Loading...
HomeMy WebLinkAboutSDP201300045 Review Comments Minor Amendment 2013-09-10Maude Ginty Service Auth6rity TO: Ellie Ray Carter FROM: Alexander J. Morrison, Civil Engineer DATE: September 6, 2013 RE: Site Plan Technical Review for: SDP201300045: SOCA Fieldhouse - Minor Amendment The below checked items apply to this site. ✓ 1. This site plan is within the Authority's jurisdictional area for: ✓ A. Water and sewer B. Water only C. Water only to existing structure D. Limited service ✓ 2. An 12 inch water line is located approximately 140' distant. 3. Fire flow from, nearest public hydrant, located distant from this site plan, is Gpm + at 20 psi residual. ✓ 4. A 8 inch sewer line is located approximately ON SITE distant. 5. An Industrial Waste Ordinance survey form must be completed. ✓ 6. No improvements or obstructions shall be placed within existing or future easements. 7. and plans are currently under review. 8. and plans have been received and approved. 9. No plans are required. 10. Final and plans are required for our review and approval prior to granting tentative approval. 11. Final site plan may /may not be signed. 12. RWSA approval for water and /or sewer connections. 13. City of Charlottesville approval for sewer. ✓ Comments: • Update the water meter service line. The new configuration will incorporate a 4" tap and 4" gate valve before downsizing and using copper. Contact Alexander Morrison ( amorrison (a-)_serviceauthority.org) for an updated detail to include in the plans. • The offsite easement for the water meter must be recorded prior to the ACSA setting a water meter. The plat and deed require ACSA review and approval prior to signing and recordation. • Correctly show fitting and bends on the fire line (specifically at the 90 degree bend). • Revise the proposed easement extents. ACSA ownership of the fire line ends after the gate valve. • No fill is to be placed over the existing ACSA sewer main. 168 Spotnap Road • Charlottesville • VA 22911 • Tel (434) 977 -4511 • Fax (434) 979 -0698 www.serviceauthority.org Searle Conty Service Auth rity • Submit updated fixture counts for water meter size verification and connection fee quoting. • Further ACSA commenting and construction review is contingent on the resolution of Fire and Rescue's comments (specifically for additional fire hydrants). If additional fire hydrants are installed it will require a full construction review by the ACSA. If no hydrants are installed then no construction review is required separate from the county review process. 168 Spotnap Road • Charlottesville • VA 22911 • Tel (434) 977 -4511 • Fax (434) 979 -0698 www.serviceauthority.org