HomeMy WebLinkAboutWPO201200060 Review Comments Erosion Control Plan 2012-07-12i" ,. `IRGINZP COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, Room 227 Charlottesville, Virginia 22902 -4596 Phone (434) 296 -5832 Fax (434) 972 -4126 Project: Moore's Creek WWTP Digester Improvements (WPO2012- 00060) Plan preparer: Hazen and Sawyer [fax 919 - 833 -18281 Owner or rep.: Rivanna Water & Sewer Authority [fax 434 - 293 -8858] Plan received date: 3 July 2012 Date of comments: 12 July 2012 Reviewer: Michael Koslow Review coordinator: Ellie Ray The first erosion and sediment control plan (WPO201200060) submitted 3 July 2012 has received Engineering Review and does not appear to meet Albemarle County minimum checklist items for approval. This review does not include Engineering comments for minor amendment to site development plan submitted separately as SDP2012- 00040. Those comments will be provided by the Review Coordinator. Please adequately address the following comments for final approval: Erosion and Sediment Control Plan 1) Please update General Erosion and Sediment Control Notes on sheet 4 with "General construction notes for Erosion and Sediment Control plans" as shown in County Design Standards Manual located here (see p. 23 ): < http: / /www.albemarle.org/upload /images /forms center /departments /community development/forms / design_ standards _manual/Albemarle _County_Desi gn_ Standards _Manual_02- 12- 2010.pdf> 2) Please describe the land parcels adjacent to the waste water treatment plant ( "adjacent areas ") in the erosion & sediment control narrative. 3) Please include a description of the existing soils and soils boundaries on site. Resubmittal of sheet COI from WPO200800079 is sufficient so long as it is accompanied by a description of the existing soils either on the plan sheet or in the narrative. 4) Please include the "dust control" and "temporary seeding" symbols with the proposed disturbed area described on sheet C3. 5) Please adjust label for 100 year flood plain so it displays on sheet C3. 6) If existing chlorine storage building's demolition as shown on sheet C2 includes removal of the building's foundation, please identify and include limits of disturbance with this project and include erosion and sediment control measures in this area. Engineering Review Comments Page 2 of 2 7) Stabilized silt fence outlets are not DCR approved erosion & sediment control practices. Please revise silt fence and remove the silt fence outlets shown on sheet C2. Silt fence should be placed along a contour line (suggest revising to contour elev. 370). A series of Diversion Dikes and a sediment trap between contour elev. 360 and 370 could also provide protection for this disturbed area. 8) Please clarify the limits of disturbance proposed near the digesters. Sheet C1 implies yard piping work north of digesters 1, 2, and 3 will disturb ground to north property line. If this is the case, another sediment trap NW of digester 1 may be needed to protect this watershed outlet. Please expand the limits of the partial site plan on sheet C2 and delineate the entire proposed limits of disturbance for this amendment. Current Development Engineering is available from 2:30 -4 PM on Thursdays to discuss these review comments. Please contact Michael Koslow at 434 - 296 -5832 ext. 3297 or email mkoslow @albemarle.ora to schedule an appointment. [17- 204.f] An application for an erosion and sediment control plan that requires modifications, terms, or conditions to be included in order for it to be approved shall be deemed to be withdrawn if the owner fails to submit a revised plan addressing the omitted modifications, terms or conditions within six (6) months after the owner is informed of the omitted information as provided under paragraph (B).