HomeMy WebLinkAboutSUB201300054 Review Comments Road Plan and Comps. 2013-05-08Albemarle County Service 'Auth4rity Serving ♦ Conserving April 24, 2013 Roudabush, Gale & Assoc., Inc. Attn: Mr. Bill Ledbetter, L.S. 914 Monticello Road Charlottesville, Virginia 22902 Re: Old Trail Village Block 29A & 35A Dear Bill: We have reviewed the plans entitled "Old Trail Village Block 35A & Block 29A Final Construction Plan" dated April 5, 2013. The following comments need to be addressed: Sheet 1 1. Provide water data sheet. 2. Flow Acceptance will be required from the Rivanna Water and Sewer Authority (RWSA). The ACSA will submit a request to the RWSA once a schedule for build -out and number of units have been provided by the developer. 3. Revised master plan showing water and sewer for Old Trail Village is required prior to plan approval. Sheet 2 1. Sewer elevations for manhole lids and inverts do not match as- builts submitted by Timmons Group for the Lickinghole Creek Sanitary Sewer Extension. Sheet 3 1. Label existing manholes as shown with the prefix Lickinghole -. 2. Show the 12 -inch gate valve that was cut in during the Block 23 project. 3. Contractor will be required to remove gate valve and stub -out directed at this site since it will not be utilized. 4. All water meters should be placed between the sidewalk and curbing. 5. Revise sewer lateral for Lot 2 so that the angle between the lateral and the downstream sewer main is at least 90 °. 6. Sewer lateral for Lot 4 should connect to manhole across the road. 7. Provide sewer lateral for Lot 5. 8. It is unclear what property the lateral shown at the end of Golf View Drive will serve. 9. Provide gate valve and blow -off at the end of Golf View Drive. 168 Spotnap Road • Charlottesville, VA 22911 • Tel (434) 977 -4511 • Fax (434) 979 -0698 www.serviceauthority.org 10. The fire hydrant along Golf View Drive should be relocated to the western side of the roadway. 11. Add a fire hydrant and future gate valve at the end of Golf View Drive. 12.Add a gate valve near Storm Structure 5 since this section will eventually be looped. Sheet 5 1. Keep trees a minimum of ten feet away from ACSA utilities. Sheet 6 1. Show water service and sewer lateral crossings on storm sewer profiles. 2. What is the 6" S/L label near Station 17 +00? 3. Should the 6" W/L be a water service near Station 5 +50? 4. Revise the reference to PVC W/L under Storm Structure 10. Sheet 7 1. Provide recently revised ACSA General Water and Sewer Notes. I can email this to you at your convenience. Sheet 8 1. There appears to be adequate fall beyond ST #1. Would it be possible to shift this down the hill and allow the water main to cross above the storm sewer? Sheets 9 -13 1. Eliminate these sheets from our submittal. If you have any questions concerning this review, feel free to contact me at (434) 977 -4511, Ext. 114. Sincerely, ;Zv- Jeremy M. Lynn, P.E. Senior Civil Engineer JML /dbh 050601 OldTrai IV i IlageBlks29A &35ACommentLtr042413