March 31, 2014
Mr. Brent Nelson
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902
Re: SDP2013 -00046 Gillenwater Property Tier II Personal Wireless Service Facility (AT &T
Wireless 648 Dry Bridge Road)
Dear Mr. Nelson:
We have reviewed the subject facility in the field and reviewed the plans identified as AT &T site
number CV404A as submitted by BC Architects Engineers and dated 1/14/.14. Per the attached
letter from the design engineer, should there be a structural failure, the tower collapse would be
no further than 56' from the center of the structure, which would approximately 10 to 15 feet
from the edge of pavement of Route 708. Under these conditions, the fall zone of the tower
would not impact Route 708 and VDOT has no objections to the proposed facility as designed.
The applicant will need to obtain a Land Use Permit from this office for the proposed entrance
and any necessary work to be performed on the State Right -of -Way.
If you need additional information concerning this project, please feel free to contact me.
Sincerely,
Troy ustin, P.E.
Area Land Use Engineer
Culpeper District
WE KEEP VIRGINIA MOVING
BC
a r c h i r e c t s
e n g i n e e r s
March 28, 2014
Mr. Preston Lloyd
Williams Mullen
RE: CV404A
6448 Dry Bridge Road, Charlottesville, VA 22903
119.4' Monopole 1- Carrier Design Tower Specification
Mr. Lloyd,
The 119.4' tower for the above listed site will comply with the following design specifications
and criteria:
1. EIA /TIA -222G. The tower and foundation will meet the requirements outlined in the
2012 IBC.
2. Wind loading will be designed based on a minimum 90 -mph basic wind speed and a
minimum 1/2" of radial ice to design the steel structure. Designer shall contact all local
governing officials to determine if minimum standards apply.
3. Foundations will be designed in accordance with the latest version of ACI and actual
geotechnical values based on site data. Normal soils assumption will not be used.
4. Tower and foundation design calculations will be submitted to engineer for final
approval.
5. The tower and foundation shall be designed, manufactured, and constructed to have
the capacity to accommodate 1- carrier's full antenna arrays.
6. In the event of structural failure, the tower will be designed to collapse no farther than
56' from the center of the structure.
Please contact us if you have any questions or concerns.
Sincerely,
C
Christopher D. Morin, P.E.
Principal of BC Architects Engineers, PLC