HomeMy WebLinkAboutSDP201300043 Review Comments Initial Site Plan 2013-08-21Maude Ginty Service Auth6rity TO: Ellie Ray FROM: Alexander J. Morrison, EIT, Civil Engineer DATE: August 20, 2013 RE: Site Plan Technical Review for: SDP201300043: Coles Import Specialists - Initial Site Plan TMP# 04500- 00- 00 -100B0 The below checked items apply to this site. ✓ 1. This site plan is within the Authority's jurisdictional area for: ✓ A. Water and sewer B. Water only C. Water only to existing structure D. Limited service ✓ 2. An 8 inch water line is located approximately 55' distance from this site plan. 3. Fire flow from, nearest public hydrant, located distant from this site plan, is Gpm + at 20 psi residual. ✓ 4. An 8 inch sewer line is located approximately (on site). 5. An Industrial Waste Ordinance survey form must be completed. ✓ 6. No improvements or obstructions shall be placed within existing or future easements. 7. and plans are currently under review. 8. and plans have been received and approved. 9. No plans are required. 10. Final water and sewer construction plans required for construction approval. 11. Final site plan may /may not be signed. 12. RWSA approval for water and /or sewer connections. 13. City of Charlottesville approval for sewer. ✓ Comments: • The ACSA will require a separate water meter for the proposed building. • The ACSA recommends that separate laterals be utilized for sanitary sewer service. • The ACSA account records reflect 660 Rio Road as a water only account. If the applicant believes they are currently on public sanitary sewer the ACSA can conduct further testing to verify. • Fixture counts should be submitted to the ACSA when available so the water meter can be sized and connection fees can be calculated. 168 Spotnap Road • Charlottesville • VA 22911 • Tel (434) 977 -4511 • Fax (434) 979 -0698 www.serviceauthoriy.org YlAGIl`11A County of Albemarle Department of Community Development Project: Cole's Import Specialist — Initial (SDP- 2013 - 00043) Plan preparer: Meridian Planning Group, LLC Owner or rep.: Clarence William Green Plan received date: 23 July 2013 Date of comments: 19 August 2013 Reviewer: Michelle Roberge The engineering comments regarding the initial site plan application for Cole's Import Specialist are provided below. Comments to address for Initial Site Plan: 1. Please provide VDOT's CG -11 commercial entrance per section 4.12.17 (b). 2. It appears that no storm drain system is proposed and all pavement runoff will be diverted by pavement surface, then to a concrete flume, then to a biofilter. Please show a storm drain system with an outfall pipe to biofilter. Two possible locations for DI s are the NE corners of parking lots. 3. Also provide VDOT Standard CG -6. 4. For parking spaces that are only 16' in length, please show a 2' unobstructed overhang per 4.12.16(c)6. 5. Please dimension the handicap parking space and verify it meets standard per 4.12.16(c)5. 6. The plans do not appear to be at (1) inch is equal to (20) feet. Please print to scale. 7. For the most southern parking lot, there is a 2' median separating the parking from the travelway. Please provide, at a minimum, a 3' median. 8. It appears there is a proposed retaining wall. The limits of disturbance will encroach on TMP 45- 100A. Please show the correct limits of grading and limits of disturbance. 9. An approved WPO will be required prior to the approval of the final site plan. Also with WPO application, an adequate channel analysis from the biofilter shall be shown with adequate outfall protection. Comments to address for Final Site Plan: 1. Please provide top and bottom elevations and detail for retaining wall. 2. Please provide pavement detail per 4.12.15. 3. Please provide the permanent drainage easement and access easement for biofilter. 4. Please provide the Albemarle County general construction note. Please contact Michelle Roberge in the Engineering Dept at mroberge@albemarle.org or 434 - 296 -5832 ext. 3458 for further information. Albemarle County Service Authdirity TO: Ellie Ray FROM: Alexander J. Morrison, EIT, Civil Engineer DATE: August 20, 2013 RE: Site Plan Technical Review for: SDP201300043: Coles Import Specialists - Initial Site Plan TMP# 04500-00-00-100B0 The below checked items apply to this site. ✓ 1. This site plan is within the Authority's jurisdictional area for: ✓ A. Water and sewer B. Water only C. Water only to existing structure D. Limited service ✓ 2. An 8 inch water line is located approximately 55' distance from this site plan. 3. Fire flow from, nearest public hydrant, located distant from this site plan, is Gpm + at 20 psi residual. ✓ 4. An 8 inch sewer line is located approximately (on site). 5. An Industrial Waste Ordinance survey form must be completed. ✓ 6. No improvements or obstructions shall be placed within existing or future easements. 7. and plans are currently under review. 8. and plans have been received and approved. 9. No plans are required. 10. Final water and sewer construction plans required for construction approval. 11. Final site plan may/may not be signed. 12. RWSA approval for water and/or sewer connections. 13. City of Charlottesville approval for sewer. ✓ Comments: ▪ The ACSA will require a separate water meter for the proposed building. • The ACSA recommends that separate laterals be utilized for sanitary sewer service. • The ACSA account records reflect 660 Rio Road as a water only account. If the applicant believes they are currently on public sanitary sewer the ACSA can conduct further testing to verify. • Fixture counts should be submitted to the ACSA when available so the water meter can be sized and connection fees can be calculated. 168 Spotnap Road • Charlottesville•VA 22911 •Tel (434) 977-4511 • Fax(434) 979-0698 www.serviceauthoriy.org Nome *are 4A_OF D��I-'�illl 8 k1,10�P COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road,North Wing Charlottesville,Virginia 22902-4596 Phone(434)296-5832 Fax(434)972-4126 August 19, 2013 Tim Miller Meridian Planning Group,LLC 1413 Sachem Place, Suite 1 Charlottesville,VA 22901 RE: SDP201300043 Cole's Import Specialists—Initial Site Development Plan Dear Mr.Miller: The Site Review Committee has reviewed the development proposal referenced above. Initial comments for the following divisions of the Department of Community Development and other agencies, as applicable, are attached: Albemarle County Planning Services (Planner) Albemarle County Engineering Services(Engineer) Albemarle County Information Services(E911) Albemarle County Building Inspections Albemarle County Planning Services(Architectural Review Board)(separate) Albemarle County Department of Fire Rescue Albemarle County Service Authority(to be forwarded upon receipt) Virginia Department of Transportation Comments reflect information available at the time the development proposal was reviewed, and should not be considered final. However,the Site Review Committee has attempted to identify all issues that will be required to be resolved prior to Final Site Plan approval. The Lead Reviewer will either approve with conditions or deny the Initial Site Plan within 15 days of the Site Review Meeting. Please contact me at your earliest convenience if you have questions or require additional information. Sincerely, Ellie Carter Ray, CLA Senior Planner Planning Services • 01 ALik3 d N County of Albemarle Department of Community Development Project: Cole's Import Specialist—Initial(SDP-2013-00043) Plan preparer: Meridian Planning Group,LLC Owner or rep.: Clarence William Green Plan received date: 23 July 2013 Date of comments: 19 August 2013 Reviewer: Michelle Roberge The engineering comments regarding the initial site plan application for Cole's Import Specialist are provided below. Comments to address for Initial Site Plan: 1. Please provide VDOT's CG-11 commercial entrance per section 4.12.17 (b). 2. It appears that no storm drain system is proposed and all pavement runoff will be diverted by pavement surface,then to a concrete flume,then to a biofilter.Please show a storm drain system with an outfall pipe to biofilter. Two possible locations for DI s are the NE corners of parking lots. 3. Also provide VDOT Standard CG-6. 4. For parking spaces that are only 16' in length,please show a 2' unobstructed overhang per 4.12.16(c)6. 5. Please dimension the handicap parking space and verify it meets standard per 4.12.16(c)5. 6. The plans do not appear to be at(1)inch is equal to(20)feet. Please print to scale. 7. For the most southern parking lot,there is a 2' median separating the parking from the travelway. Please provide, at a minimum,a 3' median. 8. It appears there is a proposed retaining wall. The limits of disturbance will encroach on TMP 45- 100A. Please show the correct limits of grading and limits of disturbance. 9. An approved WPO will be required prior to the approval of the final site plan. Also with WPO application, an adequate channel analysis from the biofilter shall be shown with adequate outfall protection. Comments to address for Final Site Plan: 1. Please provide top and bottom elevations and detail for retaining wall. 2. Please provide pavement detail per 4.12.15. 3. Please provide the permanent drainage easement and access easement for biofilter. 4. Please provide the Albemarle County general construction note. Please contact Michelle Roberge in the Engineering Dept at mroberge(i,albemarle.org or 434-296-5832 ext. 3458 for further information. Review Comments Project Name: Cole's Import Specialists- Initial Initial Site Plan Date Completed: Tuesday, July 16, 2013 Reviewer: Andrew Slack Department/Division/Agency: E911 Reviews Comments: No objection. Review Status: No Objection Review Comments Project Name: Cole's Import Specialists- Initial Initial Site Plan Date Completed: Monday, July 15, 2013 Reviewer: Jay Schlothauer Department/Division/Agency: Inspections Reviews Comments: Based on plans dated July 3, 2013. No comments or conditions. Note: Due to the proximity of the west building wall to the property line, that building wall must be of 1-hour fire- rated construction. Review Status: No Objection y...Y Review Comments Project Name: Cole's Import Specialists- Initial Initial Site Plan Date Completed: Saturday, July 20, 2013 Reviewer: Robbie Gilmer Department/Division/Agency: Fire Rescue Reviews Comments: Based on plans dated 7/03/13 No objections or comments Review Status: No Objection � jRclti�� County of Albemarle Department of Community Development 401 McIntire Road, Charlottesville, VA, 22902 Phone 434 - 296 -5832 Memorandum To: Tim Miller (tmiller(a- )meridianwbe.com) From: Ellie Ray, CLA, Senior Planner Division: Planning Date: August 16, 2013 Subject: SDP 201300043 Cole's Import Specialists - Initial Fax 434 - 972 -4126 The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Subdivision /Zoning Ordinances unless otherwise specified.] 1. [32.5.1(b)] The plan shall be prepared to the scale of one (1) inch equals twenty (20) feet or to another scale approved by the agent in a particular case. Please submit plan sets that are printed to scale. 2. [32.5.2(a)] Provide the correct tax map and parcel number in all places where the TMP is listed. An incorrect TMP is listed under `Legal Reference' and on the parcel itself on Sheet 1. 3. [32.5.2(a)] Add Entrance Corridor (EC) and Airport Impact Area (AIA) to the Zoning information. 4. [32.5.2(e)] Please make sure the existing landscape features are labeled and readable on the existing conditions and landscape plans. 5. [32.5.20)] Please make sure the existing water and sewer facilities and any easements are shown and are readable. 6. [32.5.2(k)] Verify that all necessary easements for proposed water, sewer and drainage facilities have been shown on the plan. 7. [32.5.2(1)] Provide the location of any other existing or proposed utilities and utility easements including telephone, cable, electric and gas. 8. [32.5.2(n)] Clarify if any outdoor lighting is proposed; if it is, show the location(s) and provide a photometric plan. 9. [32.5.2(n) &4.12.16(c)5] Dimension the handicapped space and access aisle. 10. [4.12.16(c)6] It appears that two rows of parking have spaces that are reduced to 16' in length. Due to the scale of the drawing it is difficult to verify if the required unobstructed overhang is provided. Please verify that a minimum of 2' of unobstructed overhang is shown on the plan. 11. [32.5.2(p) & 32.7.9)] Please include a plant schedule that includes the sizes of the proposed plant material in order to verify that the minimum size requirements of 32.7.9.5(c), 32.7.9.5(e), 32.7.9.6(c), & 32.7.9.7(c) are being met. 12. [32.5.2(p) & 32.7.9.4(b)] Existing trees may be preserved in lieu of planting new plant materials in order to satisfy the landscaping and screening requirements of section 32.7.9, subject to the agent's approval. If you intend to use existing trees to satisfy any of the landscape plan requirements, please include the following: 1. Areas and other features shown on landscape plan. The landscape plan shall show the trees to be preserved, the limits of clearing, the location and type of protective fencing, grade changes requiring tree wells or walls, and trenching or tunneling proposed beyond the limits of clearing. 2. Conservation checklist. The applicant shall sign a conservation checklist approved by the agent to ensure that the specified trees will be protected during construction. Except as otherwise expressly approved by the agent in a particular case, the checklist shall conform to the specifications in the Virginia Erosion and Sediment Control Handbook, pages III -393 through III -413, and as hereafter amended. 13. [32.5.2(p) & 32.7.9.6(a)] An area of at least five (5) percent of the paved parking and vehicular circulation area shall be landscaped with trees or shrubs. Neither the areas of street trees and shrubs required by sections 32.7.9.5(d) and (e) nor shrubs planted between a parking area and the building shall be counted toward the minimum landscaped area for a parking lot. Please provide all relevant information to verify this requirement is satisfied. 14. [32.5.2(p) & 32.7.9.8] The minimum tree canopy requirement is 10 %. It appears this requirement has been met, but a note should be provided that indicates the square footage of tree canopy required and provided. Additionally, see comment #12 if this requirement is to be satisfied using existing trees. 15. [32.5.2(r)] Please include all symbols and abbreviations used on the plan in the legend. 16. [Comment] ARB approval required. 17. [Comment] If any off -site easements are required, the easement must be established or a letter of intent to grant the easement from the adjacent property owner must be provided prior to plan approval. 18. [Comment] Please clarify how the existing structure will be used. Depending on the proposed use, additional parking may be required. Please contact Ellie Ray in the Planning Division by using eray(a)albemarle.org or 434 - 296 -5832 ext. 3432 for further information. NNW° 'quire C.) County of Albemarle Department of Community Development 401 McIntire Road, Charlottesville,VA,22902 Phone 434-296-5832 Fax 434-972-4126 Memorandum To: Tim Miller(tmiller(a..meridianwbe.com) From: Ellie Ray, CLA, Senior Planner Division: Planning Date: August 16, 2013 Subject: SDP 201300043 Cole's Import Specialists- Initial The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference,which is to the Subdivision/Zoning Ordinances unless otherwise specified.] 1. [32.5.1(b)] The plan shall be prepared to the scale of one (1) inch equals twenty(20)feet or to another scale approved by the agent in a particular case. Please submit plan sets that are printed to scale. 2. [32.5.2(a)] Provide the correct tax map and parcel number in all places where the TMP is listed. An incorrect TMP is listed under'Legal Reference' and on the parcel itself on Sheet 1. 3. [32.5.2(a)] Add Entrance Corridor(EC)and Airport Impact Area (AIA)to the Zoning information. 4. [32.5.2(e)] Please make sure the existing landscape features are labeled and readable on the existing conditions and landscape plans. 5. [32.5.2(j)] Please make sure the existing water and sewer facilities and any easements are shown and are readable. 6. [32.5.2(k)] Verify that all necessary easements for proposed water, sewer and drainage facilities have been shown on the plan. 7. [32.5.2(I)] Provide the location of any other existing or proposed utilities and utility easements including telephone, cable, electric and gas. 8. [32.5.2(n)] Clarify if any outdoor lighting is proposed; if it is, show the location(s)and provide a photometric plan. 9. [32.5.2(n) &4.12.16(c)5] Dimension the handicapped space and access aisle. 10. [4.12.16(c)6] It appears that two rows of parking have spaces that are reduced to 16' in length. Due to the scale of the drawing it is difficult to verify if the required unobstructed overhang is provided. Please verify that a minimum of 2' of unobstructed overhang is shown on the plan. 11. [32.5.2(p) &32.7.9)] Please include a plant schedule that includes the sizes of the proposed plant material in order to verify that the minimum size requirements of 32.7.9.5(c), 32.7.9.5(e), 32.7.9.6(c), &32.7.9.7(c) are being met. 1 12. [32.5.2(p) &32.7.9.4(b)] Existing trees may be preserved in lieu of planting new plant materials in order to satisfy the landscaping and screening requirements of section 32.7.9, subject to the agent's approval. If you intend to use existing trees to satisfy any of the landscape plan requirements, please include the following: 1. Areas and other features shown on landscape plan.The landscape plan shall show the trees to be preserved, the limits of clearing,the location and type of protective fencing, grade changes requiring tree wells or walls, and trenching or tunneling proposed beyond the limits of clearing. 2. Conservation checklist.The applicant shall sign a conservation checklist approved by the agent to ensure that the specified trees will be protected during construction. Except as otherwise expressly approved by the agent in a particular case,the checklist shall conform to the specifications in the Virginia Erosion and Sediment Control Handbook, pages III-393 through III-413, and as hereafter amended. 13. [32.5.2(p) &32.7.9.6(a)] An area of at least five (5) percent of the paved parking and vehicular circulation area shall be landscaped with trees or shrubs. Neither the areas of street trees and shrubs required by sections 32.7.9.5(d)and (e) nor shrubs planted between a parking area and the building shall be counted toward the minimum landscaped area for a parking lot. Please provide all relevant information to verify this requirement is satisfied. 14. [32.5.2(p) &32.7.9.8] The minimum tree canopy requirement is 10%. It appears this requirement has been met, but a note should be provided that indicates the square footage of tree canopy required and provided. Additionally, see comment#12 if this requirement is to be satisfied using existing trees. 15. [32.5.2(r)] Please include all symbols and abbreviations used on the plan in the legend. 16. [Comment] ARB approval required. 17. [Comment] If any off-site easements are required, the easement must be established or a letter of intent to grant the easement from the adjacent property owner must be provided prior to plan approval. 18. [Comment] Please clarify how the existing structure will be used. Depending on the proposed use, additional parking may be required. Please contact Ellie Ray in the Planning Division by using eray @albemarle.org or 434-296-5832 ext. 3432 for further information. 2 COMMONWEALTH of VIRGINIA DEPARTMENT OF TRANSPORTATION 1601 Orange Road Culpeper, Virginia 22701 -3819 Gregory A. Whirley Commissioner of Highways August 14, 2013 Mr. Glenn Brooks Department of Engineering and Development 401 McIntire Rd. Charlottesville, VA 22902 Subject: Site Review Meeting Comments August 200' Site Review Meeting Dear Mr. Brooks: Below are VDOT's comments for items on the August 200i, 2013 Site Review Committee Meeting agenda as indicated in a memorandum dated July 12, 2013: SDP201300043 Cole's Import Specialists — Initial Site Plan (Ellie Carter Ray) 1. The site plan needs to be submitted on a standard, full size plan sheet. The reduction has not provided a standard scale. 2. The proposed entrance does not meet the access management spacing requirements for full access based on the distance to Berkmar Drive. The entrance will need to be constructed as a right - in/right -out entrance. In addition, the distance to the nearest commercial entrance to the east of this entrance should be shown on the plan. 3. The minimum width of a commercial entrance is 30' as indicated in Appendix F of the Road Design Manual. 4. The curb and gutter of the entrance should match that of Rio Road to the end of radius. 5. The pavement structure of the entrance should match that of Rio Road. 6. The entrance to the site needs to be constructed in accordance with the standard for CG -11 as indicated in the Road and Bridge Standards. 7. Based on the ADT of Rio Road, the entrance may require at a minimum a taper. An anticipated trip generation for the site needs to be provided including both the proposed automobile service facility and the existing dwelling since it appears that the dwelling will remain as indicated on the site plan. If you need additional information concerning this project, please feel free to contact me. Sincerely, AA Troy ustin, P.E. Area Land Use Engineer Culpeper District