COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 22902 -4596
Phone (434) 296 -5832 Fax (434) 972 -4126
September 12, 2012
Frank V. Pohl, P.E.
1603 Kenwood Lane
Charlottesville, VA 22901
RE: L0R #1 for SDP - 2011 -32, Tax Map /Parcel #061 WO -02 -OB -00300
Dear Mr. Pohl,
This letter approves your submitted Letter of Revision for the above referenced site plan. The letter of revision
proposes the following changes:
1. Eliminate the oil /water separator and associated piping and canopy -pad inlets from the project. This
request is being made because the oil /water separator is not required by any State or Federal law as
confirmed with the Virginia Department of Environmental Quality (refer to attached email dated August 14,
2012).
2. As a result of eliminating the oil /water separator, adjust post - development drainage areas. Spot
elevations were revised to have positive flow off of the canopy pad. A revised WPO application has been
submitted with this Letter of Revision.
3. Eliminate "dog- house" stormwater manhole 103 and reroute drainage pipe from STIR 1.07 to the existing
manhole EX2. This was done to simplify the construction and save costs. A revised WPO application has
been submitted with this Letter of Revision to address this change.
4. Raise the finished floor elevation of the building by 4- inches to provide a minimum 1.5% slope in the front
drive lane.
5. Revise the size of Filterra Unit FT -1 to be a 8'x4' unit. The size was mislabeled in the Filterra Schedule
and Filterra documentation is submitted to show the 8'x4' unit will allow up to 0.22 acres in contributing
drainage area, which is what is draining to the unit.
Engineering and inspections both reviewed the proposed changes and each had no objection. The associated
WPO application (WPO 201200077) has also been approved by engineering.
This is the first (1s`) Letter of Revision for this site. Three (3) Letters of Revision are allowed, after which all
required changes must submitted in the form of a site plan amendment.
Sincerely,
Ellie Carter Ray, PLA, ASLA
Senior Planner
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902 -4596
Phone: (434)296 -5832 Ext 3432
Attachments: Letter of Request
Site Plan Change
POFIL CONSULTING, LLC
August 27, 2012
Ellie Ray, CLA, Senior Planner
County of Albemarle
Division of Zoning and Current Development
401 McIntire Road
North Wing
Charlottesville, VA 22902
RE: Greenbrier 7- Eleven (SDP 2011 -00032)
Letter of Revision #1
Dear Ms. Ray:
Attached please find the following documents in support of a request for a Letter of Revision for the
referenced project.
1. Letter or Revision application and $100 fee.
2. Application for. Review of E &SC Plan and SWM /BMP Plan amendment and associated fee in the
amount of $360.
3. 6 copies of the revised drawings (4 copies are for the LOR application and 2 copies are for the
E &SC /WPO application). Note that not all drawings have been submitted, just the ones that
have been revised.
This Letter of Revision is being submitted for the following changes to the approved site development
plan:
1. Eliminate the oil /water separator and associated piping and canopy -pad inlets from the project.
This request is being made because the oil /water separator is not required by any State or
Federal law as confirmed with the Virginia Department of Environmental Quality (refer to
attached email dated August 14, 2012).
2. Asa result of eliminating the oil /water separator, adjust post - development drainage areas. Spot
elevations were revised to have positive flow off of the canopy pad. A revised WPO application
has been submitted with this Letter of Revision.
3. Eliminate "dog- house" stormwater manhole 103 and reroute drainage pipe from STIR 107 to the
existing manhole EX2. This was done to simplify the construction and save costs. A revised WPO
application has been submitted with this Letter of Revision to address this change.
1.603 KENWOOD LANE
CHARLOTTESVILLE, VA 22901
T: 434- 466 -7458
F: 434 - 295 -6528
EMAIL: FRANK @POHLCONSULTINGLI -c.COM
GREENBRIER 7- ELEVEN
REVIEW COMMENT RESPONSES
Page 2 of 2
4. Raise the finished floor elevation of the building by 4- inches to provide a minimum 1.5% slope in
the front drive lane.
5. Revise the size of Filterra Unit FT -1 to be a 8'x4' unit. The size was mislabeled in the Filterra
Schedule and Filterra documentation is submitted to show the 8'x4' unit will allow up to 0.22
acres in contributing drainage area, which is what is draining to the unit.
If you have any questions or comments, please do not hesitate to let me know.
Sincerely,
y�
Frank V. Pohl, P.E.
Pohl Consulting, LLC
Ellie Ray
From: Frank Pohl [frank @pohlconsultingllc.com]
Sent: Tuesday, August 14, 2012 12:48 PM
To: Ellie Ray
Cc: Max Greene; 'Gordon Sutton'; EPG333 @aol.com; 'Robert Menasco'
Subject: FW: Oil Water Separators
Ellie,
Please refer to email from DEQ below stating an oil /water separator is not required by DEQ. Are we clear now to
proceed with removing this from our plans?
Thanks,
Frank
Frank V. Pohl, PE, LEED AP BD +C
Pohl Consulting, LLC
1603 Kenwood Lane
Charlottesville, VA 22901
434 - 466 -7458
CONFIDENTIALITY NOTICE:
This message and any attachments are solely for the intended recipient and may contain confidential or privileged information. If you are not the
intended recipient, any disclosure, copying, use, or distribution of the information included in this message and any attachments is prohibited. if
you have received this communication in error, please notify us by reply e -mail and immediately and permanently delete this message and any
attachments. Thank you.
From: Kiracofe, Brandon (DEQ) [mailto: Brandon. KiracofeCa)deq.virginia.gov]
Sent: Tuesday, August 14, 2012 12:36 PM
To: frank(ftohlconsultinallc.com
Cc: Clark, Gregory (DEQ)
Subject: RE: Oil Water Separators
Mr. Pohl,
DEQ does not regulate storm water generated at retail facilities and does not require an oil -water separator for the type of
retail facility described below. A permit from DEQ would be required to discharge process wastewater such as
wastewater generated by washing the fueling pads or washing vehicles at the facility. Please let me know if you have any
questions.
Sincerely,
Brandon Kiracofe
Brandon D. Kiracofe
Water Permits Manager
DEQ - Valley Regional Office
P.O. Box 3000
Harrisonburg, VA 22801
(540) 574 -7892
(540) 574 -7878 (fax)
brandon.kiracofe@deq.virszinia.gov
From: Frank Pohl rmailto:frank @pohlconsultin Ilq c.com]
Sent: Monday, August 13, 2012 4:58 PM
To: Clark, Gregory (DEQ)
Subject: Oil Water Separators
Greg,
I am the civil engineer for a client who is redeveloping an existing convenience store /gas filling station — they are
demolishing the entire site, removing the old tanks, installing new tanks, and building a new store, including canopy and
islands.
Albemarle County has asked me to show that an oil -water separator is not required for this type of facility. There will be
10 fueling stations and my understanding is that the intent of the OWS would be to capture the oil /gas from the canopy
pad incase of a spill (we are already providing the required stormwater treatment for the site via other measures). It is
also my understanding that the plumbing code excludes stations that do not service vehicles and this facility DOES NOT
service vehicles.
Any help on clearing up this issue is appreciated.
Thank you,
Frank
Frank V. Pohl, PE, LEED AP BD +C
Pohl Consulting, LLC
1603 Kenwood Lane
Charlottesville, VA 22901
434 - 466 -7458
CONFIDENTIALITY NOTICE:
This message and any attachments are solely for the intended recipient and may contain confidential or privileged information. If you are not the
intended recipient, any disclosure, copying, use, or distribution of the information included in this message and any attachments is prohibited. If
you have received this communication in error, please notify us by reply e -mail and immediately and permanently delete this message and any
attachments. Thank you.