Loading...
HomeMy WebLinkAboutSDP201500006 Correspondence 2015-03-18Christopher Perez From: Christopher Perez Sent: Wednesday, March 18, 2015 9:28 AM To: 'Justin Shimp, P.E.' Subject: FW: SDP201500006 Sunset Overlook - initial site plan Attachments: 11039- SunsetAvExt_11040,11038.pdf Justin, The side yard setbacks for R -4 zoning are 15 foot; however, the plan lists 10 foot. The 10 foot setback is permitted provided the provisions of Section 4.11.3 are met. Prior to final site plan/final subdivision plat approval the Fire Flow test shall be conducted and the Fire Official shall approve the reductions. Per Robbie's email below it appears they will approve your reduction in side yard setbacks. Attached is the fire flow test. Christopher P. Perez I Senior Planner Department of Community Development ICounty of Albemarle, Virginia 401 McIntire Road I Charlottesville, VA 22902 434.296.5832 ext. 3443 From: Robbie Gilmer Sent: Tuesday, March 17, 2015 6:30 PM To: Alex Morrison; Christopher Perez Subject: RE: SDP201500006 Sunset Overlook - initial site plan Alex, Thanks for the information. Chris, Fire Rescue requires 1500 gpm @ 20 psi for this site and looking at the Fire Flow test they have the needed water. Fire Rescue will approve based on the fire flow test submitted by ACSA. Thank you, Robert Gilmer Captain /Assist. Fire Marshal Albemarle County Fire Rescue 460 StageCoach Road Charlottesville, Va. 22901 Office 434 - 296 -5833 Cell 434 - 531 -6606 From: Alex Morrison [ma i Ito: amorrison(a serviceauthority.org] Sent: Tuesday, March 17, 2015 3:39 PM To: Christopher Perez; Robbie Gilmer Subject: RE: SDP201500006 Sunset Overlook - initial site plan Robbie, Attached is the fire flow test for this site plan. We were unable to obtain a 10 psi drop for the AWWA Q20 calculation because this was a 20" transmission main. Let me know if you need anything further. Chris, Please forward the fire flow test to the applicant if you are able. Thank you. Alexander J. Morrison, EIT Civil Engineer Albemarle County Service Authority 168 Spotnap Road Charlottesville, Virginia 22911 (0) 434 - 977 -4511 Ext. 116 (F) 434 - 979 -0698 Like the ACSA on Facebook at www.facebook.com /acsaconnect From: Christopher Perez [mailto:cperez(abalbemarle.org] Sent: Thursday, March 12, 2015 4:16 PM To: Robbie Gilmer Cc: Alex Morrison Subject: SDP201500006 Sunset Overlook — initial site plan Robbie, SDP201500006 Sunset Overlook — initial site plan I saw you have conducted your review and put your comments in Countyview. I have a followup question: The side yard setbacks for R -4 zoning are 15 foot; however, the plan lists 10 foot. The 10 foot setback is permitted provided the provisions of Section 4.11.3 are met. Prior to final site plan/final subdivision plat approval the Fire Flow test shall be conducted and the Fire Official shall approve the reductions. Robbie, has this happened yet? Christopher P. Perez I Senior Planner Department of Community Development ICounty of Albemarle, Virginia 401 McIntire Road I Charlottesville, VA 22902 434.296.5832 ext. 3443