HomeMy WebLinkAboutSDP201300029 Review Comments Minor Amendment 2013-06-11Maude Ginty
Service Auth6rity
TO: Megan Yaniglos
FROM: Alexander J. Morrison, EIT, Civil Engineer
DATE: June 11, 2013
RE: Site Plan Technical Review for: SDP - 2013 -029: Three Notch'd Center - Minor
The below checked items apply to this site.
✓ 1. This site plan is within the Authority's jurisdictional area for:
✓ A. Water and sewer
B. Water only
C. Water only to existing structure
D. Limited service
✓ 2. A 6 inch water line is located approximately 10 distant.
3. Fire flow from, nearest public hydrant, located distant from this site plan, is
Gpm + at 20 psi residual.
✓ 4. An 8 inch sewer line is located on site).
5. An Industrial Waste Ordinance survey form must be completed.
✓ 6. No improvements or obstructions shall be placed within existing or future
easements.
7. and plans are currently under review.
8. and plans have been received and approved.
9. No plans are required.
10. Final and plans are required for our review and approval prior to
granting tentative approval.
11. Final site plan may /may not be signed.
12. RWSA approval for water and /or sewer connections.
13. City of Charlottesville approval for sewer.
✓ Comments:
• Correctly show which buildings the existing 4 water meters located along the frontage of
TMP #56A3 -9 serve.
• Provide water meter for "Auto Laundry/ 1 Story Car Wash."
• Provide "proposed grade" profile view of existing ACSA sanitary sewer on site.
• Provide information regarding building uses so the ACSA can determine if grease
interceptors are required.
• Call out any existing tap that will not serve a proposed water meter "to be abandoned at
the main."
• Provide fixture counts so the proposed water meters can be sized. If fixture counts are not
available please change note on water meter to "to be sized by ACSA."
168 Spotnap Road • Charlottesville • VA 22911 • Tel (434) 977 -4511 • Fax (434) 979 -0698
www.serviceauthoriy.org