preliminary comments. See the action letter at the end of this
report.
ANALYSIS
REF
GUIDELINE
4/2/2012 ARB COMMENT
ISSUE
RECOMMENDATION
9
Building forms and features, including
Revise the central parapet so
A building section has been
None.
roofs, windows, doors, materials,
that the view from the back is
provided to clarify the detailing of
colors and textures should be
of a finished architectural piece
the central parapet. The back of
compatible with the forms and features
rather than a wall built to hold a
the parapet will be faced with
of the significant historic buildings in
sign. Carry the cornice around
EIFS to match the front and sides,
the area, exemplified by (but not
and provide an EIFS surface for
and the cornice will carry around
limited to) the buildings described in
the back.
from the front to the sides.
Appendix A [of the design guidelines].
The standard of compatibility can be
There was support for Alternate
The blankness of the side elevation
met through scale, materials, and
Side Elevation 3. There was
has been addressed with the
forms which may be embodied in
continued concern for the
addition of a series of fiber cement
architecture which is contemporary as
remaining blankness.
panels. The panels sufficiently
well as traditional. The replication of
relieve the blankness of the
important historic sites in Albemarle
elevation.
County is not the objective of these
guidelines.
Generally, EIFS colors should
have greater contrast.
The darker of the two EIFS colors
has been revised to a darker shade
13
Any appearance of "blankness"
resulting from building design should
of tan for greater contrast.
be relieved using design detail or
vegetation, or both.
Provide a view of the building
A photosimulation of the south
as seen by cars entering the site
elevation of the building as
from Rio Road.
viewed from the Rio Road EC has
been provided. It suggests that the
proposed treatment of fiber cement
panels will have an appropriate
appearance.
17
Accessory structures and equipment
Indicate on the plan the
The roof plan shows that the
None.
should be integrated into the overall
locations and sizes of proposed
equipment has been consolidated
plan of development and shall, to the
rooftop equipment. Consolidate
into one large area that is screened
extent possible, be compatible with the
equipment to the greatest extent
by a 7'4" -tall screen and two
building designs used on the site.
possible. Ensure that equipment
is fully screened, without
smaller areas with 4'4" -tall
screens. An individual exhaust fan
18
The following should be located to
eliminate visibility from the Entrance
requiring overscaled screens.
outside these three areas is also
Corridor street. If, after appropriate
surrounded by a screen. The
siting, these features will still have a
Provide before /after images of
elevations show the four proposed
negative visual impact on the Entrance
the mechanical equipment
screens and a note indicates that
Corridor street, screening should be
view.
the equipment will be completely
provided to eliminate visibility.
hidden by the screens. The screens
e. Mechanical equipment,
are proposed to be constructed of
metal in Sierra Tan, a color that
19
Screening devices should be
compatible with the design of the
coordinates with the other
buildings and surrounding natural
proposed building colors. The
vegetation and may consist of:
photosimulation shows the
a. Walls, b. Plantings, and c. Fencing.
proposed view from the Rio Road
EC. It suggests that the
consolidation of the equipment
and the proposed screens will
significantly improve the view
from the EC.
21
The following note should be added to
Add the following note to the
A note stating, "No rooftop
Add the following note to
the site plan and the architectural plan:
plans: "Visibility of all
equipment shown shall exceed the
the plans: "Visibility of all
"Visibility of all mechanical
mechanical equipment from the
screen wall heights indicated on
mechanical equipment
equipment from the Entrance Corridor
Entrance Corridor shall be
this plan." This is not the standard
from the Entrance
shall be eliminated."
eliminated."
wording.
Corridor shall be
eliminated."
23
Light should be shielded, recessed or
Provide the fixture cut sheets
Cut sheets have been provided and
None.
flush - mounted to eliminate glare. All
on the plan to clarify the lumen
fixture information appears on
fixtures with lamps emitting 3000
output of the proposed wall
Sheet Al. Two fixture types are
lumens or more must be full cutoff
fixtures.
proposed. One is a tall and narrow
fixtures.
wall sconce proposed for the stone
pilasters. The other is an 18"
25
Light should have the appearance of
white light with a warm soft glow;
square fixture with a silver finish
however, a consistent appearance
for the housing and 4 central
throughout a site or development is
illuminated "windows ". Both
required. Consequently, if existing
fixtures have fluorescent lamps.
lamps that emit non -white light are to
remain, new lamps may be required to
match them.
29
The following note should be included
Add the note to the plan.
The note has been added to Sheet
None.
on the lighting plan: "Each outdoor
Al.
luminaire equipped with a lamp that
emits 3,000 or more initial lumens
shall be a full cutoff luminaire and
shall be arranged or shielded to reflect
light away from adjoining residential
districts and away from adjacent roads.
The spillover of lighting from
luminaires onto public roads and
property in residential or rural areas
zoning districts shall not exceed one
half footcandle."
36
Landscaping of buildings and other
Consider adding a planting bed
The drawings have been
None.
structures:
with trees along the side (south)
coordinated regarding the
a. Trees or other vegetation should be
elevation to relieve the
sidewalk. A planting bed has not
planted along the front of long
blankness of the wall.
been provided along the south
buildings as necessary to soften the
elevation due to conflicts with
appearance of exterior walls. The
Coordinate the drawings
existing parking and travelways.
spacing, size, and type of such trees or
regarding the sidewalk on the
vegetation should be determined by the
south elevation.
length, height, and blankness of such
walls.
b. Shrubs should be used to integrate
the site, buildings, and other structures;
dumpsters, accessory buildings and
structures; "drive thru" windows;
service areas; and signs. Shrubs should
measure at least 24 inches in height.
SIGNS
4d
Lettering should be in proportion to
Coordinate all drawings
The west end of the south
None.
the sign and the building for visual
regarding sign size.
elevation has been divided into
clarity and overall balance. Proportion
three bays. The sign has been
of lettering includes font (size) and
located near the top of the center
typeface (style).
bay, where it has a balanced,
integrated appearance.
Revise the side elevation and
Sign sizes have been coordinated.
the position of the sign on that
Sheet Al shows a frame around
elevation to result in a sign
the sign on the side elevation but
location that is fully integrated
the applicant has indicated that the
with the architectural design.
frame is no longer proposed.
9e
i. External illumination is preferred for
Add this note to the sign
The note has been added to the
None.
wall signs.
drawings: The level of
sign drawings.
illumination provided by the
LED lights... by a single stroke
of 30 milliamp (ma) neon.
SUMMARY OF RECOMMENDATIONS
Staff recommends the following as the primary points of discussion:
1. The treatment for blankness on the south elevation
2. Mechanical equipment, the view from Rio Road
Staff recommends approval with the following conditions:
1. Add the following note to the plans: "Visibility of all mechanical equipment from the Entrance Corridor shall be eliminated."
TABLE A
This report is based on the following submittal items:
Sheet #
Drawing Name
Drawing Date/Revision Date
Al
ARB Final Review Submittal (in color w/ material samples and in b /w)
4 -9 -12
A0.0
Fixture Reference Plan
May 18, 2012
C1.0
Existing Conditions and Demolition Plan
March 23, 2012
C2.0
Layout Plan
March 23, 2012
C3.0
Grading and Erosion Control Plan
March 23, 2012
C4.0
Erosion Control Notes and Details
March 23, 2012
C4.1
Notes and Details
March 23, 2012
1 of 2
Sign Elevations
04 -05 -12
2 of 2
Sign Details
04 -05 -12
-
Roof /Equipment Screening Plan
-
-
Section through high parapet at entry
-
-
Views from Rio Road entrance: Current and photosimulation of proposed
renvoation
-
-
Winona Lighting Aaron Series Mentor 375 wall sconce cut sheet
-
-
Indessa Lighting 522 Wet Location Window Box cut sheets
-
-
Assorted site photos
-
ARB ARPIL 2, 2012 ACTION LETTER
Lrf2C;l1�ZA
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 22902 -4596
Phone (434) 296 -5832 Fax (434) 972 -4126
April 6, 2012
TFF Architects & Planners LLP
C/O Ginna Freyaldenhoven
300 N. Greene St. Ste 285
Greensboro, Nc 27401
RE: ARB- 2012 -25: Fresh Market
Tax Map 61, Parcel 123
Dear Ms. Freyaldenhoven:
The Albemarle County Architectural Review Board, at its meeting on April 2, 2012, completed a preliminary review of the above -noted request to renovate
the Circuit City retail space into a Fresh Market store and to add signs on the west and south elevations. The Board offered the following comments for
the benefit of the applicant's next submittal. Please note that the following comments are those that have been identified at this time. Additional
comments may be added or eliminated based on further review and changes to the plan.
1. Revise the central parapet so that the view from the back is of a finished architectural piece rather than a wall built to hold a sign. Carry the cornice
around and provide an EIFS surface for the back.
2. There was support for Alternate Side Elevation 3. There was continued concern for the remaining blankness.
3. Generally, EIFS colors should have greater contrast.
4. Provide before /after images of the mechanical equipment view.
5. Provide a view of the building as seen by cars entering the site from Rio Road.
6. Indicate on the plan the locations and sizes of proposed rooftop equipment. Consolidate equipment to the greatest extent possible. Ensure that
equipment is fully screened, without requiring overscaled screens.
7. Add the following note to the plans: "Visibility of all mechanical equipment from the Entrance Corridor shall be eliminated."
8. Provide the fixture cut sheets on the plan to clarify the lumen output of the proposed wall fixtures.
9. Add the following note to the plan: "Each outdoor luminaire equipped with a lamp that emits 3,000 or more initial lumens shall be a full cutoff
luminaire and shall be arranged or shielded to reflect light away from adjoining residential districts and away from adjacent roads. The spillover of
lighting from luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one half footcandle."
10. Consider adding a planting bed with trees along the side (south) elevation to relieve the blankness of the wall.
11. Coordinate the drawings regarding the sidewalk on the south elevation.
12. Coordinate all drawings regarding sign size.
13. Revise the side elevation and the position of the sign on that elevation to result in a sign location that is fully integrated with the architectural design.
14. Add the following note to the sign drawings: The level of illumination provided by the LED lights will not exceed the illumination produced by a single
stroke of 30 milliamp (ma) neon.
You may submit your application for continued ARB review at your earliest convenience. Application forms, checklists and schedules are available on -line
at www.albemarle.org /ARB.
Revised drawings addressing the comments listed above are required. Include updated ARB revision dates on each drawing. Please provide a memo
including detailed responses indicating how each comment has been addressed. If changes other than those requested have been made, identify those
changes in the memo also. Highlighting the changes in the drawing with "clouding" or by other means will facilitate review and approval.
If you have any questions concerning any of the above, please feel free to call me.